You are on page 1of 3

Isolating switching amplifier

1-channel
MK13-R-EX0

Isolating switching amplifier


1-channel
MK13-R-EX0
Inc. ñ3000 Campus Drive Minneapolis, MN 55441-2656 ñPhone: 763-553-7300 ñApplication Support: 1-800-544-7769 ñFax 763-553-0708 ñwww.turck.com
ñEdition:
TURCK

7 8

III II I 5 6
4 4 4
5 £ 250 VAC/
120 VDC
Power Pwr

3 3 £ 500 VA/60 W Switching status 1


3 1 £2A
6
Output mode NO NC
YE/RD adjustment OFF LM

Activating of the MK13-R-Ex0


line monitoring function
2 2 –2
7
Pwr Power
1 1 + 1 +8,2V GN
[EEx ia] IIC
8 3 4

1 2

The 1-channel isolating switching amplifier 4.


MK13-R-EX0 is equipped with an intrinsi- ● Intrinsically safe input circuits EEx ia
cally safe input circuit. When using mechanical contacts as the ● Application area according to ATEX : II
input device, wire-break and short-circuit (1) GD
The device can be connected to sensors ac- monitoring must be disabled or shunt resi-
● selectable output mode (N.O./N.C.
cording to EN 60947-5-6 (NAMUR), variable stors must be connected to the contacts (II) mode)
resistors or potential-free contacts. (see connection diagram).
● Selectable line monitoring for wire-
break/short-circuit (ON/OFF mode)
The output circuit features one relay with The green LED indicates operational readi-
one NO contact. ness. The output switching status is indicated ● SIL 2
yellow by the two color LED. In the event of ● Universal operating voltage
Switches located at the front are used to ad- input circuit errors the dual color LED (20…250VAC/ 20…125VDC)
just the output performance (pnp/npn i.e. changes to red, provided the input circuit
● Galvanic isolation of input circuits to
NC/NO mode). The input circuit is moni- monitoring function is activated. Thereupon output circuits and supply voltage
tored according to wire-break and short cir- the output relay is de-energized.
cuit. Monitoring is disabled with a switch at
the front or with the bridged terminals 3 and
• 24.09.2008

1/0908 TURCK Inc. ñ3000 Campus Drive Minneapolis, MN 55441-2656 ñPhone: 763-553-7300 ñApplication Support: 1-800-544-7769 ñFax 763-553-0708 ñwww.turck.com
Isolating switching amplifier
1-channel
MK13-R-EX0

Type MK13-R-EX0
Ident-No. 7542123
Dimensions

Nominal voltage Universal voltage supply unit


Operational voltage range: 20 … 250 VAC
Frequency ï 40 … ð 70 Hz 89
Operational voltage range: 20 … 125 VDC
Power consumption ð 3W

NAMUR EN-60947-5-6
No-load voltage 8.2 VDC 70
Short-circuit current 8.2 mA 18
Input resistance 1 kò
Output resistance ð 50 ò
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA
Wire breakage threshold ð 0.1 mA
Short-circuit threshold ï 6 mA

Output circuits (digital) 1 x relay (NO)


Relay switching voltage ð 250 VAC/120 VDC
Switching current per output ð 2A
Switching capacity per output ð 500 VA/120 W
Switching frequency ð 10 Hz
Contact quality AgNi, 3µ Au

Test voltage 2.5 kV


Constant voltage supply 250 V

Ex approval acc. to conformity certificate placeholder


Ex approval acc. to conformity certificate TÜV 04 ATEX 2621
Application area II (1) GD
Protection type [EEx ia] IIC
Max.output voltage Uo ð 9.6 V
Max. output current Io ð 11 mA
Max. output power Po ð 26 mW
Characteristic Linear
External inductance/capacitance Lo/Co
EEx ia IIC EEx ia IIB
Lo 1,0 5,0 10,0 2,0 10,0 20,0
[mH]
Co 1800 1300 1200 8600 6200 5500
[nF]

Approval SIL 2
Approval

Indication placeholder
Operational readiness green
Switching status yellow
Error indication red

ñEdition: 2/0908
Isolating switching amplifier
1-channel
MK13-R-EX0

Mechanical Data
Degree of protection IP20
Ambient temperature -25 …+ 70 °C
Housing length 89 mm
Housing width 18 mm
Housing height 70 mm
Weight 108 g
Mounting instruction Mounting on DIN rail or mounting panel
Housing material polycarbonate/ABS
Electrical connection 4 x 2-pole flat terminals with self-lifting pressure
plates
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
• 24.09.2008