You are on page 1of 1

GENERAL NOTES: MINIMUM EMBEDMENT AND LAP SPLICE (mm)

1.0 GENERAL : fc' = 20.7 MPa to 41.4 MPa


1.1 ALL DIMENSIONS ARE SHOWN IN MILLIMETERS, ELEVATIONS ARE IN METERS, 3.2. REINFORCING BARS : BAR EMDEDMENT CLASS A CLASS B CLASS C TOP BARS (W/ MIN. 300 OF CONC. CAST BELOW)
5.0 FOUNDATIONS : STRAIGHT
UNLESS NOTED OTHERWISE. SIZE LENGTH 'E' TENSION SPLICE TENSION TENSION CLASS A CLASS B CLASS C
3.2.1 EMBEDMENT STRAIGHT
UNLESS OTHERWISE SPECIFIED ON PLANS, ALL REINFORCING BARS SHALL BE W/ STD. END ALSO FOR COM- SPLICE SPLICE TENSION TENSION TENSION
1.2 THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE 5.1 FOOTINGS WERE DESIGNED USING AN ALLOWABLE SOIL BEARING 'Ld' EMBEDMENT
DEFORMED WITH A MINIMUM YIELD STRENGTH, fy = 30000 PSI HOOK 'H' PRESSION SPLICE 1.3 * Ld 1.7 * Ld SPLICE SPLICE SPLICE
SITE, AND SHALL NOTIFY THE ENGINEER OF DISCREPANCIES BETWEEN ACTUAL CAPACITY OF 144 KPa (3000 PSF) AT DEPTHS INDICATED IN THE DRAWING. 1.4 * Ld 1.4 * Ld 1.82 * Ld 2.38 * Ld
CONDITIONS AND INFORMATION SHOWN ON THE DRAWINGS BEFORE PROCEEDING FOR Ø12 AND BELOW, AND fy = 40000 PSI FOR Ø16 AND ABOVE. CONFIRMATION OF ACTUAL SOIL BEARING CAPACITY SHALL BE DONE PRIOR TO
E = 25
WITH THE WORK. THIS SHALL INCLUDE THE LOCATION AND DIMENSIONS OF CONSTRUCTION OF FOUNDATION, INCREASE IN FOUNDATION SIZE SHALL BE DONE Ø10 250 300 400 500 350 350 450 600
3.2.2 ALL REINFORCING BARS SHALL BE CLEANED OF RUST, GREASE OR OTHER H = 150
GROOVES, REGLETS, SLEEVES, CURBS, OPENINGS, EMBEDDED OR ATTACHED WHEN ACTUAL SOIL BEARING CAPACITY, CONFIRMED DURING EXCAVATION, WARRANTS
MATERIALS WHICH TEND TO IMPAIR BOND. E = 150
ITEMS, ETC. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING REVISION OF FOUNDATION SIZES. Ø12 300 400 500 600 400 400 600 700
3.2.3 H = 200
ALL FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED
DRAWINGS. BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT. 5.2 WHERE LOOSE/SOFT MATERIAL IS ENCOUNTERED AT DEPTH OF FOOTING/FOUNDATION Ø16 400
E = 200
500 600 700 600 600 700 900
INDICATED, EXCAVATE TO FIRM LAYER AND REPLACE LOOSE/SOFT MATERIALS H = 250
1.3 SECTIONS OR DETAILS. SPECIFIC NOTES AND DETAILS ON DRAWINGS SHALL TAKE 3.2.4 LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE.
PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. UNDERNEATH THE FOOTING WITHIN THE FOOTING AREA PLUS 1/2 DEPTH OF SOIL E = 250
3.2.5 UNLESS INDICATED OTHERWISE, SPLICING OF REINFORCEMENT SHALL BE IN Ø20 500 600 700 900 700 700 900 1200
MATERIAL ON ALL SIDES WITH SELECTED BACKFILL. COMPACT SELECTED BACKFILL H = 300
1.4 THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE ACCORDANCE WITH ACI- 318-95. TO 95% MAXIMUM DRY DENSITY ( ASTM D1557). E = 300
Ø25 800 800 1000 1400 1100 1100 1500 1900
FINISHED STRUCTURES. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION 3.2.6 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS : H = 400
5.3 ALL COLUMN FOOTINGS SHALL REST ON 50MM THK COMPACTED GRAVEL
UNLESS SO STATED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY E = 350
A. BEAMS AND FOOTING TIE BEAMS : TOP AND BOTTOM BARS SHALL NOT BASE COURSE, UNLESS OTHERWISE STATED. Ø28 900 900 1200 1500 1300 1300 1600 2100
MEASURES TO PROTECT THE STRUCTURES, ADJACENT PROPERTIES, WORKMEN H = 500
BE SPLICED WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE
AND OTHER PERSONS DURING ALL PHASES OF CONSTRUCTION. 5.4 FILL/BACKFILL SHALL BE PLACED IN 200 MM LAYERS AND EACH LAYER SHALL BE E = 600
MEMBER DEPTH FROM THE FACE OF THE COLUMN ; AT LEAST TWO EXTRA Ø32 900 1100 1600 1860 1560 1560 2000 2600
COMPACTED TO 95% MAXIMUM DRY DENSITY BEFORE SUBSEQUENT LAYERS H = 750
1.5 THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER AND/OR THE STIRRUP - TIES SHALL BE PROVIDED AT ALL SPLICES. THE SPLICE LENGTH
ARE TO BE LAID. E = 750
THE ENGINEER OF ANY CONDITION WHICH IN HIS OPINION MIGHT ENDANGER SHALL NOT BE LESS THAN THE LENGTH IN ITEM 4.2.9 BELOW. Ø36 1200 1300 2000 2210 1820 1820 2400 2400
H = 600
THE STABILITY OF THE STRUCTURES OR CAUSE DISTRESS IN THE STRUCTURES. B. COLUMNS : SPLICES WHEN PERMITTED SHALL BE MADE WITHIN THE CENTER STRAIGHT STRAIGHT
HALF OF COLUMN HEIGHT, AND LAP SPLICE SHALL NOT BE LESS THAN S
1.6 CONSTRUCTION MATERIALS SHALL NOT BE STORED ON POURED FLOORS. IT
40 BAR DIAMETERS. THE USE OF APPROVED MECHANICAL DEVICES MAY BE
EMBEDMENT CLASS B CLASS C EMBEDMENT CLASS A CLASS B CLASS C
FILLET WELD TABLE K

CLASS A
IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE
E

E
SUB-CONTRACTORS ARE INFORMED AND DO NOT VIOLATE THIS IMPORTANT PERMITTED PROVIDED THAT NOT MORE THAN ALTERNATE BARS ARE
SPLICED AT ANY LEVEL AND THE MINIMUM VERTICAL DISTANCE T
REQUIREMENT. WELD SIZE, S SCALLOP NOTCH H

300
BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600MM. C
PLATE THICKNESS, t (MIN)
1.7 THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACINGS AND (MM) (MM) H STD. 90° OR
SHORINGS FOR ALL THE STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE C. CMU WALLS : VERTICAL BARS SHALL BE SPLICED AT THE TOP OF WALL 180° HOOK
(MM) MIN. CONC.
STABILITY DURING ALL PHASES OF CONSTRUCTION. FOOTING OR TIE BEAM AND AT THE BOTTOM OF RC LINTEL T JOINTS LAP JOINTS R END AN- END AN- FOR FOR BEAM FOR FOR BEAM TOP BEAM TOP FOR
BEAM OR BEAMS. SPLICE LENGTHS SHALL BE 600MM MIN. CHORAGE CHORAGE COLUMN BOT. BARS CONC. BEAMS BARS BARS CONC.
1.8 THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE R FOR BOT. FOR BOT. VERT. BARS, WHERE WALL VERT. INTO WHERE WHERE WALL VERT.
3.2.7 UNLESS INDICATED OTHERWISE ALL BEAMS TERMINATING AT THE COLUMN LESS THAN 6 S=t S=t 25
PROPER ALIGNMENT OF THE STRUCTURES DURING AND AFTER THE INSTALLATION SHALL HAVE TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF E BARS OF BARS OF BEAM BOT. TENSILE BARS, SLAB WALLS TENSILE TENSILE BARS,
OF ALL STRUCTURAL AND FINISH MATERIALS. THE COLUMN, TERMINATING IN A STANDARD 90° HOOK LENGTH OF M SLAB & SLABS & BARS STRESS IN & BEAM STRESS IN STRESS IN BEAM TOP
6 TO 8 6 4 25 BEAMS BEAMS, WHERE BARS < BARS BARS < BARS < BARS
ANCHORAGE NOT LESS THAN 600MM. A
1.9 TYPICAL DETAILS AND GENERAL NOTES ON S-1 APPLY TO ALL PARTS OF THE WALL, COL. TENSILE 0.5* fy & % WHERE 0.5* fy & % 0.5* fy & % WHERE
WORKS UNLESS OTHERWISE SHOWN ON THE DRAWINGS. 9 TO 11 6 6 25 R DOWELS TO STRESS IN OF BAR TENSILE OF BAR OF BAR TENSILE
3.2.8 SHOP DRAWINGS FOR BENDING AND CUTTING OF REINFORCEMENT SHALL
BE SUBMITTED FOR APPROVAL TO THE ENGINEER PRIOR TO FABRICATION. K FOOTINGS BARS < 0.5* SPLICE > STRESS IN SPLICE > SPLICE > STRESS IN
S fy & % OF 75% BARS < 0.5* 75% 75% BARS < 0.5*
3.2.9 SPLICE LENGTH OF REINFORCING BARS SHALL BE AS SHOWN IN THE 12 TO 15 9 9 35
2.0 STANDARDS AND REFERENCES : BAR SPLICE fy & % OF fy & % OF
TABLE BELOW: > 75% BAR SPLICE BAR SPLICE
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION 16 TO 18 9 9 35 > 75% > 50%
3.3 STRUCTURAL STEEL/ANCHOR BOLTS/BOLTS/WELDS & WELDMENTS
OF THE PROJECT :
3.3.1 ALL STRUCTURAL STEEL SHALL HAVE A MINIMUM YIELD STRENGTH, 19 OR OVER 12 12 35
2.1 AMERICAN CONCRETE INSTITUTE ( ACI PUBLICATIONS ) ; Fy = 248 MPa (36 KSI) AND SHALL CONFORM TO ASTM A 36
ACI 318-95 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE SPECIFICATIONS. STANDARD END HOOK DIMENSIONS
ACI 315-80 MANUAL OF STANDARD PRACTICE FOR DETAILS AND DETAILING 3.3.2 S
ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN
OF CONCRETE REINFORCEMENT. ACCORDANCE WITH THE AISC SPECIFICATIONS (9TH EDITION) AND 180° HOOKS 90° HOOKS 135° HOOKS
2.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATION: CODE OF STANDARD PRACTICE AS AMENDED TO DATE. BAR SIZE D(mm.)
WELD ALL AROUND
MANUAL OF STEEL CONSTRUCTION, NINTH EDITION. ALL COLD FORMED STEEL SHALL HAVE A MINIMUM STRENGTH, WELD ALL AROUND (mm)
3.3.3 A (mm.) J (mm.) A (mm.) A (mm.) H (mm.)
"ALLOWABLE STRESS DESIGN" (ASD) Fy = 230 MPa (33 KSI)

t1
3.3

t2
2.3 AMERICAN WELDING SOCIETY (AWS) PUBLICATION D.1.1-90. 3.3.4 NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGS 8 50 105 65 130

t2
HAVE BEEN APPROVED BY THE STRUCTURAL ENGINEER.
2.4 AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM) 10 60 125 80 155 110 65
3.3.5 ALL SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS S
2.5 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) VOL. 1, D.1.1-2000 AND PERFORMED BY QUALIFIED WELDERS. 12 80 155 100 200 115 80
FIFTH EDITION, 2001. 3.3.6 UNLESS INDICATED OTHERWISE, WELDING ELECTRODES SHALL BE E70XX, t=t1 OR t2, WHICHEVER IS THINNER
2.6 ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES (ASEP) MINIMUM THICKNESS OF WELD SHALL BE 3MM. 16 95 180 130 250 140 95
HANDBOOK OF STRUCTURAL STEEL SHAPES AND SECTIONS, 1987
3.3.7 UNLESS OTHERWISE INDICATED ALL ANCHOR NOTE: 20 120 220 165 325 205 115
2.7 UNIFORM BUILDING CODE (UBC), VOL. 2 1997 EDITION BOLTS SHALL CONFORM TO ASTM A307 SPECIFICATIONS. UNLESS OTHERWISE SPECIFIED, SIZE OF FILLET WELDS SHALL BE PROVIDED
3.3.8 BOLTS FOR MEMBER CONNECTIONS SHALL BE HIGH STRENGTH BOLTS, AS SHOWN ABOVE. THE WELD SIZE NEED NOT EXCEED THE THICKNESS OF 25 155 275 205 425 270 155
CONFORM TO ASTM A325 FRICTION TYPE WITH WASHERS. THE THINNER MATERIAL BEING JOINT.
3.0 MATERIALS 28 240 375 300 475
3.1. NORMAL WEIGHT CONCRETE : 3.4 CONCRETE MASONRY UNITS (CMU)
32 275 425 335 550
3.1.1 CONCRETE USED IN THIS WORK SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH 3.4.1 CMU USED IN THESE WORKS SHALL HAVE A MINIMUM ULTIMATE
@ 28 DAYS AS FOLLOWS: COMPRESSIVE STRENGTH @ 28 DAYS AS FOLLOWS : W=1200 MAX W=1200 MAX STANDARD REINFORCEMENT DETAILS
100MM THICK NON-LOAD BEARING CMU, f'm = 6.9 MPa (350 PSI)
FOOTINGS, AND SLABS (3000 PSI) 100MM THICK NON-LOAD BEARING CMU, f'm = 6.9 MPa (350 PSI) (FOR W=1200 PLUS - CONSULT STRUC'L ENRG.) (FOR W=1200 PLUS - CONSULT STRUC'L ENRG.)
400 400 400 400 STANDARD HOOKS HOOK A
COLUMNS, PEDESTAL AND BEAMS (3000 PSI) 3.4.2 ALL CELLS SHALL BE SOLIDLY FILLED WITH GROUT. CONCRETE SHALL PROVIDE 12mmØ EXTRA
HAVE A MINIMUM COMPRESSIVE STRENGTH OF 13.80 MPa A TIES @ 100 MM O.C. A

d
d
3.1.2 ALL CONCRETE SHALL BE DEPOSITED, VIBRATED AND CURED IN ACCORDANCE
(2000 PSI) @ 28 DAYS. D

D
J
WITH ACI STANDARD 318-95
400

400

400

400

A
3.4.3 UNLESS INDICATED OTHERWISE, CMU REINFORCEMENT SHALL BE 10MMØ

12 d
3.1.3 MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE AS FOLLOWS: HOR. BARS @ 600 AND 10MMØ VERT. BARS @ 400. 4d
A LINTEL BEAM W/ 2-Ø12mm A
A. FOOTINGS = 75MM (CAST AGAINST EARTH)
3.4.4 ALL WALLS SHALL BE CONSTRUCTED IN CONVENTIONAL RUNNING BOND CONTINUOUS HORIZONTAL
B. BEAMS AND COLUMNS = 40MM (TO STIRUPS AND TIES) C 60mm min.
UNLESS NOTED OTHERWISE. REINFORCEMENTS WINDOW LINTEL END BLOCK

H
C. SLABS AND WALLS = 20MM (CAST AGAINST FORMS) OPENING 90° HOOKS 180° HOOKS
D. BOTTOM SLAB AND WALLS = 50MM (INSIDE SURFACE OF WATER RETAINING STRUCTURE) 3.4.5 GROUT MASONRY IN 2.4M MAXIMUM LIFTS. REINFORCING SHALL BE CHB WALL W/ 2-Ø12mm D=6d for d=8 mm. through d=25 mm. D=6d for d=8 mm. through d=25 mm.
DOOR
H

SECURED AGAINTS DISPLACEMENT PRIOR TO GROUTING BY WIRE OPENING VERTICAL REINF. D=8d for d=28 mm., d=32 mm. & d=36 mm. D=8d for d=28 mm., d=32 mm. & d=36 mm.
3.1.4 BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER POSITIONERS AT INTERVALS NOT EXCEEDING 200 BAR DIAMETERS LINTEL END BLOCK B D=10d for d=42 mm., & d=47 mm. D=10d for d=42 mm., & d=47 mm.
W/ 2-Ø12mm 2-Ø12mm ADDITIONAL D=Finished bend diameters

SILL HEIGHT
PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATIVE TO NOR 3M.
VERTICAL REINF. VERTICAL BARS
THE WORK. 3.4.6 IF WORK IS STOPPED ONE (1) HOUR OR LONGER, PROVIDE HORIZONTAL B
3.1.5 WHEN CONCRETE WILL BE EXPOSED TO EXTERNAL SOURCES OF CHLORIDES IN FLR. LEV. FLR. LEV. 6d

(75
HOOK A
SERVICES, SUCH AS DEICING SALTS, BRACKISH WATER, SEAWATER OR SPRAY FROM 4.0 CONSTRUCTION JOINTS:

mm
135° HOOKS
DOOR OPENING ELEVATION WINDOW OPENING ELEVATION

mi
THESE SOURCES, CONCRETE MUST BE PROPORTIONED TO SATISFY THE SPECIAL 4.1 CONTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS D=6d for d=8 mm. through d=25 mm.

n.)
EXPOSURE REQUIREMENTS OF ACI 318-95. TO LEAST IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT NOTE: OMIT EXTRA REINF. FOR OPENING LESS D=8d for d=28 mm., d=32 mm. & d=36 mm.
THAN 200MM VERT & 400MM HOR. D=10d for d=42 mm., & d=47 mm.
3.1.6 ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF 7 CONSECUTIVE DAYS TO APPROVAL OF THE ENGINEER.

H
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP. 4.2 UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JOINTS
@ 6.00M MAXIMUM CENTER TO CENTER.
d

ARCHITECT CONSULTANT PROJECT OWNER SHEET CONTENTS DESIGNED JKMK 08-29-2023 SHEET NO.
DRAWN JKMK 08-29-2023
KABS BUILDING DESIGN SERVICE PROPOSED OFFICE WAREHOUSE
ARCHITECTS | INTERIOR DESIGN | ENGINEERS | DESIGN BUILD JOHN KRISTIAN KABILING MR. JOEL FERNANDO CHECKED JKMK 08-29-2023

ARCHITECT-OF-RECORD
WITH MEZZANINE (REPUBLIC ACT. 9266) DRAWINGS AND SPECIFICATIONS DULY SIGNED, STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE,
30 LUCKY ST. SANTOLAN PASIG CITY, METRO MANILA, PHILIPPINES ARE THE INTELLECTUAL PROPERTIES AND DOCUMENTS OF THE ARCHITECT, WHETHER THE OBJECT FOR WHICH THEY ARE MADE IS EXECUTED
CP. NO.: +63 966 592 5770 | +63 966 235 1149 PRC: 24670 TIN: 264914365000 PRC: TIN: OR NOT. IT SHALL BE UNLAWFUL FOR ANY PERSON, WITHOUT THE CONSENT OF THE ARCHITECT OR AUTHOR OF SAID DOCUMENTS, TO
358 F. ORTIGAS, NEW ZANIGA, MANDALUYONG CITY, PHILIPPINES APPROVING OWNER DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER
PTR: 0698729 DATE: 01-07-21 Q.C. PTR: DATE: EXECUTED PARTLY OR IN WHOLE.

You might also like