Professional Documents
Culture Documents
LAPT PANEL
Quantity: 01 No.
P3 L2-PHASE HF HT FUSE
LIGHTNING ARRESTER
7.2kV, 10kA LA LIGHTNING ARRESTOR
SURGE CAPACITOR
7.2kV, 0.5 micro farad
SC SURGE CAPACITOR
P4 L3-PHASE
LIGHTNING ARRESTER PT POTENTIAL TRANSFORMER
7.2kV, 10kA
SURGE CAPACITOR F MCB
7.2kV, 0.5 micro farad
S EPOXY INSULATOR
P5 L1-PHASE
POTENTIAL TRANSFORMER-PT1 SH SPACE HEATER
RATIO:6.3KV/rt3/110V/rt3-110V/rt3
CORE1:CLASS-0.5/BURDEN-50VA PS 3 PIN POWER SOCKET
CORE2:CLASS-3P/BURDEN-50VA
OVF: 1.2 TIMES CONTINUOUS & TH THERMOSTAT
1.9TIMES FOR 8 HOURS
PL PANEL LAMP
P6 L2-PHASE
POTENTIAL TRANSFORMER-PT2 EARTH TERMINAL
RATIO:6.3KV/rt3/110V/rt3-110V/rt3
CORE1:CLASS-0.5/BURDEN-50VA
CORE2:CLASS-3P/BURDEN-50VA
OVF: 1.2 TIMES CONTINUOUS &
1.9TIMES FOR 8 HOURS
P7 L3-PHASE
POTENTIAL TRANSFORMER-PT3
RATIO:6.3KV/rt3/110V/rt3-110V/rt3
CORE1:CLASS-0.5/BURDEN-50VA
CORE2:CLASS-3P/BURDEN-50VA
OVF: 1.2 TIMES CONTINUOUS &
1.9TIMES FOR 8 HOURS
= DIS-CONNECTING
= POTENTIAL TRANSFORMER TYPE TERMINAL BLOCK =THERMOSTAT
=INDICATING LAMP
= SURGE CAPACITOR = STUD TYPE
TERMINAL BLOCK
= FUSE
=DOOR LIMIT SWITCH
PE
=EARTH
2 = POWER SOCKET
= HEATER SWITCH
=SPACE HEATER
A A
TO METERING CIRCUIT-GCP
TO AVR PANEL
PT1-PT3 3
B B
SPARE
C C
EB1
BUSDUCT
6.3KV, 50Hz,
INCOMING SUPPLY
FROM GENERATOR
D D
PT1
1E10
1 HF12
1a /2.1:A
A
6.6kV/3.15A
1E70
1n /2.1:A
A A
2E10
2a /2.1:C
N
2E70
2n /2.1:C
POTENTIAL TRANSFORMER1-3 -PT2 1E30
6.3KV/rt3/110V/rt3-110V/rt3 HF2 A 1a /2.1:A
1 2
CORE-1: CL 0.5, 50VA
6.6kV/3.15A
CORE-2: CL 3P, 50VA 1n
1E70 2E70
2E30
2a /2.1:C
N
2n
-PT3
1E50
1
HF3 2 A 1a /2.1:A
B B
6.6kV/3.15A 1n
2E50
2a /2.1:C
N
2n
C C
L1 L2 L3
3.3KV, 50Hz,
INCOMING SUPPLY
D BUSDUCT D
FROM GENERATOR
F1
1E10 1 2 1E11
/1.5:A
1E30 3 4 1E31
POTENTIAL TRANSFORMER1-3 /1.5:A
6.3KV/rt3/110V/rt3-110V/rt3
CORE-1: CL 0.5, 50VA /1.5:B 1E50 5 6 1E51
A A
1E70 7 8 1E71
/1.5:A
4A, 4P
PTTB1
1 2 3 4 5 6 7 8 9 10 11 12
F2
2E10 1 2 2E11
/1.5:A
2E30 3 4 2E31
POTENTIAL TRANSFORMER1-3 /1.5:B
6.3KV/rt3/110V/rt3-110V/rt3
2E50 5 6 2E51
CORE-2: CL 3P, 50VA /1.5:B
2E70 7 8 2E71
C /1.5:A C
4A, 4P
PTTB2
1 2 3 4 5 6 7 8
D D
A A
F3
ACTB 1 H1 1 2 H3 H3 H3 H3 H3 H3 H3 H3 H3 H3 H3
H4
230VAC SUPPLY 1 1 1 1 1 1 1 1 1 1
2 H2 3 4 H4
FROM MCC F4 F5 F6
16A,DP 6A,SP 2 6A,SP 2 6A,SP 2 DLS1 2 DLS2 2 DLS3 2 DLS4 2 DLS5 2 DLS6 2 DLS7 2 1 3
3 PE F7
10A,DP 2 4
H5 H7 H9
1 1 1
TH1 TH2 TH3
B 2 2 2 B
H6 H8 H10
PS
1
PE
x1 x1 x1 x1 x1 x1 x1
x1 x1 x1 2
SH1 SH2 SH3 PL1 PL2 PL3 PL4 PL5 PL6 PL7
x2 x2 x2
x2 x2 x2 x2 x2 x2 x2
H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 H18
C C
D D
PTTB1
1E11
1 TO METERING CIRCUIT-MCSP
1E31
2 TO METERING CIRCUIT-MCSP
1E51
3 TO METERING CIRCUIT-MCSP
1E71
4 TO METERING CIRCUIT-MCSP
1E11
5 TO AVR PANEL
1E31
6 TO AVR PANEL
1E51
7 TO AVR PANEL
1E71
8 TO AVR PANEL
1E11
9 SPARE
1E31
10 SPARE
1E51
11 SPARE
1E71
12 SPARE
PTTB2
2E11
1 TO PROTECTION CIRCUIT-GRP
2E31
2 TO PROTECTION CIRCUIT-GRP
2E51
3 TO PROTECTION CIRCUIT-GRP
2E71
4 TO PROTECTION CIRCUIT-GRP
2E11
5 SPARE
2 DRAWOUT TROLLY WITH DRAWOUT TROLLEY (TO MOUNT SINGLE PHASE Pts) REPUTED 3
Page 01 of 01