You are on page 1of 11

Document Submittal Form

Document 13-215510-1100001344-
Contractor Awad Saad BinZafrah
submittal no. ASB-CIV-ITP-000002_01

Contract no. 1100001344/022 Date 13-06-2023

To PMC AECOM

Document no. Type Description Rev no. Action required

Approval Comments

13-215510-110000134
4-ASB-CIV- ITP
1100001344/022- inspection 01
ITP-000002_01 Test Plan for Earthworks (Civil) Information Other

Approval Comments

Information Other

Approval Comments

Information Other

Contractor authorized signature


Name Asaad Sleem Date 13-06-2023

Signature

PMC’s comments

Exception is noted revise and


No exception taken Revise and resubmit
Status code resubmit for record
Rejected Review not required Issued for Construction
Engineer’s Date
name
Signature

Received by Contractor

pdf
Pdf
Pdf
Pdf
Pdf
Pdf
PDF
FilePDF
PDF 6.01.NEOM
01-NEOM
01.NEOM
01.NEOM
01.NEOM
01.NEOM
01.NEOMBay
Bay
01.NEOM
01.NEOMBay
Bay
Bay
Bay
Bay
Bay
---Luxury
C. EQUIPMENT-Luxury
-Luxury
-Luxury
-Luxury
-Luxury
Luxury
Luxury
Luxury
Mansions
Mansions
Mansions
Mansions
Mansions
Mansions
Mansions
Mansions No Weekly Report
01-630000-0000100185-ASB-HRM-CVS-000005
01-630000-0000100185-ASB-ENV-PLN-000003
MONITORING01-630000-0000100185-ASB-QMN-PLN-000001
01-630000-0000100185-ASB-PCO-SCD-000001
01-630000-0000100185-ASB-GEO-RPT-000001
01-630000-0000100185-ASB-HRM-CVS-000006
01-630000-0000100185-ASB-HRM-CVS-000007
01-630000-0000100185-ASB-CIV-ITP-000001
01-650000-0000100185-ASB-CPM-INS-000001
01-630000-0000100185-ASB-ENV-PLN-000003
01-630000-0000100185-ASB-QMN-PLN-000001
01-630000-0000100185-ASB-PCO-SCD-000001
01-630000-0000100185-ASB-PCO-SCD-000001
01-630000-0000100185-ASB-ENV-PLN-000003
01-630000-0000100185-ASB-PCO-SCD-000001
01-630000-0000100185-ASB-CIV-ITP-000002
01-630000-0000100185-ASB-CIV-MST-000007
Document 01
02
01
01
03
01
01
01
01
03
01
02
02
01
Revision Date PLAN
Inspection
IN
0000100185/04-DEMOLITION
MANAGEMENT AREA
Statement
0000100185/04-Time-Schedule
0000100185/04-Time-Schedule
0000100185/04-PROJECT
0000100185/04-Time-Schedule
0000100185/04-Method
0000100185/04-Company
0000100185/04-PROJECT
0000100185/04-Curriculum
0000100185/04-PROJECT
0000100185/04
0000100185/04-Inspection
Title Insurance
QUALITY
&QUALITY
B4
ENVIRONMENTAL
QUALITY
10Vitae
8Test
0000100185/04-Time-Schedule
01-630000-0000100185-ASB
Report
12-Dec-2020
No. 01 & Test
Plan
for
PLA
Plan
PLAN
PLAN

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 1 of 11


I n s p e c t i o n & T e s t P l an
1100001344/022- inspection Test Plan for Earthworks (Civil)

" 13-215510-1100001344-ASB-CIV-ITP-000002_01" " June 2023"

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 2 of 11


Document history

Revision code Description of changes Purpose of issue Date

01 First Submission For Approval 13-06-2023

Document approval

Prepared by Reviewed by Approved by


Name Raheem Khan Raheem Khan Asaad Sleem

Job Title QC Manager QC Manager Project Manager

Signature

Date 13-06-2023 13-06-2023 13-06-2023

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 3 of 11


INSPECTION AND TEST PLAN
NEOM QUALITY MANAGEMENT SYSTEM Main Contractor: Bin Zafrah
(ITP) FOR EARTHWORK Sub-Contractor:
Contract Sindalah island cluster 5 Substructure work on luxury resort. 13-215510-1100001344-ASB-CIV-ITP-000002
Contract No.: 1100001344/022 ITP No.: Rev. No.: 01 Date: 13/06/2023
Title:

Level of Participation Points


Controlling Document/ Acceptance
S No. Activity Phase Inspection / Test Method Remark
Reference Standard Criteria Main NEOM/ NEOM/
Con. QC PMC ETSD

1 DOCUMENT REVIEW
Confirm documents:
- Construction Drawing
- Method statement 1- Approved
- Permits Documents R/H R/H R/H
1.1
- Clean Sand, aggregates and Suitable Backfill NEOM Specs 312000, Part -1 2-NEOM Specs 312000
Material Sec 1.1, Part -2 Sec 2.2.
- Sampling, Testing & Review of Test
Reports
Conform to ASTM D 1557,
Existing /borrow fill stockpile material ASTM D 4318, ASTM D
review of test reports (Compaction curve, 2216, ASTM D 422, ASTM Method of Statement /
1.2 Liquid limit, Plastic limit, In-Situ Moisture NEOM Specs 312000, Part 3, D 2487 R/H R/H R/H Special Procedure Approval,
content, Particle size analysis, Soil Sec 3.11, 3.14,3.15,3.16 Stock Material
classification)
2 MATERIAL INSPECTION

Sampling and Soil Testing, Gradation, Soil NEOM Specs 312000 Part 2 Sec 2.1 Approved Material submittal, MIR, and H W W Check List MOB-CIV-CL-05
2.1 AASHTO T-189, ASTM D 2922
Classification, CBR, MDD. Lab Test Reports
AASHTO T-145

Clean Sand and Aggregate Base Course NEOM Specs 312 000 Part 3 Sec 3.20 Approved Material as per NEOM H W W Material Receiving Report
2.2
Receiving Inspection Specs 312000

3 CLEARING & GRUBBING


NEOM Spec 311000 Sec 3.6 A, B
As per IFC / Survey Alignment / As Per NEOM Specifications, 311000
3.1 ASTM D2922 H W W Approved WIR / Approved FDT report
Visual Inspection, NGL FDT SECTION 312000, Clause 3.15 C Sec 3.6 A, B and Check List.

4 INSTALLATION

NEOM Specs 312000, Part 3 Sec 3.1 As per Approved Drawing


4.1 Excavation & General Back filling W W W Survey Report / Check List MOB-CIV-CL-04
& 3.19 NEOM Specs 310000

1- Test report
NEOM Specs 31 20 00, Part Sec 3.16 WIR will be submitted to ETSD for FDT of
2- Compaction not less than 95%
Section 312000 Clause 3.18 A (1,2,3) each backfilled compacted layer in the
4.2 Fill Placement & Compaction Inspection Survey level check / FDT ASTM D H W W
(NEOM Specs) 3.19 A presence of 3rd party independent lab
1556(Sand Cone Method) or ASTM D
AASHTO T-189, ASTM D 2922 Check List MOB-CIV-CL-07
6938 (Nuclear Method)

4.3 Final Acceptance Inspection NEOM Specs 31 20 00, Sec 3.24 NEOM Specs 310000 & 312000 W W W Approved Survey Report / 3rd Party Reports / Drawing

ITP Approval Signature


Sub-Contractor (If Applicable) Main Contractor NEOM/PMC NEOM/ETSD
Name: Name: Name: Name:

Signature: Signature: Signature: Signature:

Date: Date: Date: Date:


Legend:
S: Responsible for carrying out random surveillance of
H: Contractor must not proceed without approval. R/H : Responsible for reviewing certification or reports & Approval W: Responsible for / and witnessing all inspection or test.
inspection or test/Random Check.

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 4 of 11


INSPECTION AND TEST PLAN
NEOM QUALITY MANAGEMENT SYSTEM Main Contractor: Bin Zafrah
(ITP) FOR EARTHWORK Sub-Contractor:
Contract
Contract No.: 1100001344/022 Sindalah island cluster 5 Substructure work on luxury resort. ITP No.: Rev. No.: 01 Date: 13/06/2023
Title:

Level of Participation Points


Controlling Document/ Acceptance
S No. Activity Phase Inspection / Test Method Remark
Reference Standard Criteria Main NEOM/ NEOM/
Con. QC PMC ETSD
GENERAL NOTES:
The first (3) of each inspection or testing activities listed require 100% participation of client site inspection personnel. After this period, client inspection may adjust the level of client participation based on the contractor's performance.
Hold(H): QA/QC team shall be notified of the schedule of inspection or test in advance. Inspection or test shall not be carried out without the QA/QC Team/Client representative in attendance.
Review(R/H): Required qualification/certification/reports shall be submit for the QA/QC team review and approval.
Witness(W): QA/QC team shall be notified of the schedule of inspection or test in advance. If the QA/QC Team/Client representative does not come on time for inspection, the activity can proceed.
Surveillance(S): QA/QC team to monitor work in progress without notice from the construction organization/Random check selection.

Legend:
S: Responsible for carrying out random surveillance of
H: Contractor must not proceed without approval. R/H : Responsible for reviewing certification or reports & Approval W: Responsible for / and witnessing all inspection or test.
inspection or test/Random Check.

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 5 of 11


DATE: WIR NUMBER:
13/06/2023
INSPECTION CHECKLIST
Check list no: ITP NO: 000002
Excavation & General Back filling, Fill ASB-CIV-CL-001
Placement & Compaction Inspection

CONTRACT NUMBER CONTRACTOR:


Project Title:
Sindalah island cluster 5 Substructure work 1100001344/022 Bin Zafrah
on luxury resort.

ITEM ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP


NO. DATE

Any Sheeting and shoring shall be gradually Neom Specs 312000,


removed as the backfill is place Part 3 Sec 3.20
A1

All Void under and behind sheeting shall be filled Neom Specs 31200,
as sheeting is withdrawn. Part 3 Sec 3.20
A2.

Sheeting shall be cut and left in place where Neom Specs 31200,
damage to the utilities may occur or failure of the Sec 3.4
A3
trench walls may cause damage or failure of
adjoining building or structures.

All Excavation shall be restored to surface contour Neom Specs


to ensure it blends with surrounding area 312000, Sec 3.4
A4

Area of land side and Pavement shall be excavated Neom Specs


and restored in accordance with quality 310000/IFC Drawing
A5
procedure, project specification & IFC Drawing

The pavement base course shall be of the same IFC Drawing


depth and material as the original base course.
A6

The edge of existing pavement and the base IFC Drawing


course shall be primed.
A7

The Surface course shall be identical to the original Neom Specs 31000,
surface course. The patch shall be rolled in both Sec 3.16
A8
directions with a 5-ton roller so it is compacted to
96% of the Marsha density in accordance with
ASTM D1559

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 6 of 11


Check for loose material, soft spot, etc.at the Neom Specs
bottom of excavation 311000, Sec 1.1 D
A9

Make sure not to blow rock during clearing and Neom Specs
grabbing work 311000, Sec 3.4
A10

Remove rocks, trees, shrubs, herbs and Neom Specs


otherplants if any 311000, Sec 3.4 A
A11

REMARKS:

Contractor PMC-ETSD

Construction Representative* Name, Initials and Date:

Work is Complete and Ready for Inspection

Name, Initials and Date:


NEOM -ETSD Representative

QC Inspection ΠT&I Witnessed ΠQC Record Reviewed ΠWork


Name, Initials and Π Performed Inspection Π Work/ Verified
Date: Rework may Proceed

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 7 of 11


DATE: WIR NUMBER:
13/06/2023
INSPECTION CHECKLIST
Check list no: ITP NO: 000002
Sampling and Soil Testing, Gradation, Soil ASB-CIV-CL-002
Classification, CBR, MDD.
Project Title: CONTRACT NUMBER CONTRACTOR:
Sindalah island cluster 5 Substructure work 1100001344/022 Bin Zafrah
on luxury resort.
ITEM RE-INSP
NO. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A DATE

The third-Party Inspection, Sub contractor shall Schedule Q


issue original report simultaneously to both the Appendix C
A1 Sec.C2.8.1
CONTRACTOR and Neom PQID representative of
the application NEOM
One Sample for CBR, Classification (AASHTO Neom Specs -
M145), and Laboratory (Moisture – density) or 312000 Part
A2. Sec2.1 D 4
relative density compaction from each source
prior to use

Each Sample shall represent not more than Neom Specs 312000
10,000m3 of fill material
A3
50-Kg samples, sealed in airtight containers of Neom Specs 312000
each proposed soil material from on site or borrow Sec 2.1
A4
source
Classification according to ASTM D 2487 of each Neom Specs -
on site or borrow soil material proposed for 312000 Sec 2.1
A5
backfill, fill embankment and subgrade layer
Laboratory Compaction curve according to Neom Specs-
AASHTO T -180 (Method D) Modified Proctor for 312000 Sec 2.1
A6
each on site or borrow soil material proposed for
backfill, fill, embankment and subgrade layer

REMARKS:

Contractor PMC -ETSD


Construction Representative* Name, Initials and Date:
Work is Complete and Ready for Inspection

NEOM -ETSD Representative


Name, Initials and Date:
QC Inspection ΠT&I Witnessed ΠQC Record Reviewed ΠWork
Name, Initials and Π Performed Inspection Π Work/ Verified
Date: Rework may Proceed

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 8 of 11


DATE: WIR NUMBER:

INSPECTION CHECKLIST 13/06/2023

Check list no: ITP NO: 000002


Fill Material Receiving & Storage Inspection ASB-CIV-CL-003

Project Title: CONTRACT NUMBER: CONTRACTOR:


Sindalah island cluster 5 Substructure work 1100001344/022 Bin Zafrah
on luxury resort.

ITEM ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP


NO. DATE
Provide Borrow Soil materials with sufficient Neom Specs -
satisfactory soil materials are not available from 312000 Sec 2.1 A
A1
excavations.

Soil material shall comply with the requirement of Neom Specs 312000
NEOM Specs -312000
A2.

A3 Record Shall be maintained for received material Neom Specs 312000


to verify frequency of sampling Sec2.1

B Material Storage
Stockpile borrow soil material and excavated Neom Specs 312000
satisfactory soil materials without intermixing, Sec 3.11
B1
place, grade, and Shape stockpile
B2 Stockpile Soil Materials aways from edge of Neom Specs 312000
Excavations. Sec 3.11
B3 Stockpile areas are to be used by the permission of Neom Specs 312000
the authorities. Sec 3.12 A2
B4 Do not stockpile unsatisfactory soil on site Neom Specs -
312000 Sec 3.12 A3
REMARKS:

Contractor PMC -ETSD

Construction Representative* Name, Initials and Date:

Work is Complete and Ready for Inspection

NEOM -ETSD Representative


Name, Initials and Date:

QC Inspection ΠT&I Witnessed ΠQC Record Reviewed ΠWork


Name, Initials and Π Performed Inspection Π Work/ Verified
Date: Rework may Proceed

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 9 of 11


DATE: WIR NUMBER
13/06/2023
INSPECTION CHECKLIST
Check list no: ITP NO: 000002
Fill Placement and Compaction Inspection ASB-CIV-CL-004

Project Title: CONTRACT NUMBER CONTRACTOR -


Sindalah island cluster 5 Substructure work Bin Zafrah
1100001344/022
on luxury resort.
ITEM RE-INSP
NO. ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A DATE
Fill Material shall be placed in lifts not exceeding Neom Specs 312000
A1 200mm in loose depth Sec 3.16

Fill material shall be placed in lifts not exceeding Neom Specs 312000
100mm in loose depth for hand – operated Sec 3.16
A2.
compaction.

Fill and backfill adjacent to any types of structure Neom Specs


shall not be compacted with heavy equipment: 312000, Sec 3.16
A3
hand operated equipment shall be used within 1.2
meter of any structure

Every effort shall be place backfill materials Neom Specs 312000


symmetrically and in uniform layer to prevent sec 3.16
A4
unnecessary eccentric loading on a structure or
foundation

Compacted surface of fill and backfill shall be finish Neom Specs 312000
graded to the cross sections, lines grades and sec 3.16
A5
elevation as indicated on the drawing.

Backfilling and removal of trench supports shall be Neom Specs 312000


accomplished by backfilling up to a level allowing sec 3.16
A6
for removal of the lower braces: Another layer of
backfill shall then be positioned in the trench to
the next layer of braces to be removed

Removal of trench supports or shoring shall Neom Specs 312000


progress together with the backfill from the sec 3.16
A7
bottom of the trench in unstable soil, ropes shall
be used to pull supporting materials from the
trench.

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 10 of 11


B Compaction Inspection
Compaction shall be only after the fill or backfill Neom Spec 311010,
has been properly placed and the material to be sec 3.11 B7
B1
compacted is at the proper moisture content
+/-3% of the optimum moisture content per ASTM
D1557 or ASTM D698, whichever is applicable

Compaction shall be performed with equipment Neom Specs 312000


compatible with soil type sec 3.2
B2

The Compaction requirement for subbase shall be Neom Specs 312000


not be less than 95% of the maximum laboratory sec 3.5 D
B3
dry density as determined by ASTM D 1557 or
AASHTO T180(FDT)

REMARKS:

Contractor PMC-ETSD

Construction Representative* Name, Initials and Date:

Work is Complete and Ready for Inspection

Name, Initials and Date:


NEOM -ETSD Representative

QC Inspection ΠT&I Witnessed ΠQC Record Reviewed ΠWork


Name, Initials and Π Performed Inspection Π Work/ Verified
Date: Rework may Proceed

Doc No. 13-215510-1100001344-ASB-CIV-ITP-000002 Rev 01 Page 11 of 11