Note:
1. In factory, the controller has been set the parameters. In generally the users don`t need to change the parameters.
2. Default control mode is terminal control mode (P0.06=1), if you need to use manual mode (press OD/CD to open/close door), please set
p0.06=0.
3. Default door arrived contact is normally closed (P6.00=1), if you need normally opened, set P6.00=0.
4. The situation you can`t change the parameter: a, make sure you input the right password, default with no password.
b, when the motor is running, you can`t change some parameters, you can pull out the OC/CD
terminal, and reset the power.
YOU CAN USE THE FOLLOWING STEPS WHEN YOU CHANGE THE CONTROLLER、MOTOR OR ENCODER.
Step 1: Reset default parameter
With the latest panel or the controller (with one will be fine)
Series Specifications
YS-P02 or YS-P03 Controller with V1.04 and above
KS centre opening 800 P8.10=11 P8.10=01
KS series
KS centre opening 900 P8.10=12 P8.10=02
Step 6: Enter elevator operation, set P0.06=1 to terminal control mode.(Let the elevator control the door)
MS DEBUGGING STEPS
Note:
1. In factory, the controller has been set the parameters. In generally the users don`t need to change the parameters.
2. Default control mode is terminal control mode (P0.06=1), if you need to use manual mode (press OD/CD to open/close door), please set
p0.06=0.
3. Default door arrived contact is normally closed (P6.00=1), if you need normally opened, set P6.00=0.
4. The situation you can`t change the parameter: a, make sure you input the right password, default with no password.
b, when the motor is running, you can`t change some parameters, you can pull out the OC/CD
terminal, and reset the power.
YOU CAN USE THE FOLLOWING STEPS WHEN YOU CHANGE THE CONTROLLER.
Step 1: Reset default parameter
With the latest panel or the controller (with one will be fine)
Series Specifications
YS-P02 or YS-P03 Controller with V1.04 and above
MS centre opening 800 P8.10=13 P8.10=03
MS centre opening 900 P8.10=14 P8.10=04
MS series
MS side opening 1100 P8.10=15 P8.10=05
MS side opening 1200 P8.10=16 P8.10=06
Step 4: Door width self-learning, set P2.05=1, then press OD or CD key, the door machine will do “open - closed - open - closed”. The door width will be
stored to P2.06 and P2.07 at the end of self-learning.
Notice: If it close-open-close-open, just change any two phase of motor!
Step 5: Modify OD/CD curve, press OD key or CD key, manually open/close the door to observe the OD/CD curve, and then properly change the OD/CD
Acc/Dec point (P3.04/P4.04) and time (P3.05/P4.05).
Step 6: Enter elevator operation, set P0.06=1 to terminal control mode.(Let the elevator control the door)