Power Transformer Foundation Design Calculations

The document provides design calculations for the foundation of a power transformer for a 70MW solar PV project in Bhadla, Rajasthan. It includes calculations for load assumptions, bearing capacity, overturning, shear stresses, reinforcement requirements, and buckling resistance of the foundation.

Uploaded by

KOTADIA KISHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
5K views5 pages

Power Transformer Foundation Design Calculations

The document provides design calculations for the foundation of a power transformer for a 70MW solar PV project in Bhadla, Rajasthan. It includes calculations for load assumptions, bearing capacity, overturning, shear stresses, reinforcement requirements, and buckling resistance of the foundation.

Uploaded by

KOTADIA KISHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

CLIENT EPC CONTRACTOR

Document Tittle. : POWER TRANSFORMER FOUNDATION


DESIGN DOCUMENT
Project:- DEVELOPMENT OF 70MW A.C. SOLAR PV PROJECT
IN BHADLA RAJASTHAN

YIL DOC NO:-YIL-BDL-C-DOC-PWTRNS-FUD-01

SW DOC NO:- SWLD-YIL-BDL-C-DOC-PWTRNS-


Rev. Date DESCRIPTION PRPD. CHKD. APP FUD-01
BY BY BY
30/35MVAPOWER FORMAT NO SWL-ENGG-01-F02R0
TRANSFORMER
FOUNDATION DESIGN
CALCULATION Effective Date 8/24/2015

5x10MW SOLAR PV POWER PLANT PROJECT AT BAP, DIST. JODHPUR,


RAJASTHAN
30/35MVAPOWER TRANSFORMER FOUNDATION DESIGN CALCULATION

Document No:-
30/35MVAPOWER Rev
TRANSFORMER FOUNDATION SWLB-SP-RJ-50MW-SS-C-CAL-PTF-504
Document Title DESIGN CALCULATION
DATE:- 4/12/2017
0

LR R.K SV
STATUS INTLS SGN INTLS SIGN INTLS SGN
PRPD BY. CHECKED. BY. APPR. BY.
ISSUE AUTHORITY
POWER TRANSFORMER FOUNDATION DESIGN CALCULATIONS GNFC
[Link]. Description Units
1 Depth of Foundation = 1.5 m
2 Height of pedestal wall above ground level = 0.5 m
3 Allowable Bearing Capacity (As per Geotech) = 176.00000 kN/m2
4 Unit Weight of Soil Dry = 18.00 kN/m3
5 Characteristic Strength of concrete, fck = 25 N/mm2
6 Yield Strength of steel, fy = 500 N/mm2
7 Clear cover = 50 mm
8 Unit Weight of concrete = 25 kN/m3
9 Overall Transformer Length = 6.65 m
10 Over all Transformer Width = 4.950 m
11 Over all Transformer Height = 5.5 m
12 Weight of Transformer with oil = 54000 kg
13 Total Weight of oil = 11200 kg
14 Density of oil = 889.9483512 kg/m3
15 Total Volume of oil = 12.59 m3
16 Width of Transformer Supporting Pedestal = 0.375 m
17 Length of Transformer Supporting Pedestal = 6.205 m
18 Center to center of pedestal wall foundation = 1.756 m
19 Area of Transformer Supporting Pedestal = 4.65375 m2
20 Pit Volume required (35% of oil vol) = 4.40 m3
21 Length of pit = 8.67 m
22 Width of pit = 6.95 m
23 Surface Area of pit = 60.26 m2
24 Net surface area of the pit = 55.60 m2
25 Average depth required = 0.30 m
26 Thickness of gravel layer = 0.3 m
27 Height of pit wall above base slab = 0.60 m
LOAD CALCULATION
Wind Load Calculation
1 Basic Wind speed, Vb (As per IS875 Part-3) = 50 m/s
2 K1 = 0.9
3 K2 = 1
4 K3 = 1
5 K4 = 1.15
6 Design Wind speed, Vz = k1 * k2 * k3 * k4* Vb = 51.75 m/s
7 Design Wind Pressure, Pz = 0.6 * Vz^2 = 1.607 kN/m2
8 Lateral Load on centre of Transformer, Pz * A = 58.77 kN
Seismic Load Caculation
1 Zone Factor, Z (Zone-V) = 0.36
2 Importance Factor, I = 1.5
Response Reduction, R = 3
Time period, T = 0.24 seconds
For Soft soil sites, Figure 2, IS1893:2002
Average Response Acceleration Coefficient, Sa/g = 2.50
Design Horizontal acceleration spectrum, Ah =
(Z*I*Sa/g)/(2*R) = 0.225
Design Base shear, H = Ah * W = 119.19 kN
According to Cl. 15.1.6 of IS 1904, " Where seismic load is less than 25% of that due to dead
and live loads, it may neglected in design.
FOUNDATION DESIGN CALCULATIONS
Check for Bearing Capacity
Weight of Transformer Supporting Pedestal = 232.6875 kN
Length of Foundation Pad = 6.905 m
Width of Foundation Pad = 3.531 m
Thickness of Foundation Pad = 0.3 m
Weight of Foundation Pad = 182.86 kN
Total Vertical Load(Dead Weight of Transformer,
Pedestal walls, Foundation slab) = 1307.3553 kN
Max Moment due to horizontal load(Lateral Load x
Lever Arm) = 238.38 kNm
Pmax (P/A)+(Mz/Zz)+(Mx/Zx) = 78.73 kN/m2
Pmin ( >0 ) (P/A)-(M/Z) = 28.51 kN/m2
Net Allowable Pressure (Safe Bearing Capacity) = 176 kN/m2
HENCE SAFE
Weight of soil filling above foundation B = 362.07 T
Check for Overturning
Overturning Moment (Lateral Load x Lever arm) = 845.32 kNm
Restoring Moment (Dead Weight x Lever Arm) = 2947.36 kNm
Factor of Safety = 3.49 > 1.5
HENCE SAFE
Check for One way Shear
Shear Force at 'd'from face of wall, Vu = 50.98 kN
Nominal Shear stress, Tv = 0.20 N/mm2
Percentage of steel = 0.151 %
Design Shear Strength Tc = 0.29 N/mm2
HENCE SAFE
Check for Two way Shear
Shear Force at 'd/2' from face of wall, Vu = 1064.297817 kN
Nominal Shear stress, Tv = 0.24 N/mm2
ks = (0.5+β) = 1.00
Design Shear Strength Tc = 1.25 N/mm2
HENCE SAFE
STRUCTURAL DESIGN CALCULATIONS
Footing Pad Reinforcement
Bottom Face Design Calculations
Maximum Moment, Mub = 28.93 kNm
Percentage of steel = 0.11 %
Area of steel = 326.53 mm2
Diameter of Reinforcement Bar = 12 mm
Spacing of Bar = 250 mm
Provided Area of steel = 452.16 mm2
Provided Percentage of steel = 0.15 %
As provided steel is greater than the required, HENCE SAFE.
Pedestal Reinforcement
Minimum % of steel required as per IS 456 = 0.20 %
Provided Steel (Y 12 @200mm c/c) = 1130.40 mm2
Bothways (Horizontal and Vertical)
Provided Percentage of steel = 0.30 %
As provided steel is greater than the required, HENCE SAFE.
Check for Buckling
Buckling Formula:- One end Fixed and Other end free

Youngs modulus for concrete E = 25000 N/mm2


Moment of Inertia I = 27268066406 mm4
Effective length of column Le = 2000 mm
Pcr = 420.6169118 Tons
Self weight of transformer on each pedestal = 27 Tons
As provided area of pedestal is greater than the required, HENCE SAFE.