HVAC SAMPLE PROJECT EXERCISE DATA

WEATHER DATA

Outside Dry Bulb Temp. = 95 ᵒF


Outside Wet Bulb Temp. = 82 ᵒF
Room Temp = 75 ᵒF
Room Relative Humidity = 50%
Daily Range Temp. = 20 ᵒF
Latitude (North) = 14 ᵒ 35”
Longitude (East) = 121 ᵒ (120 ᵒ59’’)
Design Month = May
Location = Metro Manila

BULDING DATA
EXTERAL LOAD INFORMATION

A. Roof: DARK COLOR

Construction Resistance (R) ft²-hr-ᵒF/BTU


Outside surface air film = .33
3/4 Plaster = .13
6’’HW Concrete = .50
Ceiling Air Space = 1.0
½’’ Acoustic tile = 1.796
Inside Surface Film = .685

B. Wall (Exterior) MEDIUM COLOR

Construction Resistance (R) ft²-hr-ᵒF/BTU


Outside surface air film = .33
¾’’ Plaster = .13
4’’ HW Concrete Block = .667
1’’Insulation (Preformed) = 6.667
¾’’ Plaster = .13
Inside Surface Film = .685

C. Partition (Inside) Light Color

Construction Resistance (R) ft²-hr-ᵒF/BTU


Inside Surface Film = .685
¾’’ Plaster = .13
4’’ HW Concrete Block = .667
¾’’ Plaster = .13
Inside Surface Film = .685
D. Windows

Single Glass 1/4 ‘’ clear


U-Factor = 0.61 BTU/ft²-hr-ᵒF
Glass Factor = 0.56
Int. Shade = Venetian Blind (Light Color)
Shading Data
Overhung Extension = 0’’
Overhung Height = 0’’
Reveal Depth = 6’’
Finish Separation = 0’’
Fin Extension = 10’
Windows Dimensions:
Ground Floor = 5’x8’ (North & South)
2nd-9th Floor = 5’x5’ (North & South)
10th/Penthouse = 5’x10’ (North & South)

E. Door

U-Factor = 0.30 BTU/ft²-hr-ᵒF


Glass Factor = 0.9
Int. Shade = None
Shading Data
Overhung Extension = 8’
Overhung Height = 0’’
Reveal Depth = 6’’
Finish Separation = 0’’
Fin Extension = 10’

Door Dimension = 3’x7’ two (2) Door (Non-Weather)


= Gray plate 3/8’’ Glass;
one (1) side locked metal frame
Number of Opening = 50 Door Opening/hr

INTERNAL LOAD

A. Lights

Lighting wattage input estimated = 1.5 watt/ ft²


Ballast Factor = 20%

B. People (Heat Gain)

Ground Floor
Activity = Standing, Lightwork, or Walking Slowly
Qs = 315
Qɩ = 325
No. of People = 63
2nd-9th Floor
Activity = Seated, Lightwork, Typing
Qs = 255
Qɩ = 255
No. of People = 457

10th/Penthouse
Activity = Standing, Lightwork or Walking Slowly
Qs = 315
Qɩ = 325
No. of People = 47

C. Power

Ground Floor
No. computer in every room = 3 sets
CPU = 120 watts
Monitor (LCD 24’’) = 72 watts
Water Cooler = ¾ Hp (1 unit)
Airpot = 600 watts/Floor (2 unit)
Kitchen Equipment = 12000 BTUH (1 set/kitchen)
Kitchen Gas Equipment = 100,000 BTUH

2nd-9th Floor
No. computer in every room = 3 sets
CPU = 120 watts
Monitor (LCD 24’’) = 72 watts
Water Cooler = ¾ Hp (1 unit)
Airpot = 600 watts/Floor (2 unit)

10th/Penthouse
No. computer in every room = 4 sets
CPU = 120 watts
Monitor (LCD 24’’) = 95 watts
Water Cooler = ¾ Hp (1 unit)
Airpot = 600 watts/Floor (2 unit)

D. Ventilation

Note: Assume 20 ft³/Person

E. Infiltration

Note: To be calculated as per door opening

F. Correction for Cooling Load Temp Difference

ΔT = T out
G. Others

Floor to Floor Height = 12’


Thickness of Floor/Slab = 6’’
Ceiling Drop/Headroom/Plenum = 2.5’
Height of ceiling to Finish Floor = 9’
6 5.5 5 4 3 2 1.5 1
30.00 30.00 30.00 30.00 15.00 15.00

A
15.00

Fire Exit

B
15.00

EE Room Hallway

C UP
15.00

Storage Mech.Room Elev. Shaft Staircase

D
15.00

Female
Toilet
E
15.00

Male
Lobby
Toilet

F
15.00

G Canteen
1.5
15.00

Ground Floor
H 2 English Unit (Feet)
15.00

I Canteen
15.00

Building Perspective
1 1:2

HVAC Design Project number


Date
Mech 01
Drawn by
Checked by Scale As indicated
6 5 4 3 2 1
15.00 15.00 30.00 30.00 30.00 15.00 15.00

15.00 15.00 15.00 15.00

A
15.00

Fire Exit Office Space Office Space Office Space Office Space

B
15.00

Office
EE Room Hallway Space
C UP
15.00

Office
Storage Mech.Room Elev. Shaft Space
DN
D
15.00

Female Hallway Office


Toilet Space
E
15.00

Male
Toilet Office Space Office Space Office Space Office Space

F
30.00

G Office
Space 1.5
Hallway

H
15.00

Office
I Space
15.00

J
2nd-9th Floor
1 English Unit (Feet)
5.5

HVAC Design Project number


Date
Mech 02
Drawn by
Checked by ScaleEnglish Unit (Feet)
6 5 4 3 2 1
30.00 30.00 30.00 30.00 30.00

15.00 15.00 15.00 15.00

A
15.00

Fire Exit

B
15.00

EE
Room
C
15.00

Storage AHU

D
15.00

Female
Toilet
E
15.00

Male
Toilet

F
15.00

G 1.5
15.00

H
Penthouse
15.00

1 English Unit (Feet)


I
15.00

5.5

HVAC Design Project number


Date
Mech 03
Drawn by
Checked by ScaleEnglish Unit (Feet)
6 5 4 3 2 1
9144.00 9144.00 9144.00 9144.00 9144.00

4572.004572.00 4572.004572.00

A
4572.004572.004572.004572.004572.004572.004572.004572.004572.00

Fire Exit 44 45

67 64 63 61 60 59 43
B 66 65 36
37
39 41 42
EE Room 68 34 35 38 40 46
71 62 47
2 48
C 69
58 49
Storage AHU 1
70 50

D 51
52
3
Female 53
18 9 54
Toilet 4 5 6 7 8
E 20
16
19 17
15 14 13
10
55
57
Male 11 56
Toilet 12

F 22
21

Section Section Section


23 Lenght (ft) Lenght (ft) Lenght (ft)
From To From To From To
24
G 25
Fan
1
1
3
4
20
30
31
31
32
10
11
2
65
65
71
3
3
26
3 4 7 65 66 5
27 4 5 15 1 2 20 66 67 13
H 28
5 6 8 2 34 7 66 68 28
6 7 7 34 35 15 68 69 3
31 29 7 8 15 35 36 8 68 70 18
8 9 14 36 37 7
I 30
32
8 10 10 37 38 15
10 11 15 38 39 8
10 12 14 39 40 3

J 7
5
13
14
13
13
39
41
41
42
7
15
4 15 13 42 43 13

Penthouse 3
17
17
18
3
13
43
43
44
45
7
8

1 English Unit (Feet)


17
19
19
16
5
13
42
46
46
47
5
13
19 20 31 46 48 7
20 21 3 48 58 3
21 22 12 48 49 5
22 23 13 49 50 15
23 24 8 49 51 12
24 25 3 51 52 3
25 26 7 51 53 3
26 27 13 53 54 13
26 28 10 53 55 12
28 29 3 55 56 8
29 30 10 55 57 13

HVAC Design Project number


Date
Mech 04
Drawn by
Checked by ScaleEnglish Unit (Feet)
1
2
3
23 24

22 25
4 28
26
27
Piping Data
21
5 Section Lenght
1 15
2 10
20 3 10
6 4 10
5 10
6 10
19 7 10
7 8 10
9 10
10 10
18
11 10
8
12 10
13 10
17 14 10
9 15 10
16 10
17 10
16 18 10
10 19 10
20 10
21 10
15
22 10
11
23 3
24 7
25 9
14
12 26 4
27 6
28 10
13

Mechanical Piping Layout


1

Piping System Layout

Project number
Date
M-05
Drawn by
Checked by Scale

1/31/2021 6:26:49 PM