Professional Documents
Culture Documents
Presented to:
Faculty
Presented By:
Agbon, Harthi D.
BSME - IV
January 2023
1
ESTABLISHMENT PROFILE
Location: Sta. Catalina Science High School, Cawitan, Sta. Catalina, Negros Oriental
Area:157.5 m2
Number of Lights: 20
2
GROUND FLOOR PLAN
Scaling: 1:1 M
3
AIR CONDITIONING DESIGN FACTORS
Heat Gained by Occupants
Maximum people that can occupy the building is 90. They could be seating, typing, standing, or a person
may be discussing in front of a group. Let’s assume that the building is at max capacity and everyone is
Seated, Relax 60 49
Computer Typing 80 58
Standing 90 49
Discussing 105 59
Based on the activities, it is most likely that almost half of the occupants are typing, some are doing office
work,, a few are standing,while one is discussing, and thus, these activities are the bases of heat gain by
occupants.
4
Sensible Heat by Occupants
q=k∆TAt
Where:
q = heat gained, W
k = thermal conductivity of the material, W/m-K
T= change in temperature, K
A =area of walls, m²
t = thickness, m
Wall: Concrete
Door: Wooden
Area: 157.5 m²
5
a. Heat Transfer of the walls:
Wall: A2 = 57.26 m²
Floor: A2 = 157.5 m²
6
d. Total Heat Transfer (doors)
Door 1: A = 1.89 m²
t = 0.05 m (Wooden)
T=9K
Since, all four(4) doors have the same area, the obtained wattage is multiplied by 4.
Fb= ballast factor of fluorescent lamps usually 1.2 for common fluorescent fixtures
Printer 5 20 0.60 60
7
Heat Gained by Solar Energy through a Glass Window
The Building is exposed to sunshine throughout the day, specifically from 7:00 a.m. to 5:00 p.m. The
formula below is used to calculate the heat acquired by solar energy through glass during the period the
SHGF= solar heat gained factor for a single sheet of clear glass, W/m²-K
Since, there are 5 windows on the side exposed to the sun: 149.7718 x 5 = 748.859 watts
There are a glass windoms above the four (4) wooden doors which are exposed
also to the sunlight
q= 0.27m² (26.2) (1.28) (0.58) = 5.251738 watts,
Since there are 4 doors, (5.251738 watt) x (4 doors) = 21.0069 watts
8
SUMMARY OF CALCULATED LOADS
TOTAL SENSIBLE HEAT
Total Sensible Heat (Qs) = (Heat transmitted thru floors, ceilings, walls) + (Occupant's body heat) +
(Appliance & Light heat) + (Solar Heat gain thru glass) + (Infiltration of outside air)
Total Latent Heat (Moisture-laden outside air from Infiltration & Ventilation) +
9
CONCLUSION
With a refrigerating load of 16.19491259 TR, it is recommended that an air conditioning system
that can withstand this load be used, assuming that the office is fully occupied. As a result, we, the
researchers, recommend using the Aircon Rentals 1PAC-0060 60kW Package unit
10
APPENDIX
11
17 0.17 0.40 0.06 0.24
Fixture X: recessed lights, not vented, supply and return air registers below the ceiling of through
Fixture Y: vented or free hanging lights; air registers below or through the ceilings, return air registers
Entry 2 4 6 8 10 12 14 16
12
13 0.03 0.06 0.11 0.18 0.28 0.45 0.93 0.94
Cement 0.29
Glass 1.05
13
References:
https://www.ijsr.net/archive/v7i3/ART2018997.pdf
https://en.wikipedia.org/wiki/List_of_thermal_conductivities
https://www.aircon.com.au/products/reverse-cycle/60kw-package-unit/
14