Motor starting reactor as per IEC-60076-6 standard (or IS 5553 Part-3) designed, manufactured and
tested at manufacturer’s works to ensure smooth and reliable operation for the site conditions.
a) Motor starting reactor p a n e l s h a l l b e indoor, metal clad with separate metal enclosed
compartments complete with vacuum bypass device with its control circuitry, bus bars for power
cable terminations, push buttons with indicating lamps.
c) Staring current shall be limited to 3.0 to 3.5 times the full load of the motor with power factor
improvement capacitors and shall reduce it to less than 3.0Ifl if motor torque speed and pump torque
speed allows so.
d) The three phase windings of the Motor starting reactors shall be made of copper insulated winding
with insulation class F and Max.Temperature of winding shall be limited to that of class B. Motor
starting reactor should be air core type air Cooled and mounted in dust and vermin proof panel
suitable for indoor mounting. The three phase coils must be separately available for repairs in
future. Each coil must be wound on epoxy bobbin. Making a common epoxy casting for three coils is
strictly not acceptable since it avoids thermal dissipation and also any repair to one coil makes all
the three coils assembly useless.
All coils should be vacuum pressure impregnated.
f) Starting of motor shall be from either p a n e l located near to motor or shall be from PLC.
Necessary wiring diagram shall be provided, considering staring interlock, trip circuit, staring and
running mode signal and terminated suitably.
Page 1 of 6
1 Tap5
2 Tap4
3 Tap3
4 Tap2
5 Tap1
Motor starting reactor manufacture must measure impedance XL value at the shop floor at each tap
and calculate and confirm the starting current by this method. Starting current should be fully
established at ‘manufacturer’s shop floor’ by this calculation method. Further manufacturer must
prove starting current at the pumping station.
7. Design calculation must be submitted along with the tender. Manufacturer must also design the
winding such that maximum temp rise after the two consecutive starts should be less than ‘class B’.
Design calculation for temp.rise must be submitted in tender.
h) Suitable Thermistor /RTD should be embedded in to all 3 windings with digital temperature scanner
for protection. There should be audio-visual alarm in case of the temperature of coils are higher or
any such failure.
i) Manufacturer must provide a current sensing relay protection to ensure safety of coils in case the
failure.
Page 2 of 6
Rated lightning impulse KV (Peak) 75KVp–Type test certificate required for 11KV
Withstand voltage.
2.a
One minute power frequency Mandatory shop 28KV 50 Hz for one minute for 11KV
withstand test test on each
2.b
Temperature Rise Test Mandatory shop
Motor starting current i.e.,DC current of
test on each
amplitude equal to (Motor full load current x
3.5) shall be injected into all three coils for
duration of 2 consecutive start time (2 x
starting time). Temperature will be monitored
by the temperature sensors embedded inside
the coil. Temperature rise shall be less than
Class B as per specification.
Inductance measurement at all Mandatory shop Inductance should be measured using L-C-R
the four taps i.e. Design, 5% test on each meter. Based on inductance value vendor to
lower, 5% higher and 10% calculate XL value and confirm the starting
higher and 15% higher voltage. current available to motor.
3. Type Test: - Suppliers should have successfully carried out type tests within last
3 years.
Standard lightening Impulse Type Test 75KVp for 11KV motors
Test
4. Site test :
Performance Test Site Test Manufacturer should prove the motor starting
current as per design or lesser as guaranteed
by measuring the same with D.S.O. or power
analyzer.
Page 3 of 6
Relevant starting current graph should be
submitted for performance confirmation.
1. Only manufacturers or their authorized agents are allowed to quote for this job.
2. Manufacturer must have supplied and commissioned at least 5 units of 11KV voltage and KW
capacity or above during last 3years. Satisfactory performance certificate of working for more than
1year must be submitted along with the Offer.
3. Type Test Certificate valid for last three years must be submitted.
9. Bypass VC
Page 4 of 6
14 Applicable Standard IS 3914 (Motor starter
guideline standards ) /
IS 5553 part 3 / IEC 60269 /076
15 Voltage
16 Supply Frequency
17 Fault Level
18 Insulation Level
23 Type
25 Reactor Insulation
27 Method of Cooling
28 Bus bar
30 Motor protection
31 CT and PT
32 Aux transformer
Service Conditions
Page 5 of 6
30 Altitude above Mean Sea Level
Test Requirement
Factory Acceptance (FAT) will be witnesses per IS & QAP for 100% s
Below is the mandatory test to be done at the vendor shop floor
32 INSULATION RESISTANCE BEFORE H.V.
TEST (MEGGER)
33 H.V. –POWER FREQUENCY TEST FOR 1
MINUTE
28KV - Routine test for 11KV
P.F. Capacitors :-