Professional Documents
Culture Documents
Introduction
The propagation of electric waves along any uniform and symmetrical transmission
line may be deduced in terms of the results for a hypothetical line of infinite length
having electrical constants per unit length identical to those of the line under
consideration.
Is
Es
Zo
to
Infinite line
When an alternating voltage is applied to the sending end of an infinite line, finite
current will flow due to capacity and leakage conductance between the two wires
constituting the line. The value of this current will depend on these two factors and
others to be investigated later.
The ratio of the applied voltage to the current flowing will give its input impedance.
This input impedance is known as “characteristic impedance” of the line which is
denoted by Zo. In addition to Zo, the line has the following important properties:-
1
LINE CONSTANTS
If the transmission line is very short, the conductors may be considered to be short
circuits between the generator and the load and no transmission line theory is
necessary. When the line is no longer short, this is no longer the case.
In the first place, the conductors are not perfect; they have resistance and in a long
line may be greater than the resistance of the load. The total resistance of both
conductors of a unit length of line is one of the primary line constants and is quoted in
ohms per loop mile or Km.
The dielectric separating the two conductors of the line is not perfect and if the output
terminals of unit length of line is open circuited some conductance will be measured
between them. This conductance G per unit length of line is another primary line
constant, which is usually small and is quoted in Siemens/mile or Km.
When the applied voltage on the conductor is changing, the magnetic field around the
conductor also changes. This change in flux opposes the change in the current
thereby introducing inductance on the line, this inductance is measured in Henries per
loop mile and is another line constant.
Again due to the potential gradient existing between the two conductors, an electric
field exists hence a line has capacitance which is the capacitance measured per loop
mile or Km of the line whose units is the Farads.
The line constants are not obviously lumped at one end of the line but are evenly
distributed along it. The line is also symmetrical as it is in the same no matter which
end we look into. Therefore the equivalent circuit of short length of line is as follows:
L
2
CHARACTERISTIC IMPEDANCE Zo
This is the impedance seen when looking at an infinite length of line. There is always
one value of impedance which when placed across one pair terminal of a line causes
the input impedance at the other pair of terminals to have the same value. This is the
characteristic impedance and is denoted Zo. If the internal impedance of a generator
to is equal to the characteristic impedance of the line and is equal to the load
impedance, then ideal conditions exist for maximum power transfer. At high
frequencies the impedance of the inductor i.e l is very large compared with R and
the admittance c becomes very large compared to G. Hence the effects of R and G
at high frequencies can be ignored thus making the line virtually loss free and have
an equivalent circuit as shown.
Fig 2 (a)
½ LL ½ LL
Zo CL Zo
Zo
For such a case, Zo at high frequency is Zo = √(L/C). This will be derived later.
2
If a small section near the sending end of the line is removed, such that the new line
starts at terminals 3 and 4 as shown in the diagram (Fig 4) the impedance seen looking
into the terminals 3 and 4 will be Zo since the removal of the short section does not
affect the nature of the line.
Fig 4
A B
1 3
to
2 4
3
This means that the short section AB from electrical point of view was originally
terminated in an impedance Zo at B. If the short section is now terminated in an
actual impedance Zo, the current and voltage at all points along its length will be
exactly same as if it were terminated in an infinite length of line. Hence a short line
terminated in Zo behaves electrically at all points along the line a if it were an infinite
line see figure 5
Zo Zo
2
A short line is considered as a complex electrical network and at any frequency and
may be represented by a T section.
Z½ Z½
Zo
Zo Zo zIN Z2
Line (Z in =Zo)
When this short line is terminated to its Zo, it will behave like an infinite line and
have an input impedance equal to Zo. Since the section is terminated to its Zo, It must
have an input impedance equal to Zo let the T section have series aims Z ½, Z ½ and
short aims Z2 (See Fig 5)
Then Z in = Z 1 + (Z 1 + Zo) Z2
2 2
Z2 + Z 1 + Z0
2
But Z in = Zo
Zo = Z2 1 + Z 1 Z2 + Z 1 Zo + Z 1 Z2 + Zo Z2
4 2 2 2
2
Z + Z 1 + Zo
2
Zo Z2 + Z 1 Zo+Zo2 = Z21 + Z1 Z2 + Z1 Zo + Z1 Z2 + Z2 Zo
2 4 2 2 2
Consider a short line terminated on a open circuit. The equivalent T section of such a
line is shown in fig 6 (b) below
Z½ Z½
Zoc o/c
Z2
fig 6
(a) (b)
Z½ Z½
Z2
Zsc
Fig 7
Let the input impedance with a zero – impedance termination be Zsc.
Zsc = Z¼² + Z½ Z2 + Z½ Z2
Z½ + Z2
Eqn……3
Z21 + Z1 Z2
Zsc= 4
Z1 + Z2
2
5
Multiplying the short circuit impedance with the open circuit impedance gives.
But Zo = ( Z21 + Z1 Z2 )
4
Zo =
2
Z21 + Z1 Z2
4
Replacing imp Zo in 4,
-----------5
Zo = Zoc x Zsc
Hence the characteristic impedance of a line in the geometric mean of open and short
circuit impedance. This is the method used to determine the line impedance using a
bridge.
Solution
= 360000 - 40 o
Zo = 600 - 20o
LINE AT HIGH FREQUENCIES
Zo = ( jwll)2 + jwll
2 jwcl
6
As l2 is small compared with l, terms containing l2
Can be ignored. Hence
Zo = jwll = L
jwcl C
Zo = L at high frequencies.
C
This is not exact but is good enough for practical purposes at high frequencies. But
since this formulae takes no account of frequency, it follows that the characteristic
impedance of a loss free line and high frequency is purely resistive and is sometimes
denoted Ro. As the line is purely resistive its characteristic impedance can be
calculated from the physical dimensions of the line.
a a
b
“a”= Radius of conductor
“b”= Spacing between the conductors.
Inductance per foot of the conductor = 0.281 log 10 b/a µH. capacitance per foot of
the conductor = 3.677Κ ρF
Log b/a
K = dielectric constant
From Ro = L = Zo
C
-
Hence Ro= (0.281 log b/a) x 10-6
( 3.677k) x 10ˉ12
( log b/a )
7
K
COAXIAL FEEDERS
= 565.7
Is I1 I2 I3 I4
8
A B C D E
Zo To
1 KM 1 KM 1KM Fig 8
Vs Z2
Z2
Fig 4
Due to the loss introduced in the line, the current I 1 will be less than I s and in addition,
Phase shift will be introduced. Hence the ratio of I s is a vector quantity in the form
of e where is a complex quality.
is known as the “propagation constant” per km of the line. The ratio Is = e such that
= log e Is
Considering fig 4, the current I1 in terms of Z1 and Z2 is
2
II =
Z2 x Is Is = Z1 + Zo + Z2
( Z 1 + Zo + Z2 ) II 2
2 Z2
hence e = Is = 1 + ZI + Z o
II 2Z2 Z2
Giving = log e Is = loge 1 + Z ½ + Z o
II 2Z2 Z2
I1 = 1 + Z1 + Zo
I2 2Z2 Z 2
Then I s = II = I2 = I3 = e
I1 I2 I3 I4
Hence Is = Is = I1 = e2
I2 I1 I2
and Is = Is = I1 = I2 = e3
9
I3 I1 I2 I3
And in the general case
Is = Is x I1 x ….. In -1 = e n
In I1 In In
-n
In = Is X e =
This is the general equation of a current n Kms down an infinite line in terms of the
sending current and the propagation constant per Km.
Similarly the ratio of voltage to the current at any point on the line is equal to the
characteristic impendence Zo
Thus Es = EI - E2 = E3…… Es = Zo
Is I1 I2 I3 In
Hence E s = Is but Is = e n
E n In In
II II
It follows that = log e Is ; note that e gives the ratio
II
of absolute value of the current sent to that of the current received, while β gives the
phase angle between the two currents. is known as the attenuation constant per Km
of line and is measured in neppers per Km.
is known as the phase constant or wavelength constant per Km of line and is
measured in radians/km. If the length of the line is in kilometres,
Is = e ny = e n +jn
= en n
II
Conclusion
In the general case of an infinite line of a short line terminated in its characteristic
impedance and having a propagation constant , the current I at any point distance
from the sending end will be given by
10
I = Is e -
The voltage E at any point distant from the sending end will be given by.
E = Es e
Where Es is the sending end voltage.
=Es e - -
Solution
E = Es e - x
=Es e x -βx
Attenuation /Km = 3.0 dB/Km.
= 3 x 0.115 Neppers
= 0.345 nepper/Km
Hence the voltage 10 miles down the line lags the sending end voltage by 3.19 radians
that is182 47 and is attenuated to 0.0635 volts.
THE DECIBEL
Consider a four terminal network with an input power P1 and an output power P2
PI P2
N/W
Let the ratio of O/P power to I/P power be m
pn
P1 M1 P2 M
P32 P4 M3
Pn-2 Pn-2
Mn-2 pn-1 Mn-1
Then the overall power ratio Pn is the product of the individual power ratios ie.
P1
Pn = P2 x P3 x P4 x …x Pn
PI P1 P2 P3 Pn-1
This is a reference power level whose standard level is 1 mW. Using this standard
level any power P can be expressed as 10 log P referred to 1 mW. It is then
possible to express any absolute power as so many dBs above or below this reference
standard. Hence a power of 1 watt can be expressed as 10 log 1 = 30 dBm.
(1 x10-3 )
Examples. Express the following in dBm.
12
a. 1 x 10-12 watts,
b. 800 µW
c. 1000mW
d. 100 Kw
Example 2. What power in watts is represented by 25 dBm ?
THE NEPER
The loss of power on any transmission line is known as attenuation which may be
measured using the decibels or neper notation. The neper is fundamentally a unit of
current ratio but it can be used to express power ratios when the resistive components
of the impedance are equal.
To convert from nepers to dB’s or vice versa, the following formulae is used:
If a generator is connected across the terminals of a short, loss free transmission line
at high frequency, a current will flow down the line and a voltage will be developed
across it. The current and voltage must obey ohms law i.e. V = Zo.
I
As the line is not a short circuit between the generator and the load but a chain of
networks, the current and voltage will undergo a phase change i.e. the current or
voltage wave will experience a 360 phase change over, each wavelength of line. As
the line is resistive the current and voltage will be in phase.
Ro
Gen
⋋/4
Vectorial
Phase and Represent
Magnitude of 13
ation of
V and I V and I
Impedance R
=V R
I
I and V are called incident current and voltage as they are travelling from the
generator to the load. The current and voltage produced by the generator are in phase
(resistive load). A quarter wavelength down the line I and V are still in phase but
lagging V and I at the generator by 90 (i.e. having been produced a quarter of a cycle
earlier). The voltage and current half a wavelength from the generator will lag by
180 and so on. All down the line the magnitude of I and V are such that V/I = R
and when the signal reaches the load it is despatched in it as the load value is R
(maximum power transfer).
At the load howevr the value of the load is not R O but RL is infinite. Therefore the
quotient V/I has to be made to equal infinity. This can only be done by increasing V
to or by decreasing I to zero. The vector diagram shows current being decreased to
zero. In practice the current decreases to zero at the load and the voltage increases.
For the current to be zero a current equal to its magnitude must be subtracted. The
reflected current must flow somewhere and the only path open to it is along the line
RL =
IS
Gen
II Vi
Ir Vr
+
Vs
V I
Magnitude
of current
14 -and voltage
standing
waves
IR
+Magnitude
And phase
VR
-Of current
And voltage
(resultant)
Impedance
Z = VR
IR
back to the generator. In doing this, it adds or subtracts the incident current along the
line producing waveforms as shown in the diagram.
Points to note:
a. The current and voltage are no longer constant along the line but are in
the form of nodes and antinodes.
b. From the generator to the load current seems to lead the voltage by 90
thus giving the effect of a capacitor.
c. The impedance over the last (/4) quarter wave varies from zero to
infinite
RL =0
Ir IS
+Vertical
Ii Magnitude
representati
of
onI and V
Vr 15 (standing
waves)
Vi
Vs
IR +Magnitude
And phase
-Of current
VR And voltage
Impedance
Z = VR
IR
The argument in this case is the same as in open cct line but this time when the wave
reaches the load it has to adjust itself such that V/I = 0 and this can be done by
making V = 0 and I = .
Points to note:
(1) If the value of the load is greater than R O, the results obtained will be
similar to the open circuit load but not as well defined
(2) If the value of the load is less than R O the results obtained will be
similar to the short circuit load but not as well defined.
REFLECTION COEFFICIENT
If the impedance connected to the line is incorrect then the voltage and current
will be reflected back along the line to the generator. In other words mis-match occurs
and the magnitude of this mis-match is measured in terms of reflection co-efficient
(ρ). Reflection coefficient is the measure of this mismatch and is given by:-
16
ρ =VR or IR or RL – RO or RO - RL
VI II R L + RO R O + RL
Where IR and VR are reflected current and voltage respectively V and I are incident
voltage and currents. RL is the actual load and R O is the characteristic impendance.
When ρ =0 , there is no mis-match and RL =RO.
Points to Note:
(1) When a wave is propagated along the line, the wave has no way of
knowing how the line is terminated.
(2) The wave assumes that the line is corectly terminated i.e ZR =ZO.
(3) When the waves arrives at the termination it finds that Z R = ZO then all the
power is dissipated in ZR
(4) If the wave finds that ZR ≠ ZO then a reflected wave is generated and is
transmitted back along the line.
(5) The phase and magnitude of the reflected wave depends on the nature of
ZR
(6) When ZR is a short circuit or open circuit the reflected wave is of the same
magnitude as the forward wave.
(7) Voltage and current waves are both reflected back.
Vi = Incident Voltage
Ii = Incident current
Vi Vr Vt
Ir = Reflected Voltage
Ii Ir It
Vr =reflected voltage
Vt and It = resultant V and I
respectively
Zo ZR
Then It = Ii + Ir………..(i)
And Vt = Vi + Vr……..(ii)
from (i) Vt = Vi - Vr
ZR ZO ZO
Hence Zo Vt = ZR (Vi – Vr)
From (ii), Vt = Vi +Vr
Then Zo (Vt +Vr) = ZR (Vi – Vr)
ZO Vi + Zo Vr = ZR Vi – ZR Vr
ZoVr + ZrVr = ZRVI – ZoVi
Vr (Zo + ZR) = Vi (ZR – Zo)
Hence Vr = ZR – Zo but Vr = ρ
Vi Zo + ZR Vi
ρv = ZR - Zo
Voltage reflection coefficient ZO + Z R
Voltage reflection coefficient has the same magnitude as the current reflection factor.
ZR is generally complex i.e. it has both resistance and reactance hence the modulus of
voltage reflection coefficient is Vr = ZR - Zo
Vi Zo + ZR
From (ii)
It ZR = -Ir ZO + Ii ZO
But It = Ir + Ii
ZR (Ir + Ii ) = Ii ZO - Ir ZO
ZR Ir + Ii ZR = Ii ZO – Ir ZO
Ir ZR + Ir ZO = IiZO – IiZR
Ir (ZR + ZO ) = Ii (ZO – ZR)
Current reflection coefficient Ir = ZO – ZR = ρ
Ii ZR + Z O
Hence current reflection coefficient has the same magnitude as the voltage refflection
coefficient but opposite in phase.
NB: The incident wave and the reflected wave are both example of standing waves.
An incident wave and a reflected wave form an interference pattern known as
standing wave.
This is the ratio of maximum voltage or current on the line to the minimum voltage or
current in a standing wave symbol (s)
S= Vi + ρVi = Vi I + ρ
Vi - ρVi Vi I - ρ
S= I + ρ
I - ρ NB S is always 1 or equal to 1
When Z is resistive, that is the terminating impendance and line impedance are
resistive then:-
S = 1 + ZR - ZO ZR +ZO + ZR – ZO
ZR + ZO ZR - ZO
=
1 - ZR - ZO ZR + ZO - Z R + ZO
ZR + ZO ZR + ZO
= 2ZR x ZR - ZO
ZR + ZO 2ZO
Hence S = ZR
ZO
Where ZR is less than ZO then S = ZO
ZR
From S= I + ρ then the reflection coeficient can be
I - ρ
given in terms of standing wave ratio
i.e. S (I – ρ) = (I + ρ)
S – ρs = I + ρ
S - I = ρ + ρs
S - I = ρ (I + s)
Ρ = S - I
S + I
From the foregoing it can be seen that a correctly terminated line has an SWR of 1.
When S 1 then a mismatch exists and power is wasted. Hence
SPECIAL CASES
19
(b) The voltage or current on the line may become twice the supply especially for
the extreme cases i.e. open and short circuit conditions.
POWER LOSS
When SWR is not 1:1, then power is lost from the transmission line through radiation.
Let the incident power be i and the reflected power be r then.
Incident power i = Vi x Ii
Reflected power r = VR x IR
Pr = Vr Ir but Vr = Ir =r
ri V i Ii Vi Ii
STUBS
a. Stubs are used to match a complex load to the transmission line. The
purpose of the stub is to tune out the reactance with a stub which is either
capacitive or inductive depending on the nature of the load. Short circuit or
open circiut transmission lines are often used than lumped components at very
high frequencies. Hence a matching stub is a short length of transmission line
connected across a feeder and usually of the same Zo as the feeder.
L F
ZO ZR
20
/4
open or short circuit end of stub
Stubs are often used other than lumped components because they are:
(i) Cheaper than components
(ii) Simple to use
(iii) Very affective
The design features of the stub are:-
(i) Position on the feeder at which the stub is connected
(ii) The length of the stub
LF is the distance to the nearest point on the feeder to Z R at which the admittance in
=G j. Where G =GO = 1/Zo. /4 is the length of the stub having an input
susceptance of j (with the same as above but of opposite sign). Stubs may be
open circuit or short but usually the one of shorter length is used. The procedure used
to find the length (distance) of the stub from the load is as follows:-
Solution: Since the stub is used to cancel out the resitance and then to
neutralize the reactive component proceed as follows. Let Z 1 =600 + j0, Z2=
75 + j75 .then the equivalent circuit of the load is:
75 + j75 75
600 load
j75
ZL 5 +j75
But ЧL = GL + jL
jL 6.67x10-3
The stub must have a capacitive reactance of 150. This reactance can be
neutrilized by placing capacitor of
2πfc 6.28x30x106x150
of this value can do the matching but it is more practical to use a open circiut stub.
The distance from the load to the stub must be such that Vr
Ir
V
/I =150 (75+j75)
/4 35.4 PF
TRANSFORMER MATCHING
/4 WAVE TRANSFORMER
ZO Zin Zό ZR
/4
A /4 wave transformer is inserted between the load and the line in order to match the
ohmic value of the load to that of a transmission line . Consider the variation of
impedance on a quarter wave section.
Impedance of ¼ section.
22
/4
As the value of the impedance of the /4 section varies from a low value to a high value
along its length it can be used for matching. From the general line equations.
Z O + jZR tan L
Then when the line is /4 long,L = 90 then tan L = For correct matching.
Zό = ZO ZR
As this value is different from ZO and RO, then /4 section of the line must have
different dimesions i.e. spacing and thickness. Hence /4 wave trasformer is a section
of the line having different dimensions to that of the line to be matched.
ZO Zό ZR
/4
Solution:
23
L = 1 = 6.667 x 10-3 – j 6.667 x 10-3
ZL
RO = 1 = 150
GL
Rό /4 300
600 Rό = 300
/4
Example:
200 + j 75
1.64 x 10- 3
RL = 1 = = 228
GL 4.38x10-3
= 262
Example (2) What would be the SWR if a 75Ω transmission line were used to feed a
300Ω resistive load.
24
Solution: SWR = Vmax = ZO = ZR
Vmin ZR ZO
75
Example (3) Find the reflection coefficient resulting from mismatching a 50Ω load
and a 300 Ω tx line.
Solution:
ZO + ZR 300 = 50 350
Example (4) If the SWR on the line is 4:1 determine the reflection coeficient and % of
incident power reflected back from the load and % of incident power absorbed by the
load.
Solution: = S - 1
S + 1
% of reflected power 2
a. hence = 4 - 1 = 3 = 0.6
4 + 1 5
= 0.6
= 36 %
= 100 –36 = 64
The wavelength is the distance between any point and the next point along the line in
which the current or voltage is in the same phase.
IS I IR
ZL
25
A B
2
wavelength
From the figure points A and B are such two points and although current reaches a
maximum at A and B at the same instant current at A is really leading current at B by
2 radians. The phase shift along the line is radians per Km. Hence distance
= 2 Km.
Thus V = 2 f
Or V= ω
a. Resistance RL
b. Conductance GL
c. Inductance LL
d. capacitance CL
The above are primary line constants. The secondary line constants are
a. Characteristic impedance Zo
Propagation constant L
Attenuation constant L
b. Phase constantL
26
The characteristic impendance Zo will be the same as that of a complete line. The
short length of line can be represented by a T network as shown
L Z½ Z½ ½ (R+jw)L ½ (R+jwL) ℓ
Zo Z2 Zo 1
(G + jwL) ℓ
If the length of the T section is very small, Z I will approximately equal to the series
impendance of the section i.e RL + jwLℓ and the shunt section equal to 1
GL+ wLℓ
DETERMINATION OF ZO
ZO = Z12 + Z1Z2………….(i)
Gℓ + jwLℓ
4 (G + jwc) ℓ
Zo = R+jwL
G+jwC
This can be expressed in the modulus and angle form That is from
Zo = R+jwL = R+jwL ½
G+jwc G+jwC
27
G2 + w2c2
……(ii)
= R2 + w2L2 ½ (tan-1 wL/ R - tan –1 wc/G)
4 G2 + w2c2
From equation (ii) when ω is very small ; Zo =R/G and when ω is very large Zo =
L
/C . Since R/G in all cases is greater than L/C the variation of Zo with freq for a practical
line is as shown
Zo= R/G
L/C Freq
L
Variation of Zo with frequency i.e. at high freq Zo = /G and at low freq
R
ZO = /G.
DETERMINATION OF
Z½ Z½
Z2
Z2 Zo
Z1 = (R+jwL ) ℓ and Z2 = 1
(G+jwC ) ℓ
= 1+ (R+jwL)(G+jwc) ℓ 2
+ R+jwL (G+jwc) ℓ
28
2 G+jwc
…..(iii)
l
e = 1 + (R+jwL) (G+jwc) + (R+jwL)(G+jwc) ℓ 2
2! 3!
2!
l = (R + jwL)(G+jwc) ℓ
= (R+jwL) (G+jwc)
since = + j
From the equation the real part which is the attenuation constant and the imaginary
part can be also calculated. If is obtained in modulus angle notation i.e.
= P θ
C = 0.062 F/km.
Solution:
= 100 + j 6.283
= 100.2 336’
29
G + jwc = 1.5 10-6 + j x 2 x 1000 x 0.062 x 10-6
Zo = 507 - 436’
Example 2. A sample of field cable has the following primary line constants R =
78/km. G = 62s/km, L = 1.75 mH/km, C = 0.0945F/km. Calculate at 1600 Hz
(Take ω = 10,000 rads/sec) the following
(i) Zo
line in milliseconds.
Solution:
= 78 + j 17.5
= 79.94 12°39
G + jwc
30
= 79.94 12°39’
Zo = 290 -36°48’
= 0.275 49°27’
dBs ≃ 1.556dB
= 1158 / km
(iv) wavelength λ = 2 = 2 = 30 km
0.209
0.209
47840
= 2.09mSeconds
EVALUATION OF &
From = + j,
Squaring b.s.
31
2 + 2 = (R2+w2L2) (G2+w2L2) …..(i)
( + j)2 = (R+jwL)(G+jwL)
2 - 2 = RG – w2LC ………….(ii)
= ½ (R2+w2L2)(G2+w2C2) + ( RG-W2LC)
In practice certain approximations are made to obtain simplified expressions for Zo,
and . The permissible approximations for unloaded underground cables at audio
frequencies are
a. WCG and WL R
Characteristic impedance Zo
From Zo = R+jwL
G+jwc
Jwc wc
i.e. Zo ≏ R - 45
32
WC
PROPAGATION CONSTANT
= (R + jwL) (G+jwc)
= wcR + j wcR
2 2
but = + j
= wcR neppers/km
Find the approximate values of Zo, and at 400 Hz and 1600 Hz.
Solution:
Zo = R - 45
WC
At 400 Hz Zo ≈ 44 - 45
Zo ≈ 520 - 45
At 1600 Zo ≈ 44 - 45
10,000x0.065x10-6
≈ 260 -45
at 400 ≈ wcR =
2
33
≈ 2500 x 0.065 x 10-6 x 44 = 0.0598
= 0.0598 nepper/km
2 2
= 0.120 nepper/km
LOADING OF LINES
= ½ (R2+w2L2)(G2+w2c2) + ( RG –w2LC )
This shows that depends on the four primary constatnt and the frequency under
consideration.
To determine the value of L for minimum attenuation i.e when L may be varied,
differentiate W.R.T. L and equate to zero.
½ (R2+w2L2)(G2+w2c2) + ( RG –w2LC )
R2+w2L2+(G2+w2c2)
34
= w2L (G2+w2c2) - w2c = 0
(R2+w2L2)(G2+w2c2)
i.e. = L (G2+w2c2) =C
R2+w2L2)(G2+w2L2)
= L G2+w2c2 = C
(R2+w2L2)
L G2 + w2c2 = C R2 + w2L2
square b.s
L2G2 = C2R2
L = CR
This can be found in a similar manner as L where only C is considered variable. The
value for minimum attenuation may be determined by differentiating WRT to C and
equating to zero.
Hence C = LG farads/km
35
If the received signal is not an exact replica of the transmitted signal, the signal is said
to be distorted. There are three main causes.These are
G + jwc
Zo = R (1 + jw L/R)
G (1+ jwc/G)
When LG = CR then L = C
R G
Or (1+jwL/R) = (1 + jwC/G)
Zo = R 0 L 0
G C
γ 2 = (R + jwL)(G + jwc)
when LG = CR then
CR = LG = CRLG
36
Hence (CR + LG) = 2 CRLG…….(iii)
then a2 = RG
a = RG and b2 = - W2 LC b = jw LC
then γ2 = ( RG + jw LC ) 2
.
γ = RG + jw LC
= RG
and = w LC
Thus V = W = I km/sec
W LC LC
W has disappered from the velocity equation and hence V is independent of frequency.
LOADING
37
Patch Loading: This involves continous loading of sections of a cable and separated
by sections of unloaded cable. This reduces cost and gives the same advantages as
continous loading cable
Lumped loading: If inductance coils are introduced into a line at uniform intervals
along the line, This is called lumped loading. Since the inductive reactance increases
with frequency, the line behaves as a low pass filter.
Loading characteristic
1.5 Unloaded
. Continous
loading
0.5
1 2 3 4 FREQUENCY
NETWORKS
1A lumped network is a network in which the primary line constant are consolidated
(lumped)
2Balanced network – Is a network in which both legs have identical primary line
constants.
A radio frequency feeder is tranmision line whose length is very short hence l is
negligible. It is considered lossless but is electrically long i.e. several wavelengths,
this makes the phase shift to be large (jL is large) hence γ = jL. However a feeder
has certain losses due to:
EQUALIZERS
These are four terminal networks placed in the line which have a characteristic (, or
both) opposite to that of the line. It has an effect similar to loading. There are two
types of equalizers.
a. Attenuation Equalizzer
38
b. Phase equalizer
R=Ro
1 3
Z1 Z2 R=Ro
2 4
Z1 Z2 = R2 but R = Ro
Z1 Z2 = Ro2.
Z12 = Z1 R + Z2 R but R = RO
Z1+R Z2 + R
Z12 = RO
= Vin Z 34 / Ro
Vin/Vout = Ro/Z34 = R = R + Z2
RZ2 Z2
R+Z2
Vin = 1+R = 1 + Z1
Vout Z2 R
ASSYMETRICAL NETWORKS
This is a network with a different characteristic impedance on the two sides. When
dealing with such networks the term “Iterative impedance” and “image impedance”
are used in place of characteristic impedance.
R1 R2
Ro A Rs Ro B
ITERATIVE IMPEDANCE
This is defined for a four terminal network as the impedance measured at one pair of
terminals when the other pair of terminals is terminated with an impedance of the
same value.
1 3
600 600 1 3
400 2 4004
2 4
Reffering to the diagram, the impedance seen when looking into terminals 1 and
2 is 600 when terminals 3 and 4 are terminated to 600 . Similarly impedance
40
seen on the other network is 400 at 3 and 4 when 1 and 2 are terminated to 400.
When the two iterative impedance are equal (as they are in the case of symmetrical
IMAGE IMPEDANCE
These are defined as two impedance’s which are such that when one of them is
connected across the appropriate pair of terminals of a network, the other is presented
at the other pair of the terminals.
From the diagram it can be seen that the impedance looking at terminals 1 and 2 is
300, when terminals 3 and 4 are terminated to 600. Similarly the impedance seen
at 3 and 4 is 600 when terminals 1 and 2 are terminated to 300. NB An
asymmetrical network is correctly terminated when it is terminated to its image
impedance. For symmetrical network image impedance is the same as iterative
impedance and the name characteristic impedance is used for both.
I1 I2
E1 E2 Zo2
Zo1 Zo2
θ
Thus e = E 1 I1 θ = 1/2 log e E1I1
E2I2 E2I2
θ = log e E1I1
E2I2
The real part of θ is known as the image attenuation constant and the imaginary
part is known as the image phase constant.
INSERTION LOSS
41
When a network is introduced between the generator and the load, the resultant
reduction in power in the load is known as insertion loss of the network. This loss is
expressed in neppers or dBs. Consider the case of a generator of internal impedance
Zo connected to a load ZL.
I1
Zg=Zo ZL
Let the current flowing be II If a four terminal network having image impedances Z OI
and ZO2 and image/transfer constant θ be inserted between the load and the generator
i.e.
I1 I2
Zg Z02 ZL
Zo1 θ = A+j Zo2
Then the current to the load will be altered to some value say I2
E2I2 P2
Example 1: An Asymmetrical τ pad has series arms 100 and 200 respectively and
a shunt arm of 50. Calculate the image and iterative impedance of the pad.
1 100 200 3
RoA 50 RoB
2 4
(i) The image impedance seen from terminals 1 and 2 is the characteristic
impedance. Therefore
42
Rsc = 100 + 200x50 = 140
250
150
RoB ≃ 242
it erative impedance
100 200
1 3
R2 R1 50 R2 R1
2 4
250 + R1 250 + R1
from x = - b b2 – 4ac
2a ,
= - 50 387.3
43
2
= - 50 193.6
R = - 244 or 144
R1 = 144
150 + R2
R2 = - b b2 – 4 ac = 100 10000+4x1x35000
2a 2
R2 = 244
80 80
c. Hence or otherwise show that the insertion loss of the network between this
source and the load is independent of the impedance of the load.
d. If the impedance of the load is Zo will the insertion loss of the network vary
with the internal impedance of the source (C&G 1962)
44
Solution: a. Zo = Zsc Zoc, Zoc = 80 + 120 = 200
120+80 200
Zo = 160
160 120
1v 2
120 x 1 = 120 = 1
160+80+120 360 3
160+80+120 360
= 80 + 80 = 160
(c) The output terminals may be represented by a source of 1/3 V Rms and the
internal impedance is 160. Reffering to the original circuit, it may be shown as:
I1 = 1V
Zo R
Zo + R
IV When a network is inserted the source is effectively
45
I2
R
I
/3v
The current I2 now flowing in the load is V/RT = 1/3 ÷ (Zo +R)
= I2 = 1/3(Zo + R)
= 20 log 1 ÷ 1
Zo + R 3(Zo + R)
=20log 1 x 3 (Zo + R)
(Zo + R)
= 20 log 3
II I2
II 80 80
Zx
Zx
120 Zo
Zo
IV IV
Zo + Zx
46
120 + 80 + Zo
I2
Zo + Zx 120
120
Z1/2 Z1/2
2Z2 2Z2
Z1/2 Z1/2
2Z2 2Z2
section.
Z1/2 Z1/2
2Z2 2Z2
½ T section or ½ section
ITERATIVE IMPEDANCE
Z1/2 Z1/2
47
2Z2 Z’01 Zo2
Zo’2
The two iterative impedances of a half section may be found by calculating the input
impedance of Z’o1 when the section is terminated at the other pair of terminals in Z’o1.
2 2Z2 + Z’O I
2 4
2a
4 16
2
Z’O2 + Z1Zo’2 = Z2Z1
2 4
48
Zo’2 = -Z1 ± Z1 + 21Z2
4 16
IMAGE IMPEDANCE
Z1/2 Z1/2
1 3 1 3
Zo’1 2Z2 Z0’2 Z’01 2Z2
Zo’2
2 (a) 4 2 (b) 4
From fig (a) Zo1 = Z1 + 2Z2 Zo2 (Zo connected 1:1 3&4)
2Z2 + Zo2
Zo2 4Z2
2Z1Z2 = 2Z01Zo2
Zo1
÷ RHS by 4, ZO12 = Z1 + Z2
Z1Z2 4
Z2
Zo2
Z1Z2 = Z ¼ + Z2
Zo22 Z2
Zo22 = Z1Z22
Z ¼ + Z2
50
Z ¼ +Z2 Z ¼ 2 + Z1Z2
Hence the image impedance of two sides of a half section connecting the series
impedance Z1/2 and shunt impedance 2Z2 are thus seen to be Zo T and Zo. These
impedances are equal to the characteristic impedance at T section and section having
a total series Impedance Z1 and total shunt impedance Z2 which are produced by
combining such two half sections.
(a)
Z 1/2 Z 1/2
From the theory already covered, it has been seen that a transmission line suffers from
radiation loss, resistance and leakage losses. An open wire can be used up to a max of
200 mHZ beyond which the losses became too large. These losses are due to
(i) radiation (ii) skin effect losses etc. A coaxial cable can practically be used upto
3GHZ but above that the dielectric losses between the outer and inner conductor are so
large and hence impractical. The solution to this problem is the use of wave guides or
fiber optic cables.
51