You are on page 1of 5

The Journal of Engineering

The 14th IET International Conference on AC and DC Power


Transmission (ACDC 2018)

Analysis of application effect of 220 kV UPFC eISSN 2051-3305


Received on 21st August 2018
Accepted on 17th September 2018
demonstration project in Shanghai grid E-First on 25th October 2018
doi: 10.1049/joe.2018.8364
www.ietdl.org

Yong Cui1 , Yinghui Yu1, Wei Bao1, Yuyao Feng1, Qiang Guo1, Wei Xie1, Minjie Jin1
1Electric Power Research Institute, SMEPC, Shanghai, People's Republic of China
E-mail: yongzhe578@163.com

Abstract: The feasibility study of unified power flow controller (UPFC) application in 220 kV Shanghai Grid is conducted based
on the analysis of the practical operation of the grid. The location selection method and scheme are proposed for the application
of 220 kV UPFC demonstration project. The application effect of the demonstration project of UPFC is evaluated from various
perspectives including enhancement of interface transfer capability, improvement of voltage stability performance of the grid and
contribution to balancing of reactive power in 220 kV sectionalised systems.

1 Introduction operated closely to the maximum transmission capability.


Meanwhile, as overhead lines and cables both exist on some
Unified power flow controller (UPFC) is generally considered to interfaces, the transfer capability of the interfaces may be
be the most versatile Flexible Alternative Current Transmission significantly restricted due to parameter imbalance.
Systems (FACTS) device with wide control range and outstanding Shanghai Grid receives substantial power from the aggregated
control performance [1]. UPFC may realise separate or hydraulic power plants in southwest China through four High
simultaneous control of bus voltage, active and reactive power of Voltage Direct Current (HVDC) systems. Due to large-capacity
the branches through adjustment of the magnitude or phase angle power import (accounting for around 50% of the peak load of
of the voltage output from the converters at the series side or Shanghai Grid) and peak regulation requirements, a large number
parallel side [2]. UPFC provides an efficient way for power flow of local units have to reduce their output and even be shut down.
control and enhancement of interface transfer capability. In The dynamic reactive power support of the receiving-end grid is
addition, it may achieve the benefits of strengthening dynamic weakened consequently, which exacerbate the voltage stability
reactive power support capability, improving dynamic reactive performance of the grid [9].
power and voltage control and enhancing voltage stability of the The operation of Shanghai Grid has been constantly challenged
grid [3]. by the problems of low voltages during peak load hours and high
At present, three UPFC projects have been put into service voltages during low load hours, which is mainly attributed to the
abroad, which including the UPFC project at Inez substation in the difficulty of reactive power and voltage control in the grid. In some
US [4], the UPFC project at 345 kV substation of Marcy, New areas, bus voltages during peak load hours are relatively low due to
York State [5] and the project Kangjin substation in Korea [6]. In a shortage of capacitive reactive power while in the areas with
China, a 220 kV UPFC project has been accomplished in west wide applications of cables, bus voltages during low load hours are
Nanjing Grid [7, 8]. These UPFC projects are generally quite high due to the difficulty of inductive reactive power
implemented to enhance the transmission capability and to improve balancing [10].
the reactive power and voltage support of the grid, and such The analysis above shows that the operation of Shanghai Grid
objectives have been achieved through the operation practice of needs to be optimised in the following major aspects involving
UPFC. improvement of interface transfer capability, enhancement of
The feasibility study of applying UPFC in the grid of voltage stability of the grid and balancing of reactive power in the
metropolitan area of the large city is conducted by Shanghai Grid sectionalised grid. As UPFC possesses benefit in all these aspects,
co. in accordance with grid operation necessity and the implementation of UPFC demonstration project may help Shanghai
implementation plan of the National High Technology Research Grid to develop a comprehensive and integrated solution to the
and Development of China 863 program. In this paper, the operational problems.
necessity of UPFC application in Shanghai Grid is investigated
based on analysis of grid operation practice. The UPFC location
selection rules and process are proposed, and the location selection 2.2 Location selection of UPFC demonstration project
scheme of UPFC demonstration project is determined upon To determine the appropriate location for application of UPFC
evaluation. The circuit configuration and control strategy of the demonstration project in 220 kV Shanghai Grid, 220 kV
UPFC device are presented, and the application effect of UPFC substations with necessity and space for UPFC installation need to
demonstration project on Shanghai Grid is evaluated from the be selected for further evaluation. The optimal location for UPFC
perspectives of improvement of interface transfer capability, grid application is then determined upon comprehensive analysis.
voltage stability and reactive power balancing of the sectionalised Due to the fact that 220 kV substations built up employ contact
grid. design and Gas Insulated Switchgear (GIS) equipment, there is no
adequate space for UPFC to be installed in these substations. In
2 Location selection study of UPFC contrast, in those relatively older substations, space may be
demonstration project in Shanghai Grid obtained through the replacement of the traditional equipment with
much more space-saving GIS equipment. The implementation of
2.1 Necessity analysis the UPFC demonstration project may be combined with the
As the largest city grid of China, Shanghai Grid is characterised by upgrade plans of those substations. In accordance with the analysis
high load density and extremely limited land resources for building above, three 220 kV substations (Yunzaobang, Changchun and
up new transmission lines. Some transmission equipment are
J. Eng., 2019, Vol. 2019 Iss. 16, pp. 758-762 758
This is an open access article published by the IET under the Creative Commons Attribution-NonCommercial-NoDerivs License
(http://creativecommons.org/licenses/by-nc-nd/3.0/)
Fig. 1 Configuration of the grid within the vicinity of UPFC

Fig. 2 Circuit diagram of UPFC demonstration project

Gumei) are determined for location selection of UPFC side reactor, thyristor-controlled bypassing breaker, breakers and
demonstration project. switch disconnectors. The series transformer of the UPFC with the
Effects of UPFC application in these three substations are rated capacity of 50 MVA is designed as an outdoor oil-immersed
analysed. The analysis indicates that the application of UPFC in three-phase three-winding transformer with no-load tap changer
Yunzaobang substation may improve the transfer capability of and the winding connection mode of III, yn0d11. The leakage
Yunzaobang–Zhabei interface effectively through power flow impedance voltage of the series transformer is 12%, and natural
control and enhances voltage control capability of the sectionalised oil-cycling self-cooling design is employed. The parallel
grid of Yanghang as well as the voltage stability of the grid while transformer of the UPFC with the rated capacity of 100 MVA is
UPFC applied at Changchun substation or Gumei substation is designed as an outdoor oil-immersed three-phase three-winding
solely employed as dynamic reactive power source providing transformer with no-load tap changer and the winding connection
benefits of voltage control to the sectionalised grid but no mode of Y, yn0d11. The neutral point at the valve side of the
contribution to improvement of transfer capability. parallel transformer is grounded through a resistor. The leakage
Therefore, Yunzaobang substation is determined to be the impedance voltage of the transformer is designed to be 10%, and
optimal location for application of UPFC demonstration project the natural oil-cycling self-cooling method is employed. The rated
through evaluation of space considerations and application capability of the modularised multi-level converter is 50 MVA. The
benefits. rated DC voltage and the rated AC line voltage are 20.8 and 19.2
kV, respectively. The rated AC current and the rated arm-path
3 Design and control strategy of UPFC current are 752 and 900 A, respectively. The quantity of the arm-
path sub-modules is 28(26 + 2). The parameter of IGBT is 3300 V/
demonstration application 1500 A. The reactance of the dyr-type arm-path reactor is 7 mH.
3.1 Circuit of UPFC The short-duration fault current with standability of the thyristor-
controlled bypassing breaker is 9.94 kA/100 ms.
The Zhabei–Yunzaobang interface consists of three lines including
Zha–Yun2258, Zha–Yun2210 and Zha–Yun2205. Due to the fact
that the impedance of Zha–Yun2258 differs considerably from that 3.2 Control strategy
of the other two lines, power flow distribution on this three-line The UPFC's control strategy of AC bus voltage is demonstrated in
interface is uneven, the transfer capability of the interface is Fig. 3. It may be observed that the bus voltage control of UPFC is
restricted consequently. In order to improve the transfer capability realised through control of AC reactive power and DC current
of the interface through equalising the power flow on the three which is completed by the converter.
lines, UPFC may be installed on Zha–Yun2258 line. Fig. 1 The UPFC's control strategy of power flow is demonstrated in
illustrates the installation location of UPFC on Zhabei–Yunzaobang Fig. 4. The method of decoupling the active power control and
interface and configuration of the grid within the vicinity. reactive power control enables the controls of active power and
Fig. 2 displays the circuit diagram of the UPFC demonstration reactive power to be independent, and the open-loop voltage
application. The AC side of UPFC is connected into the 220 kV injection control is provided.
grid through its series part and parallel part. Switching the switch The functionality provided by the control system of the UPFC
disconnectors and breakers enables the device to be operated as demonstration project includes DC voltage control, AC bus voltage
UPFC, SSSC, single STATCOM or double STATCOMs. Table 1 control, shunt compensation control, constant power flow control
presents the status of the switch disconnectors and breakers under of transmission line and interface power flow equalising control
various operation modes of the device. [11–13].
The UPFC device for demonstration project is composed of the
series transformer, parallel transformer, converter valves, bridge-
J. Eng., 2019, Vol. 2019 Iss. 16, pp. 758-762 759
This is an open access article published by the IET under the Creative Commons Attribution-NonCommercial-NoDerivs License
(http://creativecommons.org/licenses/by-nc-nd/3.0/)
In addition to maintaining stable voltage, the converter at the i. Constant power flow control: The active power and reactive
parallel side of the UPFC may realise the following functionalities: power of Zha–Yun 2258 line may be controlled to the
designated values.
i. Shunt compensation control: Reactive power may be sent to ii. Interface power flow equalising control: The power flow of
the grid or absorbed from the grid in accordance with the Zha–Yun2258 line may be controlled in accordance with the
commands of the local control system or the remote operation conditions and transmission capabilities of the three
dispatching centre. The maximum reactive power adjustment lines on Zhabei–Yunzaobang interface so as to keep the power
capability may be within [−50 Mvar, 50 Mvar] under the flow on the three-line interface equalised.
operation mode of single STATCOM while the maximum iii. Operation rating-based power flow control: When the Zha–
reactive power adjustment capability may be within [−100 Yun2258 line is operated within its rating, the voltage
Mvar, +100 Mvar] under the operation mode of double introduced into the line by the converter will be zero, and no
STATCOMs. power flow control is implemented. When the power flow of
ii. AC bus voltage control: When the voltage of 220 kV Zha–Yun2258 line is beyond its operation rating, the converter
Yunzaobang bus varies beyond the allowable operation range, will respond and control the power flow to be within the rating.
UPFC may send or absorb reactive power so as to keep the bus
voltage within the allowable range. In addition, UPFC's fault ride-through capability makes it be
able to maintain operation upon fault occurrence in the system
The converter at the series side of the UPFC introduces a series within certain vicinity [14].
voltage into the transmission lines and realises control of the power
flow consequently. Its major control functionality includes

Table 1 Breaker status of UPFC device under various modes


STATCOM1 STATCOM2 Double STATCOMs UPFC SSSC
QS01 close close close close open
QS02 close close close close open
QS11 open open open close close
QS12 open open open close close
QS13 close close close open open
QS14 close close close close close
QS21 close close close close open
QS31 open open open open close
QS41/QS42 open open open close open
QF01 close close close close open
QF11 open open open open open
QF12 close close close close close
QF21 close close close close open
QF22 close close close close open
QF23 close open close close open
QF31 open open open close close
QF32 open open open open open
QF33 open close close open open

Fig. 3 Control strategy of AC bus voltage

Fig. 4 Control strategy of transmission line power flow

760 J. Eng., 2019, Vol. 2019 Iss. 16, pp. 758-762


This is an open access article published by the IET under the Creative Commons Attribution-NonCommercial-NoDerivs License
(http://creativecommons.org/licenses/by-nc-nd/3.0/)
Fig. 5 Power flow of the grid upon loss of Zha–Yun 2201 line (570 MW)

Fig. 6 Power flow of the grid with UPFC upon loss of Zha–Yun 2210 line (620 MW)

Fig. 7 Power flow of the grid with UPFC upon loss of Zha–Yun 2210 line (620 MW)

Fig. 8 Step response of reactive power from 0 to 50 Mvar

4 Application effect analysis of UPFC 4.2 Improvement of voltage stability


demonstration project To accommodate the substantial power imported from the
The application effect of UPFC demonstration project in Shanghai aggregated hydraulic power plants in Southwest China, a large
Grid is evaluated from various perspectives including enhancement quantity of the local units in Shanghai Grid have to be shut down,
of interface transfer capability, improvement of grid voltage which exacerbates the voltage stability performance of the grid.
stability and reactive power balancing in the sectionalised grid. The analysis indicates that Yanghang sectionalised grid (where
Yunzaobang substation is located) is susceptible to high risk of
4.1 Enhancement of interface transfer capability voltage instability. The application of UPFC in this sectionalised
grid may provide dynamic reactive power support and improves
Zhabei–Yunzaobang interface consists of three lines which are the voltage stability of the grid consequently. Fig. 8 presents the
Zha–Yun2258, Zha–Yun2210 and Zha–Yun2205. The underground reactive power response of UPFC upon receiving the command of
cable circuit of Zha–Yun2258 has the maximum transmission stepping the reactive power from 0 to 50 Mvar.
capacity of 310 MW, and the other two lines both consisting of an It may be observed that the step response time is only 20 ms
overhead transmission part and underground cable part possess the while the over response and steady control error upon step
maximum transmission capacity of 310 MW upon enhancement of response process are both 2% [15]. It indicates that UPFC is able to
dynamic transmission capability. However, unequalised power provide rapid reactive power response and stable control
flow exists on this three-line interface due to impedance performance.
unequalisation. Zha–Yun2258 with smaller impedance carries The voltage stability analysis results indicate that application of
larger power flow than the other two lines, which contributes to the a UPFC with the maximum reactive power output of 50 Mvar in
fact that the transmission capability of the interface is restricted to Yunzaobang substation may improve the voltage stability margin
570 MW by the overloading of Zha–Yun2258 line under N − 1 of Shanghai Grid under the critical contingency by 500 MW
contingency of loss of Zha–Yun2210 line. Fig. 5 illustrates the accounting for 1.6% of the peak load of Shanghai Grid. The
power of the interface under the critical N − 1 contingencies. voltage stability analysis results are summarised in Table 2.
As UPFC is installed at Zha–Yun2258 line, power flow of 2258
line may be controlled rapidly and effectively, and the power flow 4.3 Reactive power balancing of sectionalised grid
on the interface becomes equalised. Consequently, the transmission
capability of the three lines may be fully utilised and the transfer The difficulty of inductive reactive power balancing has always
capability of the interface may be improved to 620 MW. Fig. 6 challenged the operation of Shanghai Grid. The reactive power
displays the power flow of the interface under N − 1 contingency of balancing analysis indicates that there is inductive reactive power
loss of Zha–Yun2210 line upon the application of the UPFC shortage of 110 Mvar in Yanghang sectionalised grid.
demonstration project. As cable circuits commonly applied around Yunzaobang
When Zhabei–Yunzaobang interface with no UPFC installed substation contribute considerable charging power, the application
carries the power flow of 620 MW, the power flow of the interface of UPFC may absorb the capacitive reactive power and provide
under N − 1 contingency of loss of Zha–Yun2210 line is shown in inductive reactive power compensation effectively. It may provide
Fig. 7. It may be observed that the power flow on Zha–Yun 2258 the maximum inductive power compensation of 100 Mvar under
line has reached 330 MW and exceeded its maximum transmission the operation mode of double STATCOMs, which alleviates the
capability of 310 MW. difficulty of reactive power balancing in 220 kV sectionalised grid
Therefore, the application of UPFC on Zha–Yun2258 enables of Yanghang. In addition, UPFC may provide capacitive reactive
the transfer capability of Zhabei–Yunzaobang interface improved power compensation when the capacitive reactive power shortage
from 570 to 620 MW. exists in the grid during peak-load hours.

J. Eng., 2019, Vol. 2019 Iss. 16, pp. 758-762 761


This is an open access article published by the IET under the Creative Commons Attribution-NonCommercial-NoDerivs License
(http://creativecommons.org/licenses/by-nc-nd/3.0/)
Table 2 Voltage stability margin of the Shanghai grid under the critical contingencies (MW)
Operation mode Base load Load increment margin with UPFC Load increment margin without UPFC
normal operation 31,000 7070 7110
loss of one transformer at Yanghang substation 6310 6460
loss of Xuhang–Yanghang double lines 5210 5410
blocking of Fufeng DC system 4200 4490
blocking of Fufeng and Yihua DC systems 3520 4020

5 Conclusions [3] Wang, H., Qi, W., Qiao, L., et al.: ‘A three-bus power injection model of
UPFC and its engineering application’, Power Syst. Prot. Control, 2016, 44,
UPFC provides a feasible and comprehensive solution to the major (18), pp. 145–151
[4] Schauder, C., Keri, A., Edris, A., et al.: ‘AEP UPFC project:installation,
problems in the operation of Shanghai Grid including interface commisioning and operation of the ±160 MVA statcom (phase1)’, IEEE
power flow control, grid voltage stability improvement and Trans. Power Deliv., 1998, 13, (4), pp. 1530–1535
reactive power balancing of 220 kV sectionalised grid. [5] Arabi, S., Hamadanizadeh, H., Fardanesh, B.: ‘Convertible static compensator
A 220 kV Yunzaobang substation is selected to be the location performance studies on the NY state transmission system’, IEEE Trans.
Power Syst., 2002, 22, (7), pp. 56–57
for the application of UPFC demonstration project based on a [6] Kim, S.Y., Yoon, J.S., Chang, B.H., et al.: ‘The operation experience of
comparison of space-taking, installation location and application KEPCO UPFC’, Electr. Mach. Syst., 2005, 3, (3), pp. 2502–2505
effect of UPFC, and the UPFC is determined to be installed on [7] Cai, H., Qi, W., Huang, J., et al.: ‘Application of UPFC in Nanjing western
Zha–Yun225 line so as to solve the unequalised power flow power system’, Electr. Power Constr., 2015, 36, (8), pp. 73–78
[8] Chen, G., Li, P., Yuan, Y.: ‘Application of MMC-UPFC on Nanjing western
problem of Zhabei–Yunzaobang interface due to impedance grid and its harmonic analysis’, Autom. Electr. Power Syst., 2016, 40, (7), pp.
unequalisation. 121–127
The application of UPFC demonstration project on Zha– [9] Cui, Y., Feng, Y., Yang, Z.: ‘Research on key technologies of ‘high-level
Yun2258 line may improve the transfer capability of Zhabei– power import and scale-reduced online’ off-grid safe operation’, Shanghai
Energy Conserv., 2015, 34, (6), pp. 302–306
Yunzaobang interface from 570 to 620 MW and increase the static [10] Chen, B., Yin, T., Huang, Y., et al.: ‘Reactive power issues of shanghai power
voltage stability margin under the critical contingency by 500 MW grid under the background of AC-DC electric power from external regions’,
accounting for 1.6% of the peak load of Shanghai Grid. The Power Syst. Clean Energy, 2014, 31, (4), pp. 66–71
application of UPFC demonstration project in 220 kV sectionalised [11] Cui, F., Song, J., Zhou, F., et al.: ‘Dynamic modeling and internal
characteristic simulation analysis of UPFC based on MMC’, Smart Grid,
grid of Yanghang enables the inductive/capacitive reactive power 2014, 2, (12), pp. 1–12
shortage during valley/peak load hours to be effectively resolved [12] Zhang, Z., Jiang, D.: ‘Control strategy simulation of UPFC based on modular
and helps to realise reactive power balancing in the sectionalised multilevel converters’, Power Syst. Prot. Control, 2012, 40, (3), pp. 73–77
grid. [13] Liu, Q., Ma, P., Zou, J.: ‘Solution to negative interaction caused by reactive
power flow controlling of UPFC’, Power Syst. Prot. Control, 2016, 44, (6),
pp. 76–81
6 References [14] Zhuang, L., Zhang, Y., Jing, X.: ‘Simulation research of MMC_UPFC indirect
current control strategy based on RTDS’, Power Syst. Prot. Control, 2016, 44,
[1] Gyugyi, L.: ‘The unified power flow controller: a new approach to power (16), pp. 56–62
transmission control’, IEEE Trans. Power Deliv., 1995, 10, (2), pp. 1085– [15] Zhou, F., Lu, Z., Yu, H., et al.: ‘Research on high power hardware-in-loop
1097 simulation and test technology of unified power flow controller’, Power Syst.
[2] Chen, Y., Li, L., Zhang, F., et al.: ‘Study on novel power flow control method Technol., 2016, 40, (3), pp. 861–867
of UPFC based on bus current-injection’, Power Syst. Prot. Control, 2014, 42,
(2), pp. 69–74

762 J. Eng., 2019, Vol. 2019 Iss. 16, pp. 758-762


This is an open access article published by the IET under the Creative Commons Attribution-NonCommercial-NoDerivs License
(http://creativecommons.org/licenses/by-nc-nd/3.0/)

You might also like