Professional Documents
Culture Documents
SERENTICA RENEWABLES
Serentica INDIA 3 PVT. LTD.
Project:
290MWP/200MW SOLAR PV PLANT AT
GADAG, KARNATAKA
Owner’s Engineer:
EPC CONTRACTOR:
DOCUMENT TITLE:
OIL SUMP PIT DETAILS & NIFPS FOUNDATION DETAILS
Total No. of
Doc./Dwg. No.: SG02KS-AIPL-PVP-CIV-FND-038 Rev No.: 01
Pages: 13
Stamp:
REVISION STATUS
Prepared Reviewed Approved
Rev
Name Date Name Date
No. Name Date
Mech Elec Civil C&I
00 PVN 09-10-2023 PKA 09-10-2023 VRV 09-10-2023
01 PVN 09-10-2023 PKA 08-11-2023 VRV 08-11-2023
M/s. AMARA RAJA INFRA PVT. LTD
290MWp/200MW SOLAR PV
PLANT AT GADAG,
KARNATAKA
Serentica Doc. No.: SG02KS-AIPL-PVP-CIV-
FND-038
OIL SUMP PIT DETAILS &
NIFPS FOUNDATION Rev. No.: R1 Date: 08.11.2023
DETAILS
REVISION SUMMARY SHEET
Rev
Details / Description Date
No.
00 FOR APPROVAL 09-10-2023
Page 2 of 2
OIL SUMP PIT DETAILS & NIFPS
FOUNDATION DETAILS
M/S AMARA RAJA POWER SYSTEMS LTD
1.80 1.24
LV SIDE
HV SIDE
1.5 4.00
Radiator support
3.75
2800
7.10
2
Moment due to earth pressure = 161 x 0.25 /6x 1
= 1.7 kgm
2
Hence design moment at base of wall = 270 x 0.3 /6x 1
= 4.05
i) Main reinforcement :
Mu / bd² = 1.5 x 27.6 x 9.81 x 1000
2
1000 x 56
= 0.13 N/mm²
From Table 3, SP 16 Pt = 0.070
Percentage of steel required = 0.12 (pt min.)
M/S AMARA RAJA POWER SYSTEMS LTD
moment at base of
wall = 1454.6 x( 1 - 0.1 )²/ 2
= 589 kgm
Effective depth provided = 150 - 40 - 4
= 106 mm
Mu/bd² = 1.5 x 589 x 9.81 x 1000
1000 x 106 ^2
0.771 N/mm²
From Table 3, SP 16 Pt = 0.184
Pt min = 0.12
Area of steel required = 0.184 x 10.6 = 1.95 cm²
Therefore provide 8 dia bars at 200 mm c/c bothways at top & bottom
Area of steel provided 2.51 cm² > 1.95 Hence Safe
Max. allowable Spacing of reinforcement bar= 3x 106 = 318 mm
> 200 Hence Safe
As per CEA Guideline We are providing Soak pit Oil capacity of 150% we donot required Burnt oil pit for the Soak pit.
How ever we are providing Burnt oil pit for NIFPS - System As per the NIFPS Specification ( Doc - SG02KS-AIPL-PVP-ELE-DTS-006 )
, shown in the table below:
The design calculation of Burnt Oil pit for NIFPS is illustrated below:
Inputs
1 Size of the Tank, (1.5x1.5x1.000M)
2 Length of the Tank (Clear), Clt = 1.500 m
3 Height of tank, Tw (Including free board) = 1.200 m
4 Free board depth considered = 0.200 m
5 Width of Tank, Wt = 1.500 m
2
6 Net Safe Bearing Capacity of the Soil = 11.000 T / m
3
7 Unit Weight of Soil = 1.800 T / m
8 Angle of repose = 15 (Assumed)
9 Grade of Concrete = M 25
3
10 Density of oil gw = 0.87 T / m
3
11 Density of Concrete = 2.50 T / m
Allowable Stresses in Concrete
(as per table -1 part 2 of IS 3370)
2
(i) Direct Tension = 13 Kg / cm
2
(ii) Tension Due to Bending = 18 Kg / cm
16 Min. Reinf: = Minimum steel for HYSD bars @ 0.12% per face
(0.24% overall), for length of the member less
(as per cl.8.1.part-2 of IS 3370)
than 15m
b/2 b/2 Y
Fixed 1.000
wa X
1.700
Allowable stress in concrete from tension Due to Bending, scb = 18 Kg / cm2
Design Of Wall
Case II : When the tank is empty - Soil & surcharge pressure from outside
At a Depth of 1.200 m
2
Total = 1.55 T / m
Span along shorter side lx = 1.50 m
Span along longer side ly = 1.50 m
ly / lx = 1.00 < 2
= Two way slab
Mb x 6
\ Thickness of Slab required, ts = = 8.07 cm
scb
2
= 82.73 mm
Required 10 mm @ 250 mm c/c on the Longer side at top & bottom
Ast provided = 314 mm
2
IS 3370 (P-II) Permissible Bending tensile stress in concrete = 1.8 N/mm( σcbt )
ly / lx = 1.555 / 1.565
= 1.0 < 2 Hence, Two Way Slab
Depth of Slab
Assume Depth of Slab = 100 mm Thinkness of finish = 50 mm
Clear cover = 30 mm
Load on Slab
Density of concrete (RCC) = 25 kN/m3
Steel grade = Fe 500
Concrete Grade =M 30
= 16.532 kN
Shorter Span Longer Span
At midspan At Midspan
Mx(+ve) = 0.056 x 16.5322688 Mx(+ve) = 0.056 x 16.532
= 0.93 kNm = 0.93 kNm
Mu/bd
(+ve) = ( 0.9 x 10 6
x 1.5 ) Mu/bd2 (+ve) = ( 0.93 x 10 6
x 1.5 )
2 2
( 1000 x 65 ) ( 1000 x 55 )
= 0.329 = 0.459
From Table 3 of SP-16 From Table 3 of SP-16
Pt(+ve) = 0.077 Pt(+ve) = 0.108
Hence Provide 8 dia bars @ 250 c/c Hence Provide 8 dia bars @ 250 c/c
2 78.00 2 66.00
= 201.1 mm
Ast provided > mm2 Ast provided = 201.1 mm > mm2
Hence safe Hence safe
k3 = Topography factor. = 1
= 32.571 m/s
= 0.6 x 32.571 ^ 2
2
= 636.5 N/m
2
= 0.6365 Kn/m
2
= 64.91 Kg/m
Design Wind pressure : ( as per cl. 7.2 of IS : 875 )
Pd = Pz ka kd kc
Wind Directionality factor (IS 875-Part III, Sec 7.2.1), Kd = 0.9
Area Averaging factor (IS 875-Part III, Sec 7.2.2, Table-4), Ka = 0.95
Combination factor ( IS875-Part III ,Clause 7.3.3.13) Kc = 0.9
Pd = 49.95 kg/m²
= 50 kg/m² (Say)
ii. Wind on Solid members - flat sided : (NIFPS)
Force co - efficient cf = 2
(From Table - 31, IS 875 , part 3 for flat sided individual members )
X Y
MX+MXY MY+MXY
0.4 0.3 Top
0.3 0.4 Bottom
SQX SQY
0.03 0.039 Top
0.04 0.022 Bottom
M/S AMARA RAJA INFRA PVT LTD
2
Maximum base pressure from STAAD = 0.02 kN/m
2
Net bearing pressure of soil = 148.00 kN/m
Safe (from soil test report)
DATA
2
Grade of concrete fck = 25 N/mm
2
Grade of steel fy = 500 N/mm
Thickness of wall @ base level Dc = 350 mm
Assume Thickness of base slab D = 150 mm
Clear cover Dc = 30 mm
Effective depth d1 = D-Dc-dm/2 = 115.00 mm
DESIGN OF BASE SLAB
Factored Bending moment about XX @ Bottom Mux = 0.39 kN.m b= 1000
Effective depth Required dreq = √ (Muz/0.133*fck*b) = 10.83 < d
Effective depth Provided dpro = 115.00 mm
Hence Depth Provided Ok
AST CALCULATION ABOUT X-X DIRECTION @ BOTTOM : consider
2
Mux/bd = 0.0295 singly
Percentage of Steel Required From SP-16, P = 0.007 % ( As per clause
Minimum area of steel = 0.0012*b*D 26.5.2.1 of IS 456)
= 138 sqmm.
Minimum percentage of steel = 0.120 %
2
Area of steel required Ast req = (P/100)*B*d = 138.00 mm
Dia.of bar dm = 10 mm
2
Spacing Required (π*d /4)*B/Ast req = 569.20 mm
Provided spacing Sp = 200 mm
Percentage of steel provided = 0.34 %
2
Hence Area of Steel Provided Ast pro = 392.70 mm Hence Ok
Provide 10mm Dia bars 200mm C/C Along Bottom in X-X
AST CALCULATION ABOUT Y-Y DIRECTION@ BOTTOM (Main bars) :
Factored Bending moment about YY @ Bottom = 0.58 KN.m b= 1000
= kN-m mm
Effective depth Required dreq = √ (Muz/0.133*fck*b) = 13.23 < d
Effective depth Provided dpro = 115.00 mmconsider
2
Muz/bd = 0.04 singly
Percentage of Steel Required From SP-16, P = 0.011 %
( As per clause
Minimum percentage of steel = 0.0012*b*D 26.5.2.1 of IS 456)
= 138
Hence Ok
AST CALCULATION ABOUT X-X DIRECTION @ TOP :
consider
singly
2
Mux/bd = 0.04798 Reinforced
Percentage of Steel Required From SP-16, P = 0.012 %
( As per clause
Minimum area of steel = 0.0012*b*D 26.5.2.1 of IS 456)
= 230 sqmm.
Minimum percentage of steel = 0.200 %
2
Area of steel required Ast req = (P/100)*B*d = 230.00 mm
Dia.of bar dm = 10 mm
2
Spacing Required (π*d /4)*B/Ast req = 341.50 mm
Provided spacing Sp = 200 mm
Shear check
2
Shear stress from the STAAD Model = 0.039 N/mm
Factored shear force Vu = 7 kN
2
Nominal Shear stress ζv = 0.04 N/mm
WALL STRESSES:
X Y
MX+MXY MY+MXY
1.3 1.5 OUTER
1.8 1.1 INNER
SQX SQY
0.006 0.007 OUTER
0.009 0.006 INNER
M/S AMARA RAJA INFRA PVT LTD
DESIGN OF WALL
DATA
2
Grade of concrete fck = 25 N/mm
2
Grade of steel fy = 500 N/mm
Thickness of wall @ base level Dc = 350 mm
DESIGN OF WALL
Factored Bending moment about XX @ Bottom Mux = 2.72 kN.m b= 1000
Effective depth Required dreq = √ (Muz/0.133*fck*b) = 28.60 < d
Effective depth Provided dpro = 304.00 mm
Hence Depth Provided Ok
AST CALCULATION ABOUT X-X DIRECTION @ INNER :
consider
singly
2
Mux/bd = 0.03 Reinforced
Percentage of Steel Required From SP-16, P = 0.007 %
( As per clause
Minimum area of steel = 0.002*b*D 26.5.1.1 of IS 456)
= 608 sqmm.
Minimum percentage of steel = 0.200 %
2
Area of steel required Ast req = (P/100)*B*d = 608.00 mm
Dia.of bar dm = 8 mm
2
Spacing Required (π*d /4)*B/Ast req = 82.70 mm
Provided spacing Sp = 150 mm
= 608
Minimum percentage of steel = 0.200 %
2
Area of steel required Ast req = (P/100)*B*d = 608.00 mm
Dia.of bar dm = 12
2
Spacing Required (π*d /4)*B/Ast req = 186.10 mm
M/S AMARA RAJA INFRA PVT LTD
Hence Ok
AST CALCULATION ABOUT X-X DIRECTION @ OUTER :
consider
singly
2
Mux/bd = 0.02 Reinforced
Percentage of Steel Required From SP-16, P = 0.005 %
( As per clause
Minimum area of steel = 0.002*b*D 26.5.1.1 of IS 456)
= 608 sqmm.
Minimum percentage of steel = 0.200 %
2
Area of steel required Ast req = (P/100)*B*d = 608.00 mm
Dia.of bar dm = 8 mm
2
Spacing Required (π*d /4)*B/Ast req = 82.70 mm
Provided spacing Sp = 150 mm
Shear check
2
Factored Shear stress from the STAAD Model about ZZ = 0.007 N/mm
Factored shear force Vu = 3 kN
2
Nominal Shear stress ζv = 0.01 N/mm
Client: Serentica
Engineer:
STAAD SPACE IDT FOUNDATION
START JOB INFORMATION
ENGINEER DATE 06/11/2023
JOB NAME ANALYSIS
JOB CLIENT Serentica
JOB REV 01
CHECKER DATE 06/11/2023
APPROVED DATE 06/11/2023
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER KN
JOINT COORDINATES
88 1.69262 -1.22575 1.54275; 89 1.69262 -1.22575 1.34113;
90 1.69263 -1.22575 1.1415; 91 1.69262 -1.22575 0.941875;
92 1.69262 -1.22575 0.74225; 97 1.69262 -0.9505 1.54275;
98 1.69263 -0.9505 1.34113; 99 1.69262 -0.9505 1.1415;
100 1.69262 -0.9505 0.941875; 101 1.69263 -0.9505 0.74225;
106 1.69263 -0.67525 1.54275; 107 1.69262 -0.67525 1.34113;
108 1.69262 -0.67525 1.1415; 109 1.69263 -0.67525 0.941875;
110 1.69263 -0.67525 0.74225; 115 1.69262 -0.4 1.54275;
116 1.69262 -0.4 1.34113; 117 1.69263 -0.4 1.1415; 118 1.69262 -0.4 0.941875;
119 1.69262 -0.4 0.74225; 160 0.542376 -1.22575 0.74225;
161 0.542376 -1.22575 0.941875; 162 0.542376 -1.22575 1.1415;
163 0.542376 -1.22575 1.34113; 164 0.542376 -1.22575 1.54275;
169 0.542376 -0.9505 0.74225; 170 0.542376 -0.9505 0.941875;
171 0.542376 -0.9505 1.1415; 172 0.542376 -0.9505 1.34113;
173 0.542376 -0.9505 1.54275; 178 0.542376 -0.67525 0.74225;
179 0.542376 -0.67525 0.941875; 180 0.542376 -0.67525 1.1415;
181 0.542376 -0.67525 1.34113; 182 0.542376 -0.67525 1.54275;
187 0.542376 -0.4 0.74225; 188 0.542376 -0.4 0.941875;
189 0.542376 -0.4 1.1415; 190 0.542376 -0.4 1.34113; 191 0.542376 -0.4 1.54275;
245 2.01738 -1.5 1.71413; 247 2.01738 -1.5 0.570874; 254 0.217631 -1.5 1.71413;
256 0.217631 -1.5 0.571474; 335 1.36762 -1.5 1.71375; 336 1.368 -1.5 1.42813;
337 1.36762 -1.5 1.1425; 338 1.368 -1.5 0.856875; 339 1.36763 -1.5 0.57125;
354 1.11762 -1.5 1.71375; 355 1.11763 -1.5 1.42813; 356 1.11762 -1.5 1.1425;
357 1.11763 -1.5 0.856875; 358 1.11763 -1.5 0.57125; 367 0.867618 -1.5 1.71375;
368 0.867629 -1.5 1.42813; 369 0.867618 -1.5 1.1425;
370 0.867629 -1.5 0.856875; 371 0.867629 -1.5 0.57125;
387 0.217628 -1.5 1.42813; 388 0.217617 -1.5 1.1425;
389 0.218001 -1.5 0.856875; 465 2.01763 -1.5 1.42813; 466 2.01762 -1.5 1.1425;
467 2.01763 -1.5 0.856875; 527 1.69238 -1.5 1.71413; 528 1.69238 -1.5 0.570874;
530 1.69263 -1.5 1.42813; 531 1.69262 -1.5 1.1425; 532 1.69263 -1.5 0.856875;
534 0.542631 -1.5 1.71413; 535 0.542631 -1.5 0.571474;
537 0.542628 -1.5 1.42813; 538 0.542617 -1.5 1.1425;
539 0.543001 -1.5 0.856875; 541 0.542376 -1.5 1.54275;
E:\Viswanadh\Serentica - Sterlite\Nifps Foundation Details\NIFPS Foundation - Serentica\NIFPS - Foundation - Serentica.STD
Job Title: ANALYSIS
Client: Serentica
Engineer:
542 0.542376 -1.5 1.34113; 544 0.542376 -1.5 0.941875;
545 0.542376 -1.5 0.74225; 546 1.69262 -1.5 1.54275; 547 1.69263 -1.5 1.34113;
549 1.69263 -1.5 0.941875; 550 1.69263 -1.5 0.74225;
ELEMENT INCIDENCES SHELL
78 88 89 98 97; 79 89 90 99 98; 80 90 91 100 99; 81 91 92 101 100;
86 97 98 107 106; 87 98 99 108 107; 88 99 100 109 108; 89 100 101 110 109;
94 106 107 116 115; 95 107 108 117 116; 96 108 109 118 117; 97 109 110 119 118;
123 357 356 369 370; 124 356 355 368 369; 131 355 354 367 368;
132 358 357 370 371; 143 160 161 170 169; 144 161 162 171 170;
145 162 163 172 171; 146 163 164 173 172; 151 169 170 179 178;
152 170 171 180 179; 153 171 172 181 180; 154 172 173 182 181;
159 178 179 188 187; 160 179 180 189 188; 161 180 181 190 189;
162 181 182 191 190; 165 338 337 356 357; 172 337 336 355 356;
173 336 335 354 355; 180 339 338 357 358; 181 256 535 545; 182 256 545 539 389;
183 389 539 544; 184 389 544 538 388; 185 388 538 542; 186 388 542 537 387;
187 387 537 541; 188 387 541 534 254; 189 535 371 370 545; 190 545 370 539;
191 539 370 369 544; 192 544 369 538; 193 538 369 368 542; 194 542 368 537;
195 537 368 367 541; 196 541 367 534; 197 339 528 550; 198 339 550 532 338;
199 338 532 549; 200 338 549 531 337; 201 337 531 547 336; 202 336 547 530;
203 336 530 546 335; 204 335 546 527; 205 528 247 467 550; 206 550 467 532;
207 532 467 466 549; 208 549 466 465 531; 209 531 465 547; 210 547 465 530;
211 530 465 546; 212 546 465 245 527; 215 162 544 538; 216 163 162 538 542;
220 92 91 532 550; 221 91 90 549 532; 225 88 546 530; 226 89 547 531;
227 89 88 530 547; 228 549 90 531; 229 531 90 89; 230 537 541 164;
231 542 537 163; 232 163 537 164; 233 161 539 544 162; 234 160 545 539 161;
START GROUP DEFINITION
GEOMETRY
_WALLR.F 78 TO 81 86 TO 89 94 TO 97 143 TO 146 151 TO 154 159 TO 162 215 216 -
220 221 225 TO 234
JOINT
_SUPPORT 245 247 254 256 335 TO 339 354 TO 358 367 TO 371 387 TO 389 -
465 TO 467 527 528 530 TO 532 534 535 537 TO 539
ELEMENT
_RAFT 123 124 131 132 165 172 173 180 TO 212
END GROUP DEFINITION
ELEMENT PROPERTY
78 TO 81 86 TO 89 94 TO 97 143 TO 146 151 TO 154 159 TO 162 215 216 220 221 -
225 TO 234 THICKNESS 0.35
123 124 131 132 165 172 173 180 TO 212 THICKNESS 0.15
DEFINE MATERIAL START
ISOTROPIC CONCRETE
E 2.17185e+07
POISSON 0.17
DENSITY 23.5616
ALPHA 1e-05
E:\Viswanadh\Serentica - Sterlite\Nifps Foundation Details\NIFPS Foundation - Serentica\NIFPS - Foundation - Serentica.STD
Job Title: ANALYSIS
Client: Serentica
Engineer:
DAMP 0.05
TYPE CONCRETE
STRENGTH FCU 27579
END DEFINE MATERIAL
CONSTANTS
MATERIAL CONCRETE ALL
SUPPORTS
245 247 254 256 335 TO 339 354 TO 358 367 TO 371 387 TO 389 465 TO 467 527 -
528 530 TO 532 534 535 537 TO 539 ELASTIC MAT DIRECT Y SUBGRADE 6708 PRINT
LOAD 1 LOADTYPE Dead TITLE DEAD LOAD
SELFWEIGHT Y -1
ELEMENT LOAD
123 124 131 132 165 172 173 180 TO 212 PR GY -4.41
94 TO 97 TRAP Y -0.9 -0.45
86 TO 89 TRAP Y -1.35 -0.9
78 TO 81 TRAP Y -1.8 -1.35
220 221 225 TO 229 TRAP Y -2.25 -1.8
159 TO 162 TRAP Y -0.9 -0.45
151 TO 154 TRAP Y -1.35 -0.9
143 TO 146 TRAP Y -1.8 -1.35
215 216 230 TO 234 TRAP Y -2.25 -1.8
LOAD 2 LOADTYPE None TITLE LOAD CASE 1
JOINT LOAD
115 119 187 191 FY -1.1
187 FY 1
191 FY 1
119 FY -1
115 FY -1
115 119 187 191 FZ 0.5
LOAD 3 LOADTYPE None TITLE LOAD CASE 2
JOINT LOAD
115 119 187 191 FY -1.1
187 FY 0.9
191 FY 0.9
119 FY -0.9
115 FY -0.9
115 119 187 191 FZ 0.2
LOAD 4 LOADTYPE None TITLE LOAD CASE 3
JOINT LOAD
115 119 187 191 FY -1.1
187 FY 1.1
191 FY 1.1
119 FY -1.1
115 FY -1.1
115 119 187 191 FZ 0.4
E:\Viswanadh\Serentica - Sterlite\Nifps Foundation Details\NIFPS Foundation - Serentica\NIFPS - Foundation - Serentica.STD
Job Title: ANALYSIS
Client: Serentica
Engineer:
187 FY 0.7
191 FY -0.7
119 FY 0.7
115 FY -0.7
115 119 187 191 FX 0.1
LOAD 5 LOADTYPE None TITLE LOAD CASE 4
JOINT LOAD
115 119 187 191 FY -1.1
187 FY 0.3
191 FY 0.3
119 FY -0.3
115 FY -0.3
115 119 187 191 FZ 0.1
LOAD 6 LOADTYPE None TITLE LOAD CASE 5
JOINT LOAD
115 119 187 191 FY -1.1
187 FY 0.6
191 FY 0.6
119 FY -0.6
115 FY -0.6
115 119 187 191 FX 0.1
LOAD COMB 101 COMBINATION LOAD CASE 1
1 1.0 2 1.0
LOAD COMB 102 COMBINATION LOAD CASE 2
1 1.0 3 1.0
LOAD COMB 103 COMBINATION LOAD CASE 3
1 1.0 4 1.0
LOAD COMB 104 COMBINATION LOAD CASE 4
1 1.0 5 1.0
LOAD COMB 105 COMBINATION LOAD CASE 5
1 1.0 6 1.0
PERFORM ANALYSIS
FINISH
PAGE NO. 1
****************************************************
* *
* STAAD.Pro CONNECT Edition *
* Version 22.12.00.142 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= NOV 6, 2023 *
* Time= 16:21:16 *
* *
* Licensed to: Amara Raja Infra Pvt Ltd *
****************************************************
95. CONSTANTS
96. MATERIAL CONCRETE ALL
97. SUPPORTS
98. 245 247 254 256 335 TO 339 354 TO 358 367 TO 371 387 TO 389 465 TO 467 527 -
99. 528 530 TO 532 534 535 537 TO 539 ELASTIC MAT DIRECT Y SUBGRADE 6708 PRINT
**WARNING-CHECK INFLUENCE AREAS FOR ZERO OR LARGE AREAS.
245 0.023258
247 0.023258
254 0.026468
256 0.021369
335 0.000025
336 0.082131
337 0.082104
338 0.082131
339 0.000023
354 0.000001
355 0.071459
356 0.071407
357 0.071459
358 0.000000
367 0.000028
368 0.082117
369 0.082119
370 0.082064
371 0.000014
387 0.000002
388 0.045456
389 0.000108
465 0.052185
466 0.000003
467 0.046505
527 0.052873
528 0.050900
530 0.092837
531 0.092829
532 0.092836
534 0.047446
535 0.000068
537 0.092890
538 0.092829
539 0.092739
TOTAL 1.653944
100. LOAD 1 LOADTYPE DEAD TITLE DEAD LOAD
101. SELFWEIGHT Y -1
102. ELEMENT LOAD
103. 123 124 131 132 165 172 173 180 TO 212 PR GY -4.41
104. 94 TO 97 TRAP Y -0.9 -0.45
105. 86 TO 89 TRAP Y -1.35 -0.9
106. 78 TO 81 TRAP Y -1.8 -1.35
107. 220 221 225 TO 229 TRAP Y -2.25 -1.8
108. 159 TO 162 TRAP Y -0.9 -0.45
109. 151 TO 154 TRAP Y -1.35 -0.9
P R O B L E M S T A T I S T I C S
-----------------------------------
168. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://www.bentley.com/en/support/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) Bentley Systems, Inc. *
* http://www.bentley.com *
************************************************************
M M
L L
K K
R1
F
J J
R1
R1
I I
R1
R1
H
E E
REFERENCE DRAWINGS:
DRAWING NO. DRAWING TITLE
SG02KS-AIPL-PVP-CIV-DBR-035 INVERTER DUTY TRANSFORMER GA AND DATASHEET
SG02KS-AIPL-PVP-ELE-DTS-006 NIFPS - Inverter Duty Transformer - GTP, GA, Schematic Diagrams
D D
R1
R1 08-11-2023 FOR_APPROVAL NSK PKA APPD
R0 10-09-2023 FOR_APPROVAL NSK PKA APPD
REV. DATE DESCRIPTION BY MEC. ELE. CIV. C&I APPD.
STAMP:
R1
10Ø HOLD LUST
B
CLIENT : serentica SERENTICA RENEWABLES INDIA 3 PVT LTD B
INSERT PLATE (IP100X100X10) 290 MWp / 200 MW SOLAR PV PLANT AT GADAG
PROJECT :
KARNATAKA
OWNER'S
ENGINEER: L & T - SARGENT & LUNDY LTD.
EPC
CONTRACTOR: M/S. AMARA RAJA INFRA PVT LTD.
DATE NAME TITLE:
DRAWN 08-NOV-23 NSK
A CHECKED 08-NOV-23 PKA/RGK
OIL SUMP PIT DETAILS & NIFPS A
R1
R1 R1 APPROVED 08-NOV-23 RVR FOUNDATION DETAILS
DEPARTMENT CIV
A0 (1189mm x 841mm)
R1 SCALE : NTS