PERI Structural Analysis For Wall H=5.

10m
uctural Analysis
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

Double sided wall structural analysis

Project
Ministries Complex - Eastern Car Park

Wall Height: 5.10 m

Customer
Combined Group.

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
2|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

Table Of Contents:

I) GENERAL DATA ............................................................................................... 4


1. Consistency Range ............................................................................................... 4
2. Plywood General data:.......................................................................................... 5
3. GT24 General data: .............................................................................................. 6
4. Steel waler SRZ U100 General data: .................................................................... 7
5. Tie Rods General data: ......................................................................................... 7
II) Structural Analysis : ........................................................................................ 8
1. Concrete Volume and Rate of Rise:...................................................................... 8
2. Check on Plywood: ............................................................................................... 9
3. Check on GT24 Girders: ..................................................................................... 10
4. Check on Steel waler U100 Girders: ................................................................... 12
5. Check on Tie rod DW15:..................................................................................... 15
• Check on PUSH Pull Props: .......................................................................... 16

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
3|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

I) GENERAL DATA

1. Consistency Range

• A concrete consistency range of F3 was chosen (Soft concrete). Please refer


to the following table for more details, Please note that the table will change
when TE is changed.

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
4|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

2. Plywood General data:

Hereunder is a table for some plywood type’s specifications, in order to calculate the
deflection and behavior. PERI calculations will be based on σ = 12 N/mm2 as an average
quality plywood.

- The plywood supplied by the contractor criteria should match the criteria chosen. The
plywood quality may affect the sec. girders spacing.

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
5|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

3. GT24 General data:

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
6|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

4. Steel waler SRZ U100 General data:

5. Tie Rods General data:

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
7|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

II) Structural Analysis :

1. Concrete Volume and Rate of Rise:

• In the following chart, using the concrete pressure 50KN/m2 and the consistency
range F3, we can have the rate of rise for concrete inside the formwork.
• When te=7h the rate of rise =1.90m/h,so when te=8h the rate of rise=1.83 m/h.

50

1.90 m

All these values are based on the above DIN 18218 table with the following
assumptions:

- Bulk Density of plain concrete: 25KN/m3


- Final set of the concrete 7hrs
- Temperature of green concrete +15°C
- Compaction with internal vibrators
- Tight Formwork

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
8|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

2. Check on Plywood:

o Concrete pressure : 50 kN/m2

- Max Girder Spacing : 35 cm


- Approx. Deflection : 1.50 mm

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
9|P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

3. Check on GT24 Girders:

General Design Data:

a. Concrete Pressure = 50 KN/m2


b. Pouring Height = 5.10 m
c. Girder spacing = 35 cm
d. Max Tie Rods Influence = 1.25 m

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
10 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
11 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

4. Check on Steel waler U100 Girders:

a. Maximum Load on waler = 19.05/.350(Girder Spacing) KN/m2


= 54.40 KN/m2

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
12 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

Maximum Tie Rod Spacing Here is =1.411m


And the Load on Tie Rod is = 67.24 <90 kN so its safe.

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
13 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

60

- Max deflection on waler = 1.16.

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
14 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

5. Check on Tie rod DW15:

Tension force in tie rods = 59.1900 KN < 90 kN OK SAFE

F F

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
15 | P a g e
PERI Kuwait W.L.L. P.O. Box 23910, Safat 13100 Kuwait
Phone +965 222 500 52 - Fax +965 222 500 53.kw

• Check on PUSH Pull Props:

Project : Ministires Car Park Project no.: KUW15-100065 -033 Order no. :901
Design by : M.Suhel Saifi Date : 01/25/2016
16 | P a g e