Partial Load Factor = 1.5 1.5 1.5 1.5 Factored Load on column KN-m = 347 347 42 42 Unfactored Load on column KN-m = 232 232 28 28 Width of column A Bca = 650 mm Depth of column A Dca = 650 mm Width of column B Bcb = 650 mm Depth of column B Dcb = 650 mm 750 Approximate depth of footing below F.L d = 2000 mm Centre to Centre Spacing of columns s = 690 mm Centre of gravity of loads (from column A) x = 810 mm Za Ya Xa Xb Yb Zb Provide Projection on left side of column a = 2155 mm 5000 Minimum Length of footing required Lmin. = 5930 mm d/2 d/2 Projection on right side of column b = 2155 mm d d Total length of footing L = 5000 mm A e B Width of footing B = 1800 mm 650 650 Weight of footing & soil above Footing w1 = 360.00 KN 1800 W = 823.0 KN 650 650 Total Vertical load (including weight of footing) Bearing capacity of soil Q = 150 KN/m2 2155 690 2155 Area of footing required Areq. = 5.5 m2 Area of footing provided A = 9.00 m2 Za Ya Xa Xb Yb Zb Eccentricity of loads from CG of footing = -465.00 mm Total Moment M = 215.31 KN-m P/A+M/Z = 120.16 KN/m2 P/A-M/Z = 62.74 KN/m2 Unfactored upward pressure intensity p = 120.16 KN/m2 699.14 Factored upward pressure intensity pu = 180.24 KN/m2 -351.86 Grade of Concrete M = 30 N/mm2 a b c d e Grade of steel Fe = 500 N/mm2 Dia of longitudinal bar = 16 mm 351.86 -699.14 Dia of transverse bar = 16 mm #DIV/0! Clear cover = 50 mm SF DIAGRAM
Bending moment along longitudinal direction of footing
Upward pressure intensity along long. dir. pl = 324.4 KN/m Bending moment at point c Mc = 1013.8 KN.m Bending moment at face of col. A (i.e At b) Mb = 543.2 KN.m Bending moment at face of col. B (i.e At d) Md = 543.2 KN.m Depth of footing required dreq. = 368.8 mm
Bending moment along Transverse direction of footing
Upward pressure intensity along long. dir. pl = 901.2 KN/m Bending moment at face of col. A or B (having Mb = 149.0 KN/m greater projections) Depth of footing required dreq. = 84.8 mm
Hence Provide depth of footing as D = 750 mm
Effective depth of footing d = 692 mm
Area of Steel Provided
Along Longitudinal direction :- Mu/bd2 at point c = 1.18 N/mm2 % of steel required at c = 0.284 Area of steel required at point c = 3535 mm2 Mu/bd2 under column A = 0.63 N/mm2 % of steel required under column A = 0.205 Area of steel required Under Column A = 2553 mm2 Mu/bd2 under column B = 0.63 N/mm2 % of steel required under column B = 0.205 Area of steel required Under Column B = 2553 mm2 No. of Layers = 1 Provide 16 mm dia bar @ 100 mm c/c spapcing Area of steel provided Ast = 3619 mm2
Along Transverse direction :-
Mu/bd2 at point c = 0.06 N/mm2 % of steel required at c = 0.205 Area of steel required Under Column A or B = 7093 mm2 No. of Layers = 1 Provide 16 mm dia bar @ 140 mm c/c spapcing Area of steel provided Ast = 8083 mm2
Check for One way shear
Under Column A Max. Shear Force (at section Za-Za) V = 369.20 KN (As per clause 34.2.4.1(a) of IS:456-2000) Shear stress tv = 0.30 N/mm2 (As per clause 40.1 of IS:456-2000) 100 x Ast/(B x d) = 0.29 tc = 0.39 N/mm2 (Table-19 of IS:456-2000) Under Column B Max. Shear Force (at section Zb-Zb) V = 369.20 KN (As per clause 34.2.4.1(a) of IS:456-2000) Shear stress tv = 0.30 N/mm2 (As per clause 40.1 of IS:456-2000) 100 x Ast/(B x d) = 0.29 tc = 0.39 N/mm2 (Table-19 of IS:456-2000) SAFE IN ONE WAY SHEAR Check for Two way shear Under Column A Max. Shear Force (at section Ya-Ya) V = 22.68 KN (As per clause 34.2.4.1(b) of IS:456-2000) Max. Shear stress tv = 0.01 N/mm2 ks = 1.00 (As per clause 31.6.3.1 of IS:456-2000) tc = 1.37 kstc = 1.37 N/mm2 Under Column B Max. Shear Force (at section Yb-Yb) V = 22.68 KN (As per clause 34.2.4.1(b) of IS:456-2000) Max. Shear stress tv = 0.01 N/mm2 ks = 1.00 (As per clause 31.6.3.1 of IS:456-2000) tc = 1.37 kstc = 1.37 N/mm2 SAFE IN TWO WAY SHEAR