Professional Documents
Culture Documents
Procedure
1. Following the basic OPERATING PROCEDURE smear the faces of
the heated and cooled sections with thermal conducting paste and
clamp them together without any intermediate section in place.
2. Again following the above procedure ensure the cooling water is
flowing and then set the heater voltage V to 90 volts.
3. Monitor temperatures T1, T2, T3, T6, T7, T8 until stable.
Continuous homogenous sample 4. When the temperatures are stabilised record: T1, T2, T3, T6, T7, T8,
V and I.
5. Reset the heater voltage to 120 volts and repeat the above procedure
again recording the parameters T1, T2, T3, T6, T7, T8, V and I when
temperatures have stabilised.
6. Reset the heater voltage to 170 volts and repeat the above procedure
again recording the parameters T1, T2, T3, T6, T7, T8, V and I when
temperatures have stabilised.
7. Reset the heater voltage to 200 volts and repeat the above procedure
again recording the parameters T1, T2, T3, T6, T7, T8, V and I when
temperatures have stabilised.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To measure the temperature distribution for steady state conduction
of heat energy through the wall of a thick cylinder (Radial energy
flow) and demonstrate the effect of a change in heat flow.
• To understand the use of the Fourier Rate Equation in determining
rate of heat flow for steady state conduction of heat energy through
the wall of a thick cylinder (Radial energy flow) and using the
equation to determine the constant of proportionality (the thermal
conductivity k) of the disc material.
• To observe unsteady state conduction of heat and to use this in
observation of the time to reach stable conditions.
Procedure
1. Follow the basic OPERATING PROCEDURE
2. Again following the above procedure ensure the cooling water is
flowing and then set the heater voltage V to approximately 100
volts. If however the local cooling water supply is at a high
temperature (25-35℃ or more) then it may be necessary to increase
Fourier’s law on cylinder the voltage supplied to the heater.
3. This will increase the temperature difference between the hot
centre and cool circumference of the disc.
4. Monitor temperatures T1, T2, T3, T4, T5, T6 until stable.
5. When the temperatures are stabilised record:
T1, T2, T3, T4, T5, T6, V, I.
6. Increase the heater voltage by approximately 50 volts and repeat
the above procedure again recording the parameters T1, T2, T3, T4,
T5, T6, V, I when temperatures have stabilised.
Temperature distribution across cylinder 7. Increase the heater voltage by approximately 50 volts and again
repeat the above procedure recording the parameters
T1, T2, T3, T4, T5, T6, V, I
when temperatures have stabilised.
8. If time is available, the procedure may be repeated further noting
that the maximum safe temperature for T1 is 100℃
9. When completed, if no further experiments are to be conducted
reduce the heater voltage to zero.
10. shut down the system as detailed in the operation section
11. Heat transfer rate from the heater
Q = V×I
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To show that the intensity of radiation on a surface is
inversely proportional to the square of the distance of the
surface from the source of radiation (To demonstrate the
inverse square law for thermal radiation)
• To show that the intensity of radiation varies as the fourth
power of the source temperature (To demonstrate the
Stefan-Boltzmann Law.)
• To show that the intensity of radiation measured by the
6. Schematically this produces a system as
radiometer is directly related to the radiation emitted from
shown below.
a source by the view factor between the radiometer and the
source.
• To determine the emissivity of radiating surfaces with
different finishes, namely polished and grey (silver
anodised) compared with matt black.
• To demonstrate how the emissivity of radiating surfaces in
close proximity to each other will affect the surface
7. Ensure that the radiation shield is in position
temperatures and heat exchanged.
in the radiometer aperture and station the
• To show that the illuminance of a surface is inversely
radiometer in the 900mm position.
proportional to the square of the distance of the surface
8. The radiometer should be left for several
from the light source.
minutes after handling with the radiation
shield in position to ensure that residual Technical Data T2 Black Plate
heating has dissipated. Stefan-Boltzmann Constant T3 Grey Plate
9. Follow the Operating procedure, but do not σ = 5.67 x 10-8 W/m2 K4 T4 Polished Plate
Temperature locations T5 Heated Plate
increase the supply voltage to the heater
T1 Black Plate
from the zero condition.
10. Monitor the W/m2 digital display and after
Procedure
several minutes, the display should reach a
1. Following the basic OPERATING PROCEDURE and
minimum.
INSTALLATION PROCEDURE
11. Finally, ‘Auto-Zero’ the radiometer by
2. Install the heated plate C1(10) at the left hand side of the
pressing the right hand Å button twice.
track and install the radiometer C1(12) on the right hand
12. Leave the radiation shield in position and
carriage C1(2).
rotate the voltage controller clockwise to
3. No items are installed in the left hand carriage for this
increase the voltage to maximum volts.
experiment but one of the black plates should be placed
13. Select the T5 position on the temperature
on the bench and connected to thermocouple socket T4.
selector switch and monitor the T5
temperature.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Procedure
1. Following the basic OPERATING PROCEDURE ensure that the
heated cylinder is located in its holder at the top of the duct and that
Heat lost due to natural convection the cylinder is rotated so that the thermocouple location is on the
side of the cylinder. This is shown schematically below.
Radiant component
Procedure
1. Following the basic OPERATING PROCEDURE and
INSTALLATION PROCEDURE connect the Radiation Errors
in Temperature Measurement H112F to the Heat Transfer
Service Unit H112.
2. Ensure that the radiation shield is not fitted.
3. Follow the Operating procedure, but do not increase the supply
voltage to the heater from the zero condition.
4. Set the temperature selector switch to display temperatures T1,
T2, T3, T4 and T5 and record the values. Open the throttle
butterfly but do not turn on the centrifugal fan at this point.
6. Repeat the above procedure at heater voltages of
Rotate the voltage controller clockwise to increase the heater
180 and 230 volts
voltage to 80 Volts. Select the T5 position on the temperature
7. Completely close the throttle butterfly on the fan
selector switch and monitor the T5 temperature.
intake and then turn on the centrifugal fan.
5. Also monitor temperatures T2 to T4 until these reach a stable
8. Adjust the throttle until a velocity of
temperature. When the temperatures are stable record T1, T2,
approximately 0.5m/s is indicated.
T3, T4, T5, V and I. Rotate the voltage controller clockwise to
9. Observe the temperatures T1 to T5 and when
increase the voltage to 120 Volts. Again allow the
stable record T1, T2, T3, T4, T5, V and I.
temperatures to stabilise and then record T1, T2, T3, T4, T5, V
and I.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To Using analytical transient-temperature/heat flow charts to
determine the thermal conductivity of a solid cylinder from
measurements taken on a similar cylinder but having a different
thermal conductivity.
• To Investigation of the effect of shape, size and material properties on
unsteady heat flow. Using analytical transient-temperature heat flow
charts to analyse the results obtained from different solid shapes.
• Investigation of the Lumped Thermal Capacitance method of
transient temperature analysis.
Procedure
1. Install the Unsteady State Heat Transfer Unit H112G as detailed in
INSTALLATION UNSTEADY STATE HEAT TRANSFER UNIT
H112G WITH HEAT TRANSFER SERVICE MODULE
2. Follow the OPERATING PROCEDURE onwards in order to
establish the following operating conditions:-
3. Install the 30mm diameter brass cylinder in the shape carrier G1(6).
4. The water bath temperature T1 should be stabilised at approximately
80 to 90 ℃.
5. Set the circulating pump to speed 3 and therefore the water flow
velocity in the flow duct.
6. Record the starting condition temperatures and then plunge the shape
in the flow duct.
7. Then record temperatures and time as detailed in section of the
Operating Procedure.
8. Typical observations are shown.
9. If time permits the procedure may be repeated for the other shapes
supplied.
T3 vs Time graph
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• Determination of the incidental heat transfer.
• Determination of the thermal conductivity of a liquid or a gas.
Technical Data
Nominal Radial Clearance between Effective Area A of Conducting
Plug and Jacket: 0.30mm Path through Fluid : 0.0133m2
1. Power Plug
2. Thermocouple t1
3. Thermocouple t2
4. Logger Thermocouple t1
5. Logger thermocouple t2
6. Cooling water in/out
7. Coolling water in/out
8. Test fluid inlet
Electrical Input
Objectives
• Collecting Data For Any Configuration, Using The Optional Data
Acquisition System
• Reviewing Recorded Data Using the Data Logging Software
• Investigation of the First law of Thermodynamics by Determination
of the Heat Capacity Ratio γ for air.
• Investigation of the Perfect Gas Law through an Isothermal Process.
• Investigation of the Perfect Gas Law through the Change in
Temperature of a Fixed Volume.
Objectives
• Investigation of the pressure-temperature relationship for
Water/steam.
• Investigation of the Clausius- Clapeyron equation using the Pressure-
temperature relationship for steam.
• Investigation of steam quality by throttling.
Procedure
1. Refer to the operating procedure. Ensure in particular that the boiler
contains sufficient water.
2. Record the local ambient atmospheric pressure using a locally
supplied barometer or equivalent. Record the starting condition
Temperature T1 and Pressure.
3. If the pressure is to be recorded from a sub-atmospheric pressure
then refer to the “Second Time Use When the Boiler is In Vacuum”
procedure.
4. Increase the heater to full power and monitor the increasing
temperature and pressure. At relevant intervals record both the
pressure and temperature.
5. It is recommended that either whole units of pressure or whole units
of temperature are selected as the recording points as this makes
reference to steam tables easier.
Pressure
1. The gauge pressure indicated by the bourdon tube pressure gauge is
“relative” to atmospheric pressure.
2. Atmospheric pressure varies depending upon weather conditions and
location(sea level or high altitude) and therefore it would be
impractical to present the pressure-temperature relationship for water
in terms of gauge pressure as the readings would vary.
3. Therefore it is normal to refer pressures to an absolute vacuum. This
can be achieved either by using a pressure gauge that is internally
evacuated and sealed or by adding the local atmospheric pressure to
1. Boiler the pressure measured by a standard pressure gauge.
2. Sight Glass
3. Pressure Gauge
4. Throttle Valve
5. Pressure Switch
6. Safety Valve
7. Water fill / Drain
8. Throttle Valve Vent Coupling
9. Safety Valve Vent Coupling
10. Pressure Transducer (*Only fitted if
HC112MA is Purchased).
Pressure Switch
The pressure switch is factory set to
operate at or below 900kN/m2
gauge pressure. This turns off the
heater inside the boiler.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
H112P - Free and forced convection from flat, finned and pinned plates
Objectives
• To Demonstrate the Relationship Between Power Input and Surface
Temperature in Free Convection
• To Demonstrate the Relationship Between Power Input and Surface
Temperature in Forced Convection.
• To Demonstrate the use of Extended Surfaces to Improve Heat
Transfer From the Surface.
• To Determine the Temperature Distribution Along an Extended
Surface.
Procedure
1. Ensure the instrument console main switch is sin the off position.
Ensure the fan is switched off.
2. For the natural convection experiments the fan will not be used.
3. If the flat (pinned or finned) plate is not in position, open the toggle
1. Main Switch clamps. Replace with the flat(pinned or finned) plate and close the
2. Instrument Fuse toggle clamps. Note that with the plate heat exchangers the power
3. Fan Switch leads exit from the top of the plates. Refer to the diagram.
4. Air Velocity Display (m/s) 4. No air velocity will be measurable under natural convection
5. Air Velocity Sensor(Hot Wire conditions unless specialized instrumentation is available.
Anemometer) 5. Switch on the main switch and set the heater voltage to minimum.
6. Duct 6. The objective with the steady state method is to obtain the same T1
7. T5 Air Temperature surface temperature on each of the heat exchangers and determine
8. Heated Plate the steady state power input required to achieve this. From factory
9. Air Throttle tests under “typical” conditions the following heat inputs were
required to maintain T1.
Steady State Method 7. When the temperature T1 has stabilised(this may take 10’s of
If time permits, or for a student project minutes) record the actual temperature T1, the actual voltage V and
the steady state experimental procedure the ambient air temperature T9. If either the Finned or Pinned plates
may be adopted. This allows the heat are in position the pin temperatures (T2,T3,T4) or fin temperatures
transfer rate from the three heat (T2, T3, T4) may be recorded.
exchangers to be compared at similar hot 8. Before removing the heat exchanger from the duct turn on the fan
plate temperatures. Due to the and cool the heat exchanger .
requirement for small adjustments and 9. Note that this cooling procedure may be used to quickly demonstrate
the time taken to assess stability the to students the increased heat transfer coefficient due to forced
experimental period can be long. convection if the voltage setting is left at the natural convection
Transient Method condition and the fan turned on to give maximum flow.
However for a rapid demonstration the 10. T1 will be seen to rapidly fall from the natural convection condition.
transient method may be adopted where a 11. Finally reduce the heater voltage to zero and allow to cool before
fixed heat input is applied. removing the plate from the tunnel and replacing with one of the
With this method the slope of the alternative plates.
temperature rise is an indication of the 12. Test results from the steady state method are obtained.
rate of heat transfer from the plate.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• Investigation of the effects upon the surface temperature of either face
of the module with increasing power. (Peltier Effect)
• Investigation of the effect upon heat transfer direction of reversing the
polarity of the power supply to the module. (Thomson or Lenz
Effect).
• Investigation of the variation in open circuit voltage across the
module due to the variation in surface temperature difference.
(Seebeck Effect).
• Investigation of the power generating performance of the module with
a steady load and increasing temperature difference.
• Estimation of the coefficient of performance of the module when
acting as a refrigerator.
Objectives
• Demonstration of a direct conversion of heat energy into shaft power
using a Stirling Cycle.
• Investigation of the Stirling cycle performance under load.
• Investigation of the parameters affecting the cycle performance and
cycle efficiency.
Technical data
Radius of Belt Brake Wheel r = 20mm
Procedure
1. The following experiment demonstrates the way in which direct
heating of the air charge in the Stirling engine results in a mechanical
power output.
2. Turn on the main switch of the H112 Heat Transfer Service unit and
turn the H112 Heater power control to zero.
3. Ensure cooling water is flowing through the water cooling
connections.
4. Turn the heater power control on the H112 Transfer Service unit
slowly clockwise until a current of approximately 0.500 amps is
shown on the H112 Ammeter.
5. Monitor the temperature of the heater TH on the heater temperature
display as this approaches 350°C increase or reduce the power input
1. Stirling cycle engine to maintain the TH temperature in the 350-380°C range.
2. Load cell display 6. Now ensure that the load adjuster is set so that the belt brake is
3. Tachometer indicator loose. Rotate the flywheel in a clockwise direction, as before and the
4. Heater temperature display pressure of the air acting on the power piston should be felt assisting
5. H112R heater power connection in rotation of the flywheel as the piston moves outwards along the
6. Heater terminal enclosure power cylinder. This is the effect of the expanding-heated air moved
7. heater cylinder by the displacer.
8. Cooling water inlet 7. If the flywheel is spun in a clockwise direction the engine should
9. Flywheel turn slowly and reach a stable speed.
10. Belt brake 8. Now slightly increase the heater power so that the heater temperature
11. Power cylinder TH increases slightly and observe the rotational speed of the engine.
12. Load Adjuster This should slowly increase with TH.
13. Crankshaft 9. Though the belt brake is not being used to load the engine it can be
15. Cooling water drain seen that the heat put into the system by the electric heater is being
16. cold side thermocouple converted to mechanical energy in order to maintain rotation of the
17. tachometer sensor (hidden) flywheel.
10. In this condition the engine is only generating power to overcome its
The Torque Φ developed by the engine own internal friction.
can be calculated 11. Note that the heater has a maximum temperature limit of 600°C and
when the heater temperature display
12. reaches 600°C there will be an audible click from the display . At
that point the current displayed on the digital current meter will drop
The shaft power W can be calculated to 0000 as the power is disconnected. The power is re-connected
from automatically as the temperature falls to below 599°C.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• Visual demonstration of convective, nucleate and film boiling.
• Determination of heat flux and surface heat transfer coefficient up to
and beyond the critical
• condition at constant pressure.
• Investigation of the effect of pressure on critical heat flux.
• Demonstration of filmwise condensation and measurement of overall
heat transfer coefficient.
• Demonstration of the cause of liquid carry over or priming in boilers.
• Determination of the pressure temperature relationship of a pure
substance.
• Investigation of the effect of air in a condenser.
• Demonstration of the law of partial pressures.
Procedure
1. Observe the normal operating procedure before starting this
procedure.
2. Turn on the electrical and water supplies and adjust both to very low
settings (<20 Watts). Allow the digital t1 temperature indicator to
stabilise. Observe this and the liquid temperature t2 at frequent
intervals.
3. It is assumed that the chamber is air free at this point(observed
pressure on the pressure gauge = Saturation pressure at t2).
4. Carefully watch the liquid surrounding the heated cylinder.
Convection currents will be observed, and at the same time liquid
will be seen to collect and drip on the condenser coils, indicating that
evaporation is proceeding although at a low rate. Increase the heat
1. Chamber
input in increments by adjusting the heater control , keeping the
2. Water cooled condenser
vapour pressure at any desired constant value by adjusting the
3. Heated cylinder
condenser water flow rate by the water flow control and meter.
4. Water flow control and meter
5. Nucleate boiling will soon start and will increase until vigorous
5. Chamber pressure gauge
boiling is seen, the temperature difference (t1-t2) between the liquid
6. Charging/drain valve
and metal being still quite moderate (<20K).
7. Air vent valve
6. Increase the heat input, and at between 300 and 400 Watts the nature
8. Wattmeter
of the boiling will be seen to change dramatically and at the same
9. Heater control
time the metal-liquid temperature difference will rise quickly.
10. Main switch
11. t 1 temperature indicator
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• Demonstrating indirect heating or cooling by transfer of heat from
one fluid stream to another when separated by solid wall.
• Performing an energy balance across a concentric tube heat
exchanger and calculating the overall efficiency at different fluid
flow rates.
• Demonstrating the differences between counter-current flow and
co-current flows
• Investigating the effect of changes in hot fluid and cold fluid flow
rate on the temperature efficiencies and overall heat transfer
coefficient.
Technical Data
• Inner tube material: stainless steel
• Outside diameter: 0.012m
• Wall thickness: 0.001m
• Outer tube material: Clear acrylic
Thermocouple Stations Co-current and • Inside diameter: 0.022m
Counter current flow: • Wall thickness: 0.003m
Thermocouples sense the stream • Active heat transfer section length: 2X0.3180m
temperatures at the four fixed stations: - • Active heat transfer section area: 0.02198m2
T1 – Hot Water INLET to Heat Exchanger
T2 – Hot Water RETURN from Heat Procedure
Exchanger 1. Install concentric tube heat exchanger H102A as detailed in
T3 – Cooling Water INLET to Heat installation guide.
Exchanger 2. Connect the cold water circuit to give counter current flow
T4 – Cooling Water RETURN from Heat according to installation guide.
Exchanger 3. Follow operational procedure to establish the operational
conditions.
4. Turn on main and heat switch.
5. Set hot temperature controller to 60℃.
6. Set cold water flow rate to 15 g/sec.
7. Set hot water flow rate to 50g/sec.
8. Monitor the steam temperatures and the hot and cold flow rates to
ensure these too remain close to the original setting.
9. Record T1, T2, T3, T4, T5, T6, V(cold), V(hot).
10. Adjust cooling water flow control so cold water flow is
approximately 30g/sec.
11. Maintain hot water flow rate at approximately 50g/sec.
12. Allow conditions to stabilize and repeat the above stated procedure
to ensure correct results.
1. Thermocouple sockets 9. Hot water in/out 13. Procedure can be repeated with different hot and cold water flow
2. Main switch 10. cold water in/out rates and different hot water inlet temperature if required.
3. Heater switch 11. Fill and sight tube Calculations:
4. RCCB 12. Vent 13. Tank drain valve Example of calculation is as under
5. Water temperature control Reduction in hot temperature fluid: T1-T2 = 59.3-53 = 6.2K
6. Temperature indicator Reduction in cold temperature fluid: T4-T3 = 30.9-15.4
7. Cooling water flow meter = 15.5K
8. Hot water flow meter
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• Demonstration of indirect heating or cooling by transfer of heat
from one fluid stream to another when separated by a solid Wall
(fluid to fluid heat transfer)
• Performing an energy balance across a plate heat exchanger and
calculating the overall efficiency at different fluid flow rates
• Demonstrating the differences between counter-current flow (flows
in opposing directions) and co-current flows (flows in the same
direction) and the effect on heat transferred, temperature
efficiencies and temperature profiles
• Determining the overall heat transfer coefficient for a plate heat
exchanger using the logarithmic mean temperature difference to
perform the calculations (for counter-current and co-current flows).
• Investigating the effect of changes in hot fluid and cold fluid flow
rate on the temperature efficiencies
Technical Data
• Plate Material: 316 Stainless • Number of plates: 4
steel • Number of channels on hot side:
• Plate overall dimensions: 2
0.072m x 0.189m • Cold side: 1
• Total heat transfer area: • Weight – Full 0.846kg
0.024m2 • Weight – empty 0.776kg
Procedure
1. Install the Plate Heat Exchanger H102B as detailed in
INSTALLATION / Heat Exchanger Installation guide and connect
the cold water circuit to give Counter-Current flow as detailed in
the guide.
2. Follow the operational procedure detailed in the main manual in
order to establish the operating conditions.
3. Turn on the ‘MAIN SWITCH’ and ‘HEATER SWITCH’
4. Set the hot water temperature controller to 60 ̊C.
5. Set the cold water flow rate Vcold to 15g/sec
6. Set the hot water flow rate Vhot to 35g/sec.
7. Allow the conditions to stabilise and record the observations.
1. Thermocouple sockets 12. Vent
2. Main switch 13. Tank drain valve Calculations
3. Heater switch For the example result, the calculations are as follows.
4. RCCB Reduction in Hot fluid temperature Δt hot = T1 - T2
5. Water temperature control = 51.8 - 41.5
6. Temperature indicator = 10.3 K
7. Cooling water flow meter Increase in Cold fluid temperature Δt cold = T4 – T3
8. Hot water flow meter =37.4 - 15.0
9. Hot water in/out = 22.4 K
10. Cold water in/out The test results show the effect upon the temperature differences when
11. Fill and sight tube the flow rates through a simple heat exchanger are varied.
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To demonstrate indirect heating or cooling by transfer of heat from
one fluid stream to another when separated by a solid wall (fluid to
fluid heat transfer).
• To perform an energy balance across a shell and tube exchanger
and calculate the overall efficiency at different fluid flow rates.
• To investigate the effect of changes in hot fluid and cold fluid flow
rate on the temperature efficiencies and overall heat transfer
coefficient.
• To investigate the effect of driving force (difference between hot
stream and cold stream temperature) with counter-current and co-
current flow.
• To determine the overall heat transfer coefficient for a shell and
tube heat exchanger using the logarithmic mean temperature
difference to perform the calculations (for counter-current and co-
current flows).
Objectives
• To demonstrate indirect heating or cooling by transfer of heat from
one fluid stream to another when separated by a solid wall (fluid to
fluid heat transfer).
• To investigate the heating characteristics of a stirred vessel
containing a fixed batch of liquid when heated using hot fluid
circulating through a submerged coil.
• To investigate the heating characteristics of a stirred vessel
containing a fixed batch of liquid when heated using hot fluid
circulating through an outer jacket.
• To investigate the change in overall heat transfer coefficient and
logarithmic mean temperature difference as a batch of fluid in the
vessel changes temperature.
• To perform an energy balance, calculate the overall efficiency and
determine the overall heat transfer coefficient for a continuous flow
in a stirred vessel when heated using a submerged coil.
Procedure
1. Install the Jacketed Vessel with Coil and Stirrer H102D as detailed
in installation guide and connect the hot water circuit Using the
Outer Jacket as detailed in the same guide.
2. Adjust the overflow in the vessel to the 1-litre height.
3. Configure the Cold Water Circuit following.
4. Follow the OPERATING PROCEDURE detailed in the main
manual in order to establish the operating conditions.
5. Turn on the ‘MAIN SWITCH’ and replenish the hot circuit as the
jacket fills.
6. Turn on the ‘HEATER SWITCH’.
7. Set the hot water temperature controller to 70 ̊C.
1. Thermocouple sockets 12. Vent 8. Set the cold water flow rate Vcold to 8g/sec
2. Main switch 13. Tank drain valve 9. Set the hot water flow rate V hot to 34g/sec.
3. Heater switch 10. Turn stirrer ON, speed to 100%.
4. RCCB 11. Make T5 probe 15mm below surface.
5. Water temperature control CALCULATIONS
6. Temperature indicator For the example result the calculations are as follows.
7. Cooling water flow meter Reduction in Hot fluid temperature Δt hot = T1 – T2 = 70.2 – 64.2
8. Hot water flow meter = 6.0 K
9. Hot water in/out Increase in Cold fluid temperature Δt cold = T5 – T4
10. Cold water in/out =32.5 – 14.1
11. Fill and sight tube = 18.4 K
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Procedure
1. Install the Concentric tube Heat Exchanger as detailed in
INSTALLATION / Heat Exchanger Installation guide and connect
the cold water circuit to give Counter- Current flow as detailed in
the same section.
2. Follow the OPERATING PROCEDURE detailed in the main
manual in order to establish the operating conditions.
3. Turn on the ‘MAIN SWITCH’ and ‘HEATER SWITCH’
4. Set the hot water temperature controller to 60 ̊C.
5. Set the cold water flow rate Vcold to 10g/sec
6. Set the hot water flow rate V hot to 30 g/sec.
7. Monitor the stream temperatures and the hot and cold flow rates to
1. Thermocouple sockets 12. Vent ensure these too remain close to the original setting. Then record
2. Main switch 13. Tank drain valve the following: T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, Vcold and V
3. Heater switch hot
4. RCCB 8. Then adjust the ‘COOLING WATER FLOW CONTROL’ so that
5. Water temperature control Vcold is approximately 10g/sec.
6. Temperature indicator 9. Maintain the Hot water flow rate V hot at approximately 30g/sec.
7. Cooling water flow meter 10. Allow the conditions to stabilise and repeat the above
8. Hot water flow meter observations.
9. Hot water in/out 11. The procedure may be repeated with different hot and cold flow
10. Cold water in/out rates and different hot water inlet temperature if required.
11. Fill and sight tube
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To demonstrate indirect heating or cooling by transfer of heat from
one fluid stream to another when separated by a solid wall (fluid to
fluid heat transfer).
• To perform an energy balance across a plate heat exchanger and
calculate the overall efficiency at different fluid flow rates
• To demonstrate the differences between counter-current flow (flows
in opposing directions) and co-current flows and the effect on heat
transferred, temperature efficiencies and temperature profiles
through a plate heat exchanger.
• To determine the overall heat transfer coefficient for a plate heat
exchanger using the logarithmic mean temperature difference to
perform the calculations.
• To investigate the effect of changes in hot fluid and cold fluid flow
rate on the temperature efficiencies and overall heat transfer
coefficient.
Procedure
1. Install the Plate Heat Exchanger as detailed in INSTALLATION /
Heat Exchanger Installation guide and connect the cold water
circuit to give Co-Current flow as detailed in the same section.
2. Follow the OPERATING PROCEDURE detailed in the main
manual in order to establish the operating conditions.
3. Turn on the ‘MAIN SWITCH’ and ‘HEATER SWITCH’
4. Set the hot water temperature controller to 60 ̊C.
5. Set the cold water flow rate Vcold to 10g/sec
6. Set the hot water flow rate V hot to 30g/sec.
7. Allow the conditions to stabilise and record the observations.
8. The procedure may be repeated with different hot and cold flow
1. Thermocouple sockets 12. Vent rates and different hot water inlet temperature if required.
2. Main switch 13. Tank drain valve CALCULATIONS
3. Heater switch For the example result the calculations are as follows.
4. RCCB Reduction in Hot fluid temperature Δt hot = T1 - T2
5. Water temperature control = 60.1 – 48.5 = 11.6 K
6. Temperature indicator Increase in Cold fluid temperature Δt cold = T4 – T3
7. Cooling water flow meter =47.9 – 16.6 = 32.3 K
8. Hot water flow meter The test results show the effect upon the temperature differences when
9. Hot water in/out the flow rates through a simple heat exchanger are varied.
10. Cold water in/out
11. Fill and sight tube
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
Objectives
• To demonstrate indirect heating or cooling by transfer of heat from
one fluid stream to another when separated by a solid wall (fluid to
fluid heat transfer).
• To perform an energy balance across a concentric tube heat
exchanger and calculate the overall efficiency at different fluid
flow rates.
• To demonstrate the differences between counter-current flow (flows
in opposing directions) and co-current flows (flows in the same
direction) and the effect on heat transferred, temperature
efficiencies and temperature profiles through a concentric tube heat
exchanger.
• To determine the overall heat transfer coefficient for a concentric
tube heat exchanger using the logarithmic mean temperature
difference to perform the calculations.
• To investigate the effect of changes in hot fluid and cold fluid flow
rate on the temperature efficiencies and overall heat transfer
coefficient.
• To investigate the effect of driving force (difference between hot
stream and cold stream temperature) with counter-current and co-
current flow.
Procedure
1. Install the Coiled Concentric tube Heat Exchanger as detailed in
INSTALLATION / Heat Exchanger Installation guide and connect
the cold water circuit to give Counter-Current flow as detailed in
the same section.
2. Follow the OPERATING PROCEDURE detailed in the main
manual in order to establish the operating conditions.
3. Turn on the ‘MAIN SWITCH’ and ‘HEATER SWITCH’
1. Thermocouple sockets 12. Vent 4. Set the hot water temperature controller to 60 ̊C.
2. Main switch 13. Tank drain valve 5. Set the cold water flow rate Vcold to 10g/sec
3. Heater switch 6. Set the hot water flow rate V hot to 30g/sec.
4. RCCB 7. Monitor the stream temperatures and the hot and cold flow rates to
5. Water temperature control ensure these too remain close to the original setting. Then record
6. Temperature indicator the following:
7. Cooling water flow meter T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, Vcold and V hot
8. Hot water flow meter 8. Allow the conditions to stabilise and record the observations.
9. Hot water in/out 9. The procedure may be repeated with different hot and cold flow
10. Cold water in/out rates and different hot water inlet temperature if required.
11. Fill and sight tube
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering
1. Chamber Objectives
2. Heater • Visual demonstration of film wise and dropwise condensation, and
3. Drain/Fill Valve of nucleate boiling.
4,5. Dropwise & • Measurement of heat flux and surface heat transfer coefficient in
Film wise both film wise and dropwise condensation at pressures up to
Condenser atmospheric.
6. Steam Baffles • Demonstration of the effect of air in condensers.
7. Pressure Gauge • Investigation of the effect of air in condensers.
8. Pressure Relief • Investigation of the saturation pressure/temperature relationship for
Valve H2O between about 20°C and 100°C.
9. Air Extract • Demonstration of Daltons Law of Partial Pressures.
Valve Extractor
20,21. Water Inlet Technical Data
& Outlet hose • Dimensions of each Condenser:
Length 90mm • Internal diameter of chamber
Thermocouple Locations • Diameter 12.7mm Surface Area glass Cylinder: 76mm
t5 Steam / Saturated water 37 cm2 (3.7 x 10-3 m2) • Normal Water Capacity: 500cm3
t6 Dropwise/ Film wise Condenser surface • Internal Volume of Steam • Surface Area of Heating
t7 Cooling Water into Condenser Chamber (empty): 1840cm3 Element: 144cm2
t8 Cooling Water leaving Condenser
Temperature drop across condenser shell Procedure
1. Select and connect the heat exchanger that is to be demonstrated
first.
2. Having checked that there is sufficient water in the chamber to
cover the element by about 20mm, switch on the heater and
increase the water temperature (t1) to about 90-95°C.
3. Carry out the air extraction procedure as detailed in mannual and
then carry on heating until t1 reaches the desired value - say
100°C.
4. Adjust the condenser water flow rate to 50 g/s (maximum flow)
and adjust the heater power output until the steam temperature t5
is constant at the desired value say 100℃.
5. Observe the condensation process and then change over to the
other condenser and establish the same steam temperature t5 with
the cooling water flow rate at maximum (50g/s)
Condensation processes:
• Dropwise condensation: The steam condenses on the surface
forming a large number of static beads which grow in size. When a
1. Thermocouple sockets 12. Vent bead reaches a certain size it breaks away and rapidly runs down
2. Main switch 13. Tank drain valve • the surface, gathering all the static beads in its path.
3. Heater switch • Film wise condensation: The surface of the condenser is covered
4. RCCB with an unbroken film of liquid which steadily increases in
5. Water temperature control thickness as it flows downward. The smooth surface of the liquid
6. Temperature indicator film indicates that flow within it is probably laminar and that there
7. Cooling water flow meter will be little or no mixing of the hot outer layer with the cooler
8. Hot water flow meter inner layer close to the condenser surface. In this case, heat transfer
9. Hot water in/out from the condensing steam (on the outer layer of the film) to the
10. Cold water in/out metal surface is by conduction through the film of liquid.
11. Fill and sight tube
King Abdulaziz University
Faculty of Engineering, Rabigh
Dep. of Chemical & Mat. Engineering