DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101
PURPOSE :
ISSUED FOR APPROVAL
REV Description Prepared Checked Approved Date
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |2
LEMBAR REVISI
REV DATE DESCRIPTION
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |3
DAFTAR ISI
LEMBAR REVISI..................................................................................................................... 2
1 GENERAL ........................................................................................................................ 6
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |4
DAFTAR TABEL
Tabel 1-1 Kontrol Lendutan pada Struktur Baja Untuk Bangunan Gedung ............................ 7
Tabel 4-1 Tabel Rasio Tegangan.......................................................................................... 14
Tabel 4-2 Tabel Lendutan Struktur ....................................................................................... 16
Tabel 4-3 Tabel Simpangan Struktur .................................................................................... 16
EPC CONTRACTOR
PT. NINDYA KARYA (Persero)
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |5
DAFTAR GAMBAR
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |6
1 GENERAL
Untuk baja profil, plat baja dan material baja struktural lainnya mengacu kepada JIS G3101 atau
ASTM A36 atau SS 400 dengan tegangan leleh minimum 240 MPa dan modulus elastisitas
210,000 MPa. Untuk bolt dan nut direncanakan memenuhi ASTM A.307 dan ASTM A.325
seluruhnya digalvanis.
EPC CONTRACTOR
PT. NINDYA KARYA (Persero)
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |7
Tabel 1-1 Kontrol Lendutan pada Struktur Baja Untuk Bangunan Gedung
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |8
L 75.75.6
L 50.50.6
Gambar 2-2 Profil Struktur
3 PERHITUNGAN PEMBEBANAN
Area Skirtboard
Sesuai loading data, sbb:
- Carry Idler ( 39 / 0,4 ) : 97.5 kg/m
- Return Idler : 17.6 kg/m
- Belt mass : 24.0 kg/m
Total Beban SDL : 139.2 kg/m = 69.55 kg/m per-sisi
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 Page |9
Inlet Chute
Sesuai loading data, Point Load : 3.7 Kn
Jumlah kaki tumpuan chute : 6 pcs
Beban Chute : 0.617 Kn
: 62.9 Kg
Inlet Chute
Sesuai loading data, Point Load : 2.8 Kn ( 6.5 – 3.7 kn )
Panjang tumpuan chute : 2,48 m
Beban Chute : 1.13 Kn/m
: 115.1 Kg/m = 57.6 kg/m per-sisi
EPC CONTRACTOR
PT. NINDYA KARYA (Persero)
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 10
The wind load is based on SKBI - 1.353.1987 The wind load is based on SKBI - 1.353.1967
Velocity v= 33.33 m/sec Velocity v= 33.33 m/sec
= 120.00 km/hr = 120.00 km/hr
a= 0 [roof] a= 0 [roof]
Pressure v2 = 69.43 kg/m2 Pressure v 2 69.43 kg/m2
P P=
16 16
= 0.07 t/m2 = 0.07 t/m2
UNP 150.75.6,5.10 L 75.75.6
X Y X Y
WIND IN-WALL WIND IN-WALL WIND IN-WALL WIND IN-WALL
C = 1.6 C = 1.6 C = 1.6 C = 1.6
P1 = (P x C) = 0.111 t/m2 P1 = (P x C) = 0.111 t/m2 P1 = (P x C) = 0.111 t/m2 P1 = (P x C) = 0.111 t/m2
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 11
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 12
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 13
Kondisi ultimit
ULS 101 : 1.4 (D+SDL)
ULS 201 : 1.2 (D+SDL) + 1.6 LIVE + 0.5 Lr
ULS 202 : 1.2 (D+SDL) + 1.6 LIVE + 0.5 R
ULS 301 : 1.2 (D + SDL) + 1.0 LIVE + 1.6 R
ULS 302 : 1.2 (D + SDL) + 1.0 LIVE + 1.6 Lr
ULS 303 : 1.2 (D + SDL) + 1.6 R + 0.5 Wx Non-Seismic
ULS 304 : 1.2 (D + SDL) + 1.6 Lr + 0.5 Wy
ULS 401 : 1.2 (D + SDL) + 1.0 LIVE + 0.5 Lr + 1.0 Wx
ULS 402 : 1.2 (D + SDL) + 1.0 LIVE + 0.5 Lr + 1.0 Wy
ULS 403 : 1.2 (D + SDL) + 1.0 LIVE + 0.5 R + 1.0 Wx
ULS 404 : 1.2 (D + SDL) + 1.0 LIVE + 0.5 R + 1.0 Wy
ULS 501 : 1.2 (D + SDL) + 1.0 LIVE + 0.3 Eqx + 1.0 Eqy
ULS 502 : 1.2 (D + SDL) + 1.0 LIVE + 0.3 Eqx - 1.0 Eqy
ULS 503 : 1.2 (D + SDL) + 1.0 LIVE - 0.3 Eqx + 1.0 Eqy
ULS 504 : 1.2 (D + SDL) + 1.0 LIVE - 0.3 Eqx - 1.0 Eqy
Seismic
ULS 505 : 1.2 (D + SDL) + 1.0 LIVE + 1.0 Eqx + 0.3 Eqy
ULS 506 : 1.2 (D + SDL) + 1.0 LIVE + 1.0 Eqx - 0.3 Eqy
ULS 507 : 1.2 (D + SDL) + 1.0 LIVE - 1.0 Eqx + 0.3 Eqy
ULS 508 : 1.2 (D + SDL) + 1.0 LIVE -1.0 Eqx - 0.3 Eqy
ULS 601 : 0.9 (D + SDL) + 1.0 Wx
Non-Seismic
ULS 602 : 0.9 (D + SDL) + 1.0 Wy
ULS 603 : 0.9 (D + SDL) + 1.0 Eqx + 0.3 Eqy
ULS 604 : 0.9 (D + SDL) + 1.0 Eqx + -0.3 Eqy
ULS 605 : 0.9 (D + SDL) + -1.0 Eqx + 0.3 Eqy
ULS 606 : 0.9 (D + SDL) + -1.0 Eqx + -0.3 Eqy
Seismic
ULS 701 : 0.9 (D + SDL) + 0.3 Eqx + 1.0 Eqy
ULS 702 : 0.9 (D + SDL) + 0.3 Eqx + -1.0 Eqy
ULS 703 : 0.9 (D + SDL) + -0.3 Eqx + 1.0 Eqy
ULS 704 : 0.9 (D + SDL) + -0.3 Eqx + -1.0 Eqy
EPC CONTRACTOR
PT. NINDYA KARYA (Persero)
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 14
ENGINEERING DOCUMENT
PT. PUPUK KALTIM
-
DESIGN CALCULATION FOR STRUCTURE STRINGER CV-101 P a g e | 16
Lendutan maksimum yang terjadi adalah 0.587 mm. dengan lendutan izin L/240 = 3000/240 =
12.50 mm. sehingga lendutan yang terjadi masih dibawah nilai yang diijinkan