SUBJECT: FOUNDRY ELECTRICAL LOADS COMPUTATION

AREA: Steel Building (Foundry)


SIN 100038970101

ITEM DESCRIPTION NO. OF POWER RATING POWER RATING Proposed load to be


Power factor Load in KW
NO. UNITS (KVA) (Total KVA) retained (KW)

1 Induction Furnace (300KW) 1 345.000 345.00 0.80 276.00 0.00


2 Induction Furnace (Inductotherm 150KW) 1 175.000 175.00 0.80 140.00 140.00
3 Shot Blasting 1 15.600 15.60 0.80 12.48 12.48
4 Furan Sand Mixer 1 7.500 7.50 0.80 6.00 6.00
5 Sand Reclaimer 1 22.000 22.00 0.80 17.60 17.60
6 Air Compressor 1 29.840 29.84 0.80 23.87 23.87
7 Shell Firing 1 3.600 3.60 0.80 2.88 2.88
8 Mini Boiler 1 2.600 2.60 0.80 2.08 2.08
9 Dust Collector 1 1.500 1.50 0.80 1.20 1.20
10 Slurry Mixer 1 3.000 3.00 0.80 2.40 2.40
11 Wax Injection 1 3.200 3.20 0.80 2.56 2.56
12 Wax Curing Tank 1 2.100 2.10 0.80 1.68 1.68
13 Melting Tank 1 3.000 3.00 0.80 2.40 2.40
14 ACU (3TR) 2 3.900 7.80 1.00 7.80 6.24
15 ACU (WT) 2 1.900 3.80 1.00 3.80 3.04
16 Small Power Outlets 12 0.036 0.43 1.00 0.43 0.35
17 Lightings 36 0.014 0.50 1.00 0.50 0.40

TOTAL 626.48 503.69 225.18

Note: To retire the Induction Furnace (300KW) to reduce the total electrical load by 55%