You are on page 1of 3

SR.

NO. DESCRIPTION OF ITEMS UoM QTY

1.0 SITC of Variable Refrigerant Type System


SITC of coated fins, panel, corrosion resistant coated condenser, inverter
based condenser fan, M.S. hot dip galvanised stands / supports, electrical &
microprocessor panel, isolating valves, etc. AS REQUIRED. THE UNIT CAPACITY
1.1 DEFINED BELOW SHALL BE AT AMBIENT TEMPERATURE OF 42 ºC

a 14 HP VRV (TOP DISCHARGE) CIRCUIT - 01 each 2


b 20 HP VRV (TOP DISCHARGE) CIRCUIT - 02 each 1
c 20 HP VRV (TOP DISCHARGE) CIRCUIT - 03 each 1
d 20 HP VRV (TOP DISCHARGE) CIRCUIT - 05 each 2
e 14 HP VRV (TOP DISCHARGE) CIRCUIT - 08 each 2
f 16 HP VRV (TOP DISCHARGE) CIRCUIT - 09 each 1
g 16 HP VRV (TOP DISCHARGE) CIRCUIT - 10 each 2
h 20 HP VRV (TOP DISCHARGE) CIRCUIT - 11 each 1
i 14 HP VRV (TOP DISCHARGE) CIRCUIT - 12 each 1
j 14 HP VRV (TOP DISCHARGE) CIRCUIT - 13 each 2
k 20 HP VRV (TOP DISCHARGE) CIRCUIT - 14 each 1
l 20 HP VRV (TOP DISCHARGE) CIRCUIT - 15 each 1
m 12 HP VRV (TOP DISCHARGE) CIRCUIT - 16 each 1

SITC OF WALL MOUNTED Hi-WALL UNITS (Noise Level to be <40 Db at


Medium Speed in the
Room).

a 0.60 TR each 2
b 1.00 TR each 3
b 1.60 TR each 2
c 2.00 TR each 38

1.2 SITC OF CEILING SUSPENDED 4 WAY CASSATTE UNITS (Noise Level to be <40
Db at Medium Speed in the Room).
a 1.00 TR each 3
b 1.28 TR each 1
c 1.60 TR each 4
d 2.00 TR each 12
d 2.26 TR each 1
e 2.56 TR each 24
f 3.18 TR each 4
g 4.00 TR each 4

1.3 CEILING SUSPENDED DUCTABLE HIGH STATIC UNITS (Noise Level to be <45
Db at Medium Speed in the
Room).

a 6.36 TR each 2
b 8.00 TR each 2

1.4 Remote Control with receiver


a Corded remote controllers each 4
b Cordless remote controllers each 98

Computer controlled network system for monitoring & controlling all indoor &
outdoor units with required control cabling between all indoor and outdoor
units, central point including all software & cabling. Controller shall be with
open protocol for soft integration with Building automation system(BAS).
Necessary software shall be provided to ON/OFF/control VRF indoor and
outdoor units through BAS for all Units. CONTRACTOR TO STUDY TENDER
DRAWING PRIOR TO QUOTE FOR LENGTH OF CONTROL CABLING FROM THE
1.4 CONTROLLER TO BE MOUNTED AT RECEPTION AREA. SUITABLE PC IF each 1
REQUIRED, SHALL BE PROVIDED BY THE PURCHASER

1.5 Supply & Installation of the following components of VRV system:


REFRIGERANT PIPING & CONTROL CABLING
All required refrigerant piping & power/control cable from indoor to outdoor
units as per OEM requirement with REFRIGERANT JOINTS, Hard Copper
refrigerant piping between indoor & outdoor units (Single Distance to be
considered)) of neatly brazed & should pass thru in sleeves provide in
columns / beams. Refrigerant piping and cabling running at terrace level &
Inside the air-conditioing area shall be on the perforated heavy duty cable tray
and duly epoxy coated Black painted clamps . Refrigerant pipes shall be
insulated with 13mm Thick Closed Cell Elastomeric Tube Insulation covered
1.6 with 7mil glass cloth of fire retardant quality and painted with anti UV paint
and final coat of Anti rodant repelent as per specifications.

a 14 HP VRV (TOP DISCHARGE) CIRCUIT - 01 RMT 80


b 20 HP VRV (TOP DISCHARGE) CIRCUIT - 02 RMT 55
c 20 HP VRV (TOP DISCHARGE) CIRCUIT - 03 RMT 40
d 20 HP VRV (TOP DISCHARGE) CIRCUIT - 05 RMT 130
e 14 HP VRV (TOP DISCHARGE) CIRCUIT - 08 RMT 95
f 16 HP VRV (TOP DISCHARGE) CIRCUIT - 09 RMT 75
g 16 HP VRV (TOP DISCHARGE) CIRCUIT - 10 RMT 115
h 20 HP VRV (TOP DISCHARGE) CIRCUIT - 11 RMT 95
i 14 HP VRV (TOP DISCHARGE) CIRCUIT - 12 RMT 70
j 14 HP VRV (TOP DISCHARGE) CIRCUIT - 13 RMT 120
k 20 HP VRV (TOP DISCHARGE) CIRCUIT - 14 RMT 115
l 20 HP VRV (TOP DISCHARGE) CIRCUIT - 15 RMT 110
m 12 HP VRV (TOP DISCHARGE) CIRCUIT - 16 RMT 90

Providing and erecting approved make split air-conditioning unit consisting of


copper condensing unit with fan motor, hermetically sealed rotary compressor
with accessories etc. duly connected separately erected evaporating unit and
blower motor with its accessories by means of extra supplied proper insulated
copper tubing,drain PVC pipes suitable for ( cost includes powder coated
Stand, Eco Friendly green gas charging, 15A plug top & Remote Control) with
a necessary core cutting. 2
1. 1.56TR CAPACITY

Providing and erecting approved make split air-conditioning unit consisting of


copper condensing unit with fan motor, hermetically sealed rotary compressor
with accessories etc. duly connected separately erected evaporating unit and
blower motor with its accessories by means of extra supplied proper insulated
copper tubing,drain PVC pipes suitable for ( cost includes powder coated
Stand, Eco Friendly green gas charging, 15A plug top & Remote Control) with
b necessary core cutting. 2
1. 2.56TR CAPACITY

Providing and erecting approved make Cassette type split air-conditioning unit
consisting of condensing unit with fan motor, hermetically sealed scroll/rotary
compressor with accessories etc. duly connected separately erected
evaporating unit and blower motor with its accessories by Eco friendly Green
gas charging & Internal copper wiring & Remote control ( 3 star and above of
c current year) with necessary core cutting. 1
1. 4TR CAPACITY-3 PH

3.0 M.S. Stand for installing VRV outdoor units duly epoxy coated Black paint Kgs 3600

PVC Drain piping for the units with 9mm Thick Closed Cell Elastomeric Tube
Insulation covered with 7mil glass cloth of fire retardant quality and painted
with anti UV paint and final coat of Anti rodant
3.1 repelent as per specifications.

a 25 mm RMT 495
b 32 mm RMT 130
c 40 mm RMT 76
d 50 mm RMT 20

3.2 Testing & Commissioning charges along with topping-up of refrigerant & OIL Lot 1
AS REQUIRED

3.3 All Refrigerant Joints each 99