You are on page 1of 49

JURUTERA PERUNDING SB SDN. BHD. COMPANY NO.

27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402
2 x 2.1 x 3 x 4.75 x 10 = 599 299
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

12.35 + 1.2 = 13.55


18.5 + 1.2 = 19.7

Total area = #REF! sq.m Total Weight / Area = #REF!


kN/m2

Uplift load:
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Max. flood level = 22.60 m

Min. base level = 15.83 m

Uplift load = 1 x 50.76 x 6.77 x 10

= 3436.5 kN

Total Weight = 5269 = 1.53 > 1.1


Uplift force 3436.5

Uplift load for base with hill: m


Max. flood level = 35.15
m
Min. base level = 28.8
6.35
Uplift load = 15.42 x 19.7 x x 10

= 19290 kN

Total Weight = 5018 = 0.26 > 1.1


Uplift force 19290
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 Tank A


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 Tank B
2 x 2.1 x 3 x 4.75 x 10 = 599 299 Tank C
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 Total dead l
431 kN

Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74 Total live loa


1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN Ultimate loa

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 421


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 552
2 x 2.1 x 3 x 4.75 x 10 = 599 299 1042
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 Total dead load
431 kN

Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74 Total live load


1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN Ultimate load,

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 211


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 276
2 x 2.1 x 3 x 4.75 x 10 = 599 299 521
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 Gk
431 kN

Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74 Qk


1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN n

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 340


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 678
2 x 2.1 x 3 x 4.75 x 10 = 599 299 820
1662 kN
2015

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 Tank a
431 kN Tank b
Tank c
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74 Tank a
1 x 0.4 x 5.32 x 3.6 x 24 184 Tank b
1 x 0.4 x 4.75 x 3.8 x 24 173 Tank c
258 kN Tank a
Tank b
Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74 Tank c
1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402
2 x 2.1 x 3 x 4.75 x 10 = 599 299
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184 1
1 x 0.4 x 4.75 x 3.8 x 24 = 173 1243
431 kN 1683
2266
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74 2
1 x 0.4 x 5.32 x 3.6 x 24 184 2
1 x 0.4 x 4.75 x 3.8 x 24 173 2
258 kN 1743
2359
Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74 3175
1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402
2 x 2.1 x 3 x 4.75 x 10 = 599 299
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184 1/2
1 x 0.4 x 4.75 x 3.8 x 24 = 173 621
431 kN 841
1133
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74
1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:
UDL
Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 1416
2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 1853
2 x 2.1 x 3 x 4.75 x 10 = 599 299 3501
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:
SLAB 400
Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 1.77
2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 0.3
2 x 2.1 x 3 x 4.75 x 10 = 599 299 0.87
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184 kn/m
1 x 0.4 x 4.75 x 3.8 x 24 = 173 1009
431 kN 1094
1770
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74
1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129 459


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402 140
2 x 2.1 x 3 x 4.75 x 10 = 599 299 428
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 10902
431 kN 21262
36312
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74
1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN. BHD. COMPANY NO. 27875 P

CALCULATION SHEET SHEET

Job: KOLAM A Contract No: MGZ-1


Part of Work: Raw Water Intake
Group: Structural Assistant: MFQ Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$full

Total Weight:

Water = 2 x 2.1 x 1.6 x 3.85 x 10 = 259 129


2 x 2.1 x 3.6 x 5.32 x 10 = 804 402
2 x 2.1 x 3 x 4.75 x 10 = 599 299
1662 kN

Wall A = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173 5451
431 kN 10631
18156
Wall B = 1 x 0.4 x 3.85 x 2 x 24 = 74
1 x 0.4 x 5.32 x 3.6 x 24 184
1 x 0.4 x 4.75 x 3.8 x 24 173
258 kN

Wall C = 1 x 0.4 x 3.85 x 2 x 24 = 74


1 x 0.4 x 5.32 x 3.6 x 24 = 184
1 x 0.4 x 4.75 x 3.8 x 24 = 173
431 kN

Wall D = 1 x 0.4 x 5.4 x 3.85 x 24 = 200


200

Wall E = 1 x 0.4 x 5.4 x 5.32 x 24 = 276


276 kN

Wall F = 1 x 0.4 x 5.4 x 4.75 x 24 = 246


246 kN

Total Wall = 431 + 258 + 431 + 200 + 276 + 246


= 1842 kN

Slab = 2.17 x 5.4 x 2 x 24 = 562


0.7 x 5.4 x 3.6 x 24 = 327
1.27 x 5.4 x 3.8 x 24 = 625
1515 kN

Total Weight = 1662 + 1842 + 1515 + 5% Weight of pump,valve and pipe

= 5018 kN + 250.88 kN

= 5269 kN

Area = 50.76 m2 Total Weight / Area = 98.8


98.8 kN/m2

For Base With Hill


1.87 + 0 = 1.87
#REF! + 1.2 = #REF!
JURUTERA PERUNDING SB SDN BHD
CALCULATION SHEET SHEET

Job: KOLAM A Contract No:


Part of Work: Intake
Group: Structural Assistant: ABA Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Intake

Total Weight:

Wall A,B & C = 1.6 x 0.4 x 3.85 x 3 x 24 = 177

Wall D,E & F = 3.6 x 0.4 x 5.32 x 3 x 24 = 552

Wall G,H & I = 3 x 0.4 x 4.75 x 3 x 24 = 410

Wall J & K = 2.7 x 0.4 x 1.9 x 2 x 24 = 98

Wall L = 3.85 x 0.4 x 5.4 x 1 x 24 = 200

Wall M = 5.32 x 0.4 x 5.4 x 1 x 24 = 276

Wall N = 4.75 x 0.4 x 5.4 x 1 x 24 = 246

Wall O = 1.9 x 0.25 x 5.4 x 1 x 24 = 62

Base 1 = 2 x 5.4 x 2.17 x 24 = 562

Base 2 = 3.6 x 5.4 x 0.7 x 24 = 327

Base 3 = 3.8 x 5.4 x 1.27 x 24 = 625

Base 4 = 2.95 x 5.4 x 0.4 x 24 = 153

+ 10% MISC 369

Total Weight = 4057 kN

= 4057 kN

Total load on soil = 4057 = 79.93 kN/m2


19.44 + 31.32

Soil Bearing Capacity = 1 kN/m2 (lower) & 154.85 kN/m2 (upper)

Uplift load:

Max. flood level = 9.32 m


Min. base level = 4.5 m

Density of saturated soil = 8 kN/m3


(if tank with heel)

Length of heel = 0 m

Weight of soil = 0 kN

Hence, Total weight = #VALUE! kN

Uplift load = 19.44 + 31.32 x 4.82 x 10

= 2447 kN

Total Weight = ### = ### => #VALUE!


Uplift force 2447

Note: (Factor of safety for floatation must be > 1.1)


kN

kN

kN

kN

kN

kN

kN

kN

kN

kN

kN

kN

kN
ly 2700 ly 3600 ly 3800
lx 1800 lx 2700 lx 2700
1.5 1.3 1.4

1800 3600 3800

2700

2700

Moment x continuous ed mid span Moment Y continuous edge mid span


Panel A-B 440.22 332.99 Panel A-B 253.97 191.89
Panel B-C 1065.76 807.91 Panel B-C 636.02 481.31
Panel C-D 1712.54 1272.83 Panel C-D 1041.41 786.84

-1712.54

-811.26 -811.26
-394.45

+ 332.99
+ 807.91
+ 1272.83

Size column 400 x 400 to reduce moment 0.15Fhc


Moment distribution 0.15 x 1562 x 0.4 93.72
Column Strip Minddle strip -394.45 + 93.72 -300.73
55% 45%
75% 25%
55% 45%
75% 25%
55% 45%
75% 25%
Flat Slab Design tp BS8110:Part 1997

Slab Dimension
Span of slab in x-direction Span x 2000 3600 3800 mm
Span of slab in y-direction Span y 2700 2700 2700 mm
Column diemntion in x-direction lx 400 400 400 mm
Column diemntion in y-direction ly 400 400 400 mm
External column dimension in x-direction lx1 250 250 250 mm
External column dimension in y-direction ly1 250 250 250 mm
Edge dimension in x-direction ex 125 125 125 mm
Edge dimension in y-direction ey 125 125 125 mm
Effective span of internal bay in x-direction Lx 1600 3200 3400 mm
Effective span of internal bay in y-direction Ly 2300 2300 2300 mm
Effective span of end bay in x-direction Lx1 1800 3400 3600 mm
Effective span of end bay in y-direction Ly1 2500 2500 2500 mm

Slab details
Depth of slab h 2170 700 1270 mm
Charecteristic strenght of concrete fcu 35 N/mm2
Charecteristic strenght of reinforcement fy 460 N/mm3
Charecteristic strenght of shear reinforcement fyv 460 N/mm4
Material safety factor ym 1.15
Cover to bottom reinforcement c 25 mm
Cover to top reinforcement c' 25 mm

Load details
Characteristic dead load Gk 1243 1683 2266 kN/m2
Characteristic Imposed load Qk 2 2 2 kN/m2
Dead load factor yG 1.4 1.4 1.4
Imposed load factor yK 1.6 1.6 1.6
Total ultimate load Nult 1742 2358 3175 kN/m2
Moment redistribution ratio Bb 1 1.3 1.4
Ratio of support moment to span moments i 1

Design slab in the x direction


Sagging Moment
End bay A-B
Effective span L 1800 mm
Depth of reinforment d 2135 mm
Midspan moment m 333 kNm/m
Support moment m' 440 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.002 K < K'
Compression reinforcement is not required
z 2028 mm
Area of reinforcement design As_des 376 mm2/m
Minimum area of reinforcemenr required As_min 2821 mm2/m
Area of reinforcement required As_req 2821 mm2/m
Provided 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 2514 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 344 N/mm2
Modification factor k1 1.78 <2
Allowable span to depth ratio 0.9x26xk1` 41.65
Actual span to depth ratio L/d 0.843
PASS - Span to depth ratio is OK
Internal bay B-C
Effective span L 3200 mm
Depth of reinforcement d 662.5 mm
Midspan moment m 808 kNm/m
Support moment m' 1066 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.053 K<K'
Compression reinforcement is not required
z 621 mm
Area of reinforcement designed As_des 3251 mm2/m
Minimum area of reinforcement required As_min 910 mm2/m
Area of reinforcement required As_req 3251 mm2/m
Provide 25 die bars @ 100 centres
. As_prov 4909 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 203 N/mm2
Modification factor k1 2.00
Allowable span to depth ratio 0.9x26xk1` 46.80
Actual span to depth ratio L/d 4.830
PASS - Span to depth ratio is OK

End bay C-D


Effective span L 3600 mm
Depth of reinforment d 1207.5 mm
Midspan moment m 1273 kNm/m
Support moment m' 1713 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.025 K<K'
Compression reinforcement is not required
z 1147 mm
Area of reinforcement design As_des 2774 mm2/m
Minimum area of reinforcemenr required As_min 1651 mm2/m
Area of reinforcement required As_req 2774 mm2/m
Provided 25 dia bars @ 125 centres
Area of reinforcement provided As_prov 3928 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 217 N/mm2
Modification factor k1 2.00
Allowable span to depth ratio 0.9x26xk1` 46.80
Actual span to depth ratio L/d 2.981
PASS - Span to depth ratio is OK

HOGGING MOMENTS-INTERNAL STRIP


Internal column -B2
Consider the reinforcement concentrated in half width strip over the support
Depth of reinforcement d' 2135 mm
Support moment m' 440.22 kNm/m
Lever arm K' 0.1764
K 0.0028 K<K'
Compression reinforcement is not required
z 2028 mm
Area of reinforcement required As_des 542.61 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 2821.00 mm2/m
Provide 25 dia bars @ 150 centres
Area of reinforcement provided As_prov 3273 mm2/m
PASS - Span reinforcement is OK
Internal column C2
Consider one and a half bays of negetive moment being resisted over the edge and penultimate column
Depth of reinforcement d' 1207.5 mm
Support moment m' 1712.54 kNm/m
Lever arm K' 0.176
K 0.034 K<K'
Compression reinforcement is not required
z 1147 mm
Area of reinforcement required As_des 3732 mm2/m
Minimum area of reinforcement required As_min 1570 mm2/m
Area of reinforcement required As_req 3732 mm2/m
Provide 25 dia bars @ 125 centres
Area of reinforcement provided As_prov 3928 mm2/m
PASS - Span reinforcement is OK

HOGGING MOMENTS-ENTERNAL STRIP


Corner Column A1, A3
Depth of reinforcement d' 2135 mm
Total load of column S 2891 kN
Area of column head A 0.100 m2
Support moment m' 440.22 kNm/m
Lever arm K' 0.176
K 0.000 K<K'
Compression reinforcement is not required
z 2028 mm
Area of reinforcement required As_des 543 mm2/m
Minimum area of reinforcement required As_min 2776 mm2/m
Area of reinforcement required As_req 2776 mm2/m
Provide 25 dia bars @ 175 centres
Area of reinforcement provided As_prov 2805 mm2/m
PASS - Span reinforcement is OK

Corner Column D1, D3


Depth of reinforcement d' 1207.5 mm
Total load on column S 9482 Kn
Area of Column head A 0.100 m2
Support Moment m' 3490 kNm/m
Lever arm K' 0.1764
K 0.0001 K<K'
Compression reinforcement is not required
z 1147 mm
Area of reinforcement required As_des 7606 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 7606 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 2514 mm2/m
PASS - Span reinforcement is OK

Edge Column A2
Depth of reinforcement d' 2135 mm
Total load on column S 5139 Kn
Area of Column head A 0.012 m2
Support Moment m' 834 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 2028.25 mm
Area of reinforcement required As_des 0.0010 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 2821 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK
Edge Column D2
Depth of reinforcement d' 1207.5 mm
Total load on column S 5139 Kn
Area of Column head A 0.575 m2
Support Moment m' 580 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 1147.125 mm
Area of reinforcement required As_des 0.0013 mm2/m
Minimum area of reinforcement required As_min 1569.75 mm2/m
Area of reinforcement required As_req 1569.75 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Edge Column B1, B3


Depth of reinforcement d' 2135 mm
Total load on column S 5139 Kn
Area of Column head A 0.575 m2
Support Moment m' 420 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 2028.25 mm
Area of reinforcement required As_des 0.0005 mm2/m
Minimum area of reinforcement required As_min 3667.3 mm2/m
Area of reinforcement required As_req 3667.3 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Edge Column C1, C3


Depth of reinforcement d' 1207.5 mm
Total load on column S 17793 Kn
Area of Column head A 0.0002 m2
Support Moment m' 3354 kNm/m
Lever arm K' 0.1764
K 0.0001 K<K'
Compression reinforcement is not required
z 1147.125 mm
Area of reinforcement required As_des 7309 mm2/m
Minimum area of reinforcement required As_min 1385 mm2/m
Area of reinforcement required As_req 7309 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Between columns 1-2, 2-3


Around the perimeter the column heads provide a minimum of 50% of the required end span bottom
reinforcement
Area of reinforcement required As_req
Provide 16 dia bars @ 150 centres - 'U' bars with 1600mm long legs
Area of reinforcement provided
Design Slab in Y-direction
Sagging Moment
End bay 1-2 (A-B)
Effective span L 2500 mm
Depth of reinforment d 2125 mm
Midspan moment m 192 kNm/m
Support moment m' 254 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.001 K < K'
Compression reinforcement is not required
z 2019 mm
Area of reinforcement design As_des 238 mm2/m
Minimum area of reinforcemenr required As_min 2821 mm2/m
Area of reinforcement required As_req 2821 mm2/m
Provided 25 dia bars @ 150 centres
Area of reinforcement provided As_prov 3273 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 264 N/mm2
Modification factor k1 2.00
Allowable span to depth ratio 0.9x26xk1` 46.80
Actual span to depth ratio L/d 1.176
PASS - Span to depth ratio is OK

Internal bay 1-2 (B-C)


Effective span L 2500 mm
Depth of reinforcement d 645 mm
Midspan moment m 481 kNm/m
Support moment m' 636 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.033 K<K'
Compression reinforcement is not required
z 613 mm
Area of reinforcement designed As_des 1964 mm2/m
Minimum area of reinforcement required As_min 910 mm2/m
Area of reinforcement required As_req 1964 mm2/m
Provide 20 die bars @ 200 centres
. As_prov 1571 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 383 N/mm2
Modification factor k1 1.42
Allowable span to depth ratio 0.9x26xk1` 33.14
Actual span to depth ratio L/d 3.876
PASS - Span to depth ratio is OK

End bay 1-2 (C-D)


Effective span L 2700 mm
Depth of reinforment d 1225 mm
Midspan moment m 787 kNm/m
Support moment m' 1041 kNm/m
Design reinforcement
Lever arm K' 0.176
K 0.015 K<K'
Compression reinforcement is not required
z 1164 mm
Area of reinforcement design As_des 1690 mm2/m
Minimum area of reinforcemenr required As_min 1651 mm2/m
Area of reinforcement required As_req 1690 mm2/m
Provided 20 dia bars @ 175 centres
Area of reinforcement provided As_prov 1795 mm2/m
PASS - Span reinforcement is OK
Check deflection
Design service stress fs 289 N/mm2
Modification factor k1 2.00
Allowable span to depth ratio 0.9x26xk1` 46.80
Actual span to depth ratio L/d 2.204
PASS - Span to depth ratio is OK

HOGGING MOMENTS-ENTERNAL STRIP


Corner Column A1, A3
Consider one and a half bays of negetive moment being resisted over the edge and penultimate column
Depth of reinforcement d' 2125 mm
Total load on column S 2891 Kn
Area of Column head A 0.100 m2
Support moment m' 878.64 kNm/m
Lever arm K' 0.1764
K 0.0000 K>K'
Compression reinforcement is not required
z 2019 mm
Area of reinforcement required As_des 0.00 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 2821.00 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Corner Column D1, D3


Depth of reinforcement d' 1225 mm
Total load on column S 9482 Kn
Area of Column head A 0.1 m2
Support Moment m' 3212.96 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 1164 mm
Area of reinforcement required As_des 0.007 mm2/m
Minimum area of reinforcement required As_min 1651 mm2/m
Area of reinforcement required As_req 1651 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Edge Column A2
Depth of reinforcement d' 2125 mm
Total load on column S 5139 Kn
Area of Column head A 0.1 m2
Support Moment m' 676 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 2018.75 mm
Area of reinforcement required As_des 0.0378 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 2821 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK
Edge Column D2
Depth of reinforcement d' 1225 mm
Total load on column S 17793 Kn
Area of Column head A 0.100 m2
Support Moment m' 2416 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 1163.75 mm
Area of reinforcement required As_des 0.1697 mm2/m
Minimum area of reinforcement required As_min 1651 mm2/m
Area of reinforcement required As_req 1651 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Edge Column B1, B3


Depth of reinforcement d' 2125 mm
Total load on column S 2952 Kn
Area of Column head A 0.100 m2
Support Moment m' 574 kNm/m
Lever arm K' 0.1764
K 0.0000 K<K'
Compression reinforcement is not required
z 2018.75 mm
Area of reinforcement required As_des 0.0536 mm2/m
Minimum area of reinforcement required As_min 2821 mm2/m
Area of reinforcement required As_req 2821.0000 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Edge Column C1, C3


Depth of reinforcement d' 1225 mm
Total load on column S 17793 Kn
Area of Column head A 0.100 m2
Support Moment m' 3397 kNm/m
Lever arm K' 0.1764
K 0.0001 K<K'
Compression reinforcement is not required
z 1163.75 mm
Area of reinforcement required As_des 0.0073 mm2/m
Minimum area of reinforcement required As_min 1651 mm2/m
Area of reinforcement required As_req 1651 mm2/m
Provide 20 dia bars @ 125 centres
Area of reinforcement provided As_prov 4909.375 mm2/m
PASS - Span reinforcement is OK

Between columns 1-2, 2-3


Around the perimeter the column heads provide a minimum of 50% of the required end span bottom
reinforcement
Area of reinforcement required As_req
Provide 16 dia bars @ 150 centres - 'U' bars with 1600mm long legs
Area of reinforcement provided As_prov
ly - lx/2

lx/4

PUNCHING SHEAR
Corner column A1
Design shear transfer to column Vt 2393 kN
Design effective shear transfer to column Veff 2991 kN
Area of tension steel in x-direction Asx_ten 2805 mm2/m
Area of tension steel in y-direction Asy_ten 2805 mm2/m
Column parameter uc 2550 mm
Average effective depth of reinforcement d 2090 mm
maximum allowable shear stress vmax 4.733 N/mm2
Design shear stress st column perimeter v0 0.00056 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(3097.5mm)
Length of shear perimeter u 8820 mm
Area of tension steel at shear perimeter As_ten 17595200 mm2
Design concrete shear stress vc 1.020 N/mm2
Nominal design shear stress at perimeter v 0.162 N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(4646.25mm)
Length of shear perimeter u 11955 mm
Area of tension steel at shear perimeter As_ten 17595200 mm2
Design concrete shear stress vc 1.020 N/mm2
Nominal design shear stress at perimeter v 0.120 N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(6186mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required
Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

Corner column A1
Design shear transfer to column Vt kN
Design effective shear transfer to column Veff kN
Area of tension steel in x-direction Asx_ten mm2/m
Area of tension steel in y-direction Asy_ten mm2/m
Column parameter uc mm
Average effective depth of reinforcement d mm
maximum allowable shear stress vmax N/mm2
Design shear stress st column perimeter v0 N/mm2
PASS - Maximum concrete shear stress not exceeded at column perimeter
Shear reinforcement at a perimeter of 1.50d-(321mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 2.25d-(482mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
Shear reinforcement required at perimeter Asv_req mm2
Shear reinforcement at a perimeter of 3.00d-(642mm)
Length of shear perimeter u mm
Area of tension steel at shear perimeter As_ten mm2
Design concrete shear stress vc N/mm2
Nominal design shear stress at perimeter v N/mm2
v < vc no shear reinforcement required

CURTAILMENT OF REINFORCEMENT
Internal column
Radius of circular yield line
Minimum curtailment length in x-direction
Minimum curtailment length in y-direction

Corner column
Radius of circular yield line
Minimum curtailment length in x-direction
Minimum curtailment length in y-direction
Edge column
Radius of circular yield line in x-direction
Minimum curtailment length in x-direction
Radius of circular yield line in y-direction
Minimum curtailment length in y-direction
=2*2.17*5.4*24
562 327 625

C1 C4 C7 C10

C2 C5 C8 C11

C3 C6 C9 C12

Size column 400 x 400 X 3000


h
Load
Self weight column = 0.4 x 0.4 x 3.0 x 24 11.52 Kn
slab weight
fcu 30 N/mm2
fy 460 N/mm2 effective length, le = βlo 2.7 Table 3.22
c 20 mm d=b-c-ølink-øbar/2 364 mm
d' 370 mm
slenderness ratio
Total dead load Gk Tank a 1113 le/h =2.7/0.4 6.75 <10
Tank b 1280 le/b =2.7/0.4 6.75 <10
Tank c 2266 short column (unbraced)
7.297297
1
Ultimate load
Total Dead Live load
Column Slab load Self load 1.4Gk +
load (Gk) (Qk)
1.6Qk
C1 186 12 197 0.5 277
C2 186 12 197 0.5 277
C3 186 12 197 0.5 277
C4 186 12 197 0.5 277
C5 186 12 197 0.5 277
C6 186 12 197 0.5 277
C7 378 12 389 0.5 546
C8 378 12 389 0.5 546
C9 378 12 389 0.5 546
C10 378 12 389 0.5 546
C11 378 12 389 0.5 546
C12 378 12 389 0.5 546

corner edge internal

be=cx+cy be=cx+y
be=cx+y 800

Moment transfer to column


Mt, max = 0.15*be*d^2*fcu
Load N 277 kN 546
Moment at span (about x-x axis) 2.13 kNm 2.46

Bending about x-x axis


End condition : top - 1, bottom - 3
From table 3.21 of the code b=0.9, lo=3000
so lex 2700 lex/h 6.75 <15

Bending about y-y axis


End condition : top - 1, bottom - 3
From table 3.21 of the code b=0.9, lo=3000
so lex 2700 lex/b 6.75 <10
": short and slender column

bending moment at x-x


lex 2700 mm
b' 400 mm
K 1

Madd = Nh/2000(le/b')^2 2.52 kNm 4.97


Minimum eccentricity, emin = 0.0 20 mm 20

From clause 3.8.3.2


1. M2 2.13 2.457
2. M1 = 0.4M1 +0.6M2 < 0.4M2 1.278 0.852 1.4742 0.9828
M1+Madd 3.37 5.95
3. M1 + Madd/2 2.113 3.47
4. Mmin = emin*N 5.54 10.91

Design moment Mt 5.54 10.91

N/bh 1.73 3.41


M/bh2 0.09 0.17

Assuming d = 400-20-20/2 370 370


d/h 0.93 ~ 0.95 0.95

From chart 30, 100As/bh = 0.4 As = 640 mm2 K factor 1


Modify design moment, Mt 73.25 73.38

Mt is greater then Mmin

N/bh 1.73
M/bh2 1.14 1.15
From chart 30, 100As/bh = 0.4 As 640 mm2 K factor 1

Use min moment Mmin 5.54 10.91


N/bh 1.73 3.41
M/bh2 0.09 0.17
From chart 30, 100As/bh = 0.4 As 640 mm2 K factor 1
Use 4/16 (805mm2)
4T16-250
K' 0.156 As_min 0.00468
Column Moment, Mt Shear K Z A' A
C1 2.1294 1.34 283 -718 -701 4T10-250 314 mm2
C2 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C3 2.1294 1.34 283 -718 -701 4T10-250 314 mm2
C4 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C5 2.1294 1.34 283 -718 -701 4T10-250 314 mm2
C6 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C7 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C8 2.457 1.55 283 -842 -823 4T10-250 314 mm2
C9 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C10 2.1294 1.34 283 -718 -701 4T10-250 314 mm2
C11 1.3104 0.82 283 -405 -395 4T10-250 314 mm2
C12 2.1294 1.34 283 -718 -701 4T10-250 314 mm2
Raft Foundation Design

Raft and soil definition

Soil definition
Allowable bearing pressure qallow 155 kN/m2
No. of types of soil Two or more types
Soil density Firm
Depth of hardcore beneath slab hhcoreslab 150 mm (Dispersal allowed for bearing
pressure check)
Density of hardcore yhcore 20 kN/m3
Basic assume dia. Of local dep'n ødepbasic 1500 mm
Dia. Under slab mod for hardcore ødepslab 1350 mm

Raft slab definition


Max dim between joints Imax 20 m
Slab thickness hslab 500 mm
Concrete strenght fcu 30 N/mm2
Poissons ratio of concrete v 0.2
Slab mesh reinft strengh fyslab 460 N/mm2
Partial safety factor for reinft ys 1.15
Min mesh for shrinkage (top) A252
Actual mesh adopted in top A393
Mesh adopted in bottom A393 (Asslabbtm = 393 mm2/m)
Top mesh bar diameter øslabtop 10 mm
Bottom mesh bar diameter øslabbtm 10 mm
Cover to top reinforcement Ctop 40 mm
Cover to btm reinforcement Cbtm 40 mm
Ave eff depth of top reinforcement dtslabav 450 mm
Ave eff depth of bottom reinforcement dbslabav 450 mm
Overall average effective depth dslabav 450 mm
Min eff depth of top reinft dtslabmin 445 mm
Min eff depth of bottom reinft dbslabmin 445 mm

Slab edge reinforcement


mesh provided in top
mesh provided in bottom
minimum width of edge reinforment
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

Design of Base Slab

4300

350

Vls Vss

Vls
Vss Mss Mls

P = S 24 X 0.35 = 8.4 kN/m2


Gk 10 X 4.3 = 43 kN/m2
= 51.4 kN/m3
Qk 1.5 = 1.5 kN/m2
1.4 gk + 1.6 qk = 74 kN/m2

ly/ lx = 1.10 (must be < than 2 for two way slab)

Moment *Use Table 3.14 & 3.15 (BS 8110):Part 1 to get the coefficients.
(1 edges discontinuous)

Mss (short span) = 0.049 x 74.36 x 2.3 =


2
19.53 kN.m

Mls (long span) = 0.037 x 74.36 x 2.3 =


2
14.74 kN.m

Vss (short span) = 0.4 x 74.36 x 2.3 = 68.86 kN

Vls (long span) = 0.36 x 74.36 x 2.3 = 61.97 kN

Page 38 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

Design of short span:

h = 350 mm
cover = 40 mm
f bar = 16 mm
d = 350 - 40 - 8
= 302 mm
b = 1000 mm
fcu = 35 N/mm
fy = 460 N/mm2
w = 0.2 mm

M1 = M - Ft ( d - h/2 )
= 19.53 - 0.00 ( 0.302 - 0.175 )
= 19.53 kN.m

Estimate of stress for 0.2 mm crack = 130 N/mm2

For design purposes, estimate the stress and assume z = 0.9d and calculate resulting
crack width, w

z = 0.9 x d
= 0.9 x 302
= 272 mm

As = M1 + Ft
required js x z js
=

= 19.53 x 10+6 + 0 x103


130 x 272 130

= 553 + 0
(As for M1) (As for Ft)

= 553 mm2/m

Try T 16 @ 250 mm c/c (As provided = 804 mm2/m)

Page 39 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

Actual As resisting M = 553 x 804 = 804 mm2


553

Actual As resisting Ft = 0x 804.2496 = 0 mm2


553

% age As resisting M = 804 x 100 = 0.266


1000 x 302

From table 9.10, for as % = 0.266

x = 0.246 x 302 = 74 mm

z = 0.917 x 302 = 277 mm

i) Calculation of crack width

x = 74 mm

d-x
h-x

48

125 a cr
surface

cr
125

bt = 1000 mm
As provided = 804 mm2
a' = 350 mm
Cmin = 40 mm
As actual = 804 mm2

Page 40 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

js = M1
As x z

= 19.53 x 10+6
804 x 277
= 87.64 N/mm2

xs = 87.64 = 0.000438
200000

x1 = xs x( h - x )
( d - x )

= 0.0004382 x( 350 - 74 )
( 302 - 74 )
= 0.0005306

Stiffening effect, x2 =

= bt x( h - x )x( a' - x )
3 x Es x As x( d - x )

= 1000 x( 350 - 74 )x( 350 - 74 )


3 x 200000 x 804 x( 302 - 74 )

= 0.00069

xm = x1 - x2
= 0.0005306 - 0.000692
= -0.000161

acr = s 2
+( cover + f )2 1/2
f
2 2 - 2

= 250 2
+( 40 + 16 )2 1/2
16
2 2 - 2

= 125.90 mm

Page 41 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

w = 3 x xm x acr
1 +2 acr - cmin
h - x

= 3 x -0.00016 x 125.90
1 +2 125.90 - 40
350 - 74

= -0.037 < 0.2 mm this is satisfactory. OK

ii) Ultimate State

M1U = 19.53 x 1.4 = 27.34 kNm

k = MU
fcu x b x d2

= 27.34 x106
35 x 1000 x 302 2

= 0.009

From table 9.11 'z/d' lever arm factors for ultimate bending moment

z = 0.95 x d
= 0.95 x 302
= 286.9

As for M1U = 27.34 x106 = 218


0.95 x 460 x 286.9

As for FtU = 0.00 x 1.40 x103 = 0


0.95 x 460

Total
218 < 804
OK

Page 42 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

iii) Design for Shear

Vu = 68.86 x 1.4 = 96.40 kN

u = 96.40 x 103
1000 x 302

= 0.32 N/mm2

% As = 100 x 804.2496
302 x 1000

= 0.27

uc = 0.79 x % As 1/3
x 400 1/4
x fcu 1/3

1.25 d 25

= 0.79 x 0.27 1/3


x 400 1/4 x 35 1/3

1.25 302 25
= 0.49 > 0.32 OK

iv) Deflection:

Slenderness ratio = 2550 / 302 = 8.4 < 20 OK

Crack Spacing And Crack Widths in Relation To Temperature And Moisture Effects

wmax = Maximum estimated crack width

R = Restraint factor = 0.5

a = coefficient of thermal expension 0.000010 / o C


of mature concrete

T1 = Fall in temperature = 37 oC

T2 = Seasonal fall in temperature = 0 oC

fct / fb = ratio of tensile strength 3 day concrete


Av. Bond stress concrete / steel

Page 43 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

f = diameter of bar

r% = % of steel in zone thickness

Smax = fct / fb * f / (2 * r) Eq. # 1

wmax = Smax * R * a * (T1 + T2) Eq. # 2

Where,
fct / fb = 0.67

R = 0.50 (Restraining Factor)

Wmax = 0.20 mm

a = 0.000010 / o C

T1 + T 2 = 37 oC

t = 350 mm Base Slab thickness

In Base Slab, for t<500mm, assume each reinforcement face controls half depth of
Concrete, ignoring any central core beyond this surface depth.

t1 = t/2 175 mm

From equation # 1,
Smax = 0.67 *f* 0.50 *1/r = 0.335 * f /r

From equation # 2,
wmax = Smax * 0.50 * 1E-05 * 37

= 0.335 * f /r * 0.000185

= 0.000062 * f /r

0.20 = 0.000062 * f /r

Page 44 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

From above, f/r= 3227

Diameter of % of steel Required area Spacing to be


Steel Bar, f r% of steel, As provided in each face
(Each face)

12 0.37 % 651 T12@125 (905)

16 0.50 % 868 T16@150 (1340)

20 0.62 % 1085 T20@200 (1570)

Use 16 250
ie As = 804 mm / m
2

Minimal horizontal reinforcement

As req = 0.0035 x 175 x 1000

= 612.5 mm2 / m < 804 mm2 / m

The min. reinforcement provided for bending are adequate enough

Design of long span:

h = 350 mm
cover = 40 mm
f bar = 16 mm
d = 350 - 40 - 16 - 8
= 286 mm
b = 1000 mm
fcu = 35 N/mm
fy = 460 N/mm2
w = 0.2 mm

Page 45 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)
M1 = M - Ft ( d - h/2 )
= 14.74 - 0.00 ( 0.286 - 0.175 )
= 14.74 kN.m

Estimate of stress for 0.2 mm crack = 130 N/mm2

For design purposes, estimate the stress and assume z = 0.9d and calculate resulting
crack width, w

z = 0.9 x d
= 0.9 x 286
= 257 mm

As = M1 + Ft
required js x z js
=

= 15 x106 + 0.00 x103


130 x 257 130

= 441 + 0
(As for M1) (As for Ft)

= 441 mm2/m

Try T 16 @ 250 mm c/c (As provided = 804 mm2/m)

Actual As resisting M = 441 x 804 = 804 mm2


441

Actual As resisting Ft = 0x 804 = 0 mm2


441

% age As resisting M = 804 x 100 = 0.28


1000 x 286

From table 9.10, for as % = 0.281

x = 0.159 x 286 = 45 mm

z = 0.947 x 286 = 271 mm

Page 46 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

i) Calculation of crack width

x = 45 mm

d-x
h-x

48

125 a cr
surface

cr
125

bt = 1000 mm
As provided = 804 mm2
a' = 350 mm
Cmin = 40 mm
As actual = 804 mm2

js = M1
As x z

= 14.74 x 10+6
804 x 271

= 67.69 N/mm2

xs = 67.69 = 0.000338
200000

x1 = xs x( h - x )
( d - x )

= 0.0003385 x( 350 - 45 )
( 286 - 45 )
= 0.0004285

Page 47 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

Stiffening effect, x2 =

= bt x( h - x )x( a' - x )
3 x Es x As x( d - x )

= 1000 x( 350 - 45 )x( 350 - 45 )


3 x 200000 x 804 x( 286 - 45 )

= 0.00080

xm = x1 - x2
= 0.0004285 - 0.000799
= -0.00037

acr = s 2
+( cover + f )2 1/2
f
2 2 - 2

= 250 2
+( 40 + 16 )2 1/2
16
2 2 - 2

= 126 mm

w = 3 x xm x acr
1 +2 acr - cmin
h - x

= 3 x -0.00037 x 126
1 +2 126 - 40
350 - 45

= -0.089 < 0.2 mm this is satisfactory. OK

ii) Ultimate State

M1U = 14.74 x 1.4 = 20.64 kNm

k = MU
fcu x b x d2

= 20.64 x106
35 x 1000 x 286 2

= 0.007

Page 48 of 49
PUTRA KONSULT SDN BHD

CALCULATION SHEET SHEET

JOB: SG RETANG Contract No:


Part of Work: SUCTION TANK
Group: STRUCTURAL Assistant: NMI Checked by: ABA
Date: December 11, 2023 File:
'file:///conversion/tmp/activity_task_scratch/711915101.xls'#$Base (without piles)

From table 9.11 'z/d' lever arm factors for ultimate bending moment

z = 0.95 x d
= 0.95 x 286
= 271.7

As for M1U = 20.64 x106 = 174


0.95 x 460 x 271.7

As for FtU = 0.00 x 1.40 x103 = 0


0.95 x 460

Total
174 < 804 OK
iii) Design for Shear

Vu = 61.97 x 1.4 = 87 kN

u = 87 x 103
1000 x 286

= 0.30 N/mm2

% As = 100 x 804
286 x 1000

= 0.28

uc = 0.79 x % As 1/3
x 400 1/4
x fcu 1/3

1.25 d 25

= 0.79 x 0.28 1/3


x 400 1/4 x 35 1/3

1.25 286 25

= 0.50 > 0.30 OK

Page 49 of 49

You might also like