Eigenvalue analysis was carried out by considering 3D Mass model to confirm that the vibration
frequnecy of the foundation does not concide with twice the machine vibration frequency
(f=3600rpm)to avoide resonace.
Natural
Natural Frequency
Mode Period
(fn) Remarks Judgement
No (T)
(cps) (rpm) (s)
1st Mode in
1 4.87 292.00 0.205 fn<2880rpm o・k
Longitudinal Dir
First Mode in
2 4.97 298.00 0.201 fn<2880rpm o・k
Transverse Dir.
3 5.49 329.00 0.182
4 6.97 418.00 0.144
5 7.05 423.00 0.142
From the above results it can be seen that first natural frequencies in both axila and
longitudinal direction is less than 80% of machine vibraiton frequency and therefore
the resonance does not occur.
Modal mass and mass participation ratio
Longitudinal
Mode Transvese Direction Vertical Direction
Direction Remarks
No
Mass (%) Sum (%) Mass (%) Sum (%) Mass (%) Sum (%)
1 84.32 84.32 1.63 1.63 0.00 0.00 Longitudinal 1st Mode
2 1.68 86.00 77.12 78.75 0.00 0.00 Transverse 1st Mode
3 0.20 86.20 3.60 82.35 0.00 0.00
4 0.04 86.24 3.63 85.98 0.00 0.00
5 0.15 86.39 0.07 86.05 0.00 0.00