DS0300 (Z)APC alarm: Need reference return DS0300 (T)APC alarm: Need reference return DS0306 (X)APC alarm: Battery voltage 0 DS0306 (Z)APC alarm: Battery voltage 0 DS0306 (T)APC alarm: Battery voltage 0
1. Off – On the machine
2. Bring X and Z axis to machine home position. (X=130mm, Z=to tailstock pin lock) 3. Press off/set key 4. Set parameter enable key 5. Go to parameter 1815 6. Set x axis APZ and z axis APZ to bit 1 7. Set parameter disable key 8. (ON/OFF) the machine. Then Re start 9. Check if the X and Z axis is in reference machine home 10. Reference the X, Z, and C axis 11. Set parameter enable key 12. Go to parameter 1815 13. Check T axis APZ=0 (to enable k0014 bit 6) turret rotation OK 14. Go to MNT the to Keep relay function 15. Go to K0013.0 to K0013.2 then set to bit 1 (Turret reference operation, Turret reference ON) 16. Press spindle override to disengage turret 17. Go to MNT the to Keep relay function 18. Go to K0014.2 then set bit to 1 (turret pin unlock) 19. Go to K0014.6 then set bit to 1 (turret rotation OK) 20. Move the turret assy one rotation then direct it to tool no.1. 21. Go to K0014.2 then set bit to 0 then set K0014.1 to bit 1 (A sound confirming turret pin lock is established) 22. Go to K0013.0 to K0013.2 then set bit 0 23. Go to parameter 1815 24. Set T axis APZ=1 (to stablish the new position) 25. Press off/set key 26. Set parameter disable key 27. Off – On the machine 28. Cycle the turret