Professional Documents
Culture Documents
APARTMENT
Electrical
Revision 01 on 17h march 2009
Subject to change
APARTMENT
Electrical
Revision 01 on 17h march 2009
Subject to change
The Design check list draft by design department in accordance with Phu My Hung’s
design check list (refer to see the below attached)
The blue text is SPCC’s additional part
Table of Contents
1. Exterior 2. Interior
+ General + General
+ Level + Entrance
+ Elevation + Living room
+ Exterior wall + Dinning room
+ Handicap access + Kitchen
+ Arcade + Staircase
+ Flower bed + Corridors
+ Fence + Master bedroom(phòng ngủ có WC)
+ Pavement + Bedroom(ko có WC)
+ Landscape + Storage
+ Resettlement joint + Bathroom
+ Gas tank housing + Loggia
+ A/C balcony
+ Laundry balcony
+ Door
+ Penthouse
+ Maid’s room
+ Roof
+ Basement
3. Public space 4. Shop
+ Entrance lobby + Shop front
+ Elevator lobby + Door
+ Elevator + Interior
+ Escape staircase + Toilet
+ Corridors + Exhaust
+ Terrace + A/C(cục nóng máy lạnh)
+ Roof + Parking
+ Driveway
+ Parking lot
+ Guard house
+ Water tank
+ Transformer room
+ Generator room
+ Others
I. Exterior
Infrastructure: already Electrical Box, PABX, MDF, SCTV cable, speed of
1.
wind and moisture (to calculate IP of lighting and socket),
FAR:
2.
See detail : Vietnam Building Code QCXDVN 01 2008BXD
Building distance
3. Distance to: MV, HV line >= 1.5m (with cover), >= 2.5 (with no cover), Gas
depot >= 100m, Substation >= 3m, ..
No. of floors:
General Lightning: Traditional lightning protection (franklin air terminal) or Modern
4.
lightning protection (Early Streamer emission : ESE); Air – lamp for signal
plane,
All drawing must show: Earthing, MV&HV line, Lightning system,
communication system, Lighting system, Position of Transformer, how about
5.
cable under ground, how about distance between power cable with
communication cable, how about distance between finished floor with cable
Fit with 1/2000:
6. All drawing must show: Earthing, MV&HV line, Lightning system,
communication system, Lighting system, Position of Transformer,
1. Show level of project, protective level, age, …
Level What is Design based on Standard: VIETNAM, IEC, BS EN, NFPA, CIBSE,
2.
NEC, ASHRAE, AS, CP, NF C…
Scope of work, limited design, new design, modify, prepared design,
3.
connecting design, continue design, improve design, destroy design, ….
Elevation 1. Transformer, generator lay on the ground around 10 years no flood
2. Power line system on sky or under ground must safety with person. For
example: cable under ground
Arcade
2.
Flower Bed 1. Lighting for statue, tree, …IP 55 (or water proof)
1. Lighting for road, security, lux = 15cd/m2
Fence 2. CCTV: camera
3. Anti-Theft protection
1. Lighting for road, landscape,
Pavement 2. Lay out to suitable among systems: pipe line, cable, …
3. Manhole:
e. 1 double socket required under stove, at 300mm height from ceiling for
water heater
f. 1 socket required under sink, at 300mm height for water heater
g. 1 socket required above stove, offset 300mm, at 2200mm height for
cooker hood.
h. Hot water supply needed at the sink.
i. If the kitchen is near WC, no need socket for heater.
j. If the kitchen is separated from WC, socket for the water heater need
install on high level (in corner).
2 Lighting: guarantee Lux = 500 cd/m2 for cooking
3 Local Earthing: LEB
Staircase 1 Lighting: for emergency and exit.
1 Lighting: normal, auto control and from control center room
2 Socket: h = 300mm
Horn button: fire alarm bell: for example
Corridors
3
Master
Bedroom
3
1
Loggia
Earthing: less than 1Ohm and connect to the earthing system of whole
2
building. (MEB)
Air-lamp: Aviation obstacle warning lamp, lamps' type is up to professional
3
company, please also follow relative local authority requirements.
4 Lighting for advertisement
1 Lighting: normal and emergency
Basement
2 Socket:
3 Power for motor of fire door
4 Power for Pump
5 Power for Control Panel
6 Power for Utilities
Communication: Tel for emergency, parking lots management system, public
7
alarm…
Fire alarm: if car-motor park or equipment using heat detector, normal use
8
smoke detector.
9 Power for ventilation
III. Public Space