Professional Documents
Culture Documents
net/publication/351029765
CITATIONS READS
0 56
5 authors, including:
Ahmed Al-Durra
Khalifa University
229 PUBLICATIONS 2,990 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Black Powder - Detection and Transportation in Gas Transmission and Distribution Systems View project
All content following this page was uploaded by Mohamed Aboushal on 14 May 2021.
Mohamed M. Zakaria Moustafa and M. A. Aboushal are with the Power & Energy Center, Electrical Engineering and Computer Science
Electrical Engineering Department, Alexandria University, Alexandria, Department, Khalifa University, Abu Dhabi, UAE.
Egypt and Dr. M. Moustafa was a Visiting Scholar at Khalifa University, H. H. Zeineldin is with Electrical Power Engineering Department, Cairo
Abu Dhabi, UAE. University, Giza, Egypt and is currently on leave from Khalifa University,
Tarek H.M. El-Fouly and Ahmed Al-Durra are with the Advanced Abu Dhabi, UAE.
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
2
Analytical lookup
conductance Adaptive method
methods
link voltage regulation, mainly used while operating in a grid Perturb &
Observe Curve fitting Fuzzy logic methods
connected mode (GCM); 2) power sharing, primarily employed
Curve sweep Particle swarm
while operating in an islanded mode (ISM); and 3) active optimization
Constant voltage
synchronization with the main grid.
Constant current
For maximum power point tracking, the control system Fig. 1 classification of maximum power point tracking techniques.
should manipulate the power circuit output impedance till variations are not very common. Therefore, a compromise
matching with the PV internal resistance at the point of between MPPT sampling rate and incremental step voltage
maximum power. For this purpose, many MPPT algorithms should be considered with DC voltage regulation in order to
have been presented for conditioning the control system aiming achieve an optimized performance with minimal oscillations.
the extraction of the maximum power point (MPP) belonged to
the P-V and I-V characteristics of a PV module. This tracking Regarding the second objective related to the power sharing,
should be addressed automatically by the local controller of the droop-based control-methods have been broadly used in voltage
voltage source inverter (VSI) depending on various techniques, control mode (VCM) to support the dual mode of operation for
which can be divided into three major categories [1]–[4], as parallel inverters in micro-grids (MGs). However, this
depicted in Fig. 1. The first category continuously monitors the technique is prone to many disadvantages which can be realized
PV current and/or voltage, thus achieving precise MPPT from multiple perspectives [23]–[25], e.g. design dependency
independently of empirical data related to the PV module on uncertain effective line impedance (EFLI), power sharing
deviations particularly for reactive power due to mismatched
characteristics. The main methods imputable to this category
EFLIs among parallel DGs, poor dynamic response owing to
are the incremental conductance (InC) [5], [6], perturb and
the bandwidth limitation influenced by the dual voltage-current
observe (P&O) [6]–[8], hill climbing (HC) [9], [10], BJT- loop architecture, the lack of adaptability with load variations
Tuned MPPT [11], in addition to optimization and fuzzy logic considering the inertia-less nature of VSIs, and the indirect
(FLC) based techniques [12]–[15]. The second category control of line currents since P-Q are used as the main control
embraces several methods that determine the MPP at different variable resulting in poor power quality. Therefore, to enhance
irradiances and temperatures relying on apriori data belonged power quality, a fast islanding detection (ID) and transient
to the typical I-V curves of the PV array, such as fractional open mitigation strategies are needed for switching over between
circuit voltage (FOCV) [16], fractional short circuit current voltage controlled mode (VCM) and current controlled mode
(FSCC) [4], [17], constant reference voltage (CRV) [18], curve (CCM) subsequent to MG operating mode changes from ISM
fitting [19], look-up tables based method [20], and current to GCM, and vice versa [26]–[28]. Attractively, all these issues
sweep [1], [2]. With the use of these methods, the total number have been obviated through a hybrid scheme reported in [29]
of required voltage and/or current sensors is reduced, but at the which encompasses predictive current estimator to cope with
expense of compromising the tracking accuracy, which is the load variations, robust current droop controller (RCDC) used
main disadvantage of such approach, particularly under for proportional active current sharing, and quasi-proportional
anomalous changes in ambient insolation and temperature. The resonant (QPR) regulator which regulates both the reference
last category contains hybrid methods combining both current signal plus sharing reactive current intrinsically. Thus,
measurements and empirical data [1], [2], [21]. it offers a unified architecture operated in CCM while
supporting dual mode of operation, outstanding robustness
P&O, which is the algorithm adopted in this paper, relies on against load fluctuations, proportional sharing of P-Q output
the voltage to power gradient (dVPV/dPPV) in tracking the MPP. power, and universal droop formula suitable with wide range of
It has been remarked to be better in terms of dynamic response output impedance's angle between – π/2 to π/2. In spite of those
and output voltage regulation at the DC-link [2], [22]. P&O advantages, this method does not guarantee accurate power
algorithm not only has relatively simple control algorithm, but sharing under intermittent input power fed by renewable energy
also offers high tracking precision for the MPP without prior source (RES) like PV arrays. The underlying reason beyond this
knowledge of the mathematical PV model, besides granting shortage is that an idealized DC-link voltage has been assumed,
satisfactory dynamic response. Therefore, P&O has been while pushing all DGs to their maximum power ratings during
widely employed for MPPT using only two set of sensors for GCM, which can be impractical in case input power goes below
measuring the PV current and voltage. However, this method the rated setpoints of the current controlled voltage source
still holds few disadvantages as follows [21]. Firstly, the P&O inverter (CCVSI).
algorithm causes an inherent oscillation in the output of the PV Finally, concerning the active synchronization with the main
system during the tracking process. In addition, the time elapsed grid. The simulation results presented in [29] have relied on
while oscillating around the MPP results in energy waste until synchronous reference frame phase-locked loop (SRF-PLL) to
convergence is achieved. Moreover, the convergence time can detect the frequency in the MG; meanwhile, a simple zero-cross
be further increased under rapidly changing atmospheric detection (ZCD) method has been adopted for the active
conditions leading to higher energy losses; however, such rapid synchronization to clear any phase shift between the inverter
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
3
and the main grid voltages. Then, the per unit values of the Utility
filtered grid voltages, Vgαβ (pu) have been directly used as a Grid
template for the reference currents. However, despite the DG# Filter Io abc Tie Switch
+ +V / Lf
simplicity of ZCD method, its performance is poor under + dc E IL ZLine Iloadabc
Vdc −
abc abc
VPV +V /
transient events like load fluctuations and disturbances at the − dc IC Cf PCC
− − abc ZLoad
point of common coupling (PCC), which may result in high
inrush currents and voltage distortions upon synchronization. DG# Filter Io abc
+ +V /
Instead, phase-locked-loops (PLLs) have been remarked as + dc E IL Lf ZLine Common
Vdc −
abc abc
better synchronization choice over simple ZCD owing to their VPV +V / AC-Bus
− dc IC Cf
stable performance under disturbances and weak grid − − abc
conditions [30]–[32]. Nevertheless, PLLs are inherently Fig. 2 Typical block diagram of the MG under study.
nonlinear, thus necessitating complex design and advanced
tuning methods, which in turn reduces the system dynamic
III. OVERVIEW OF RCDC-QPR SCHEME AND ITS LIMITATIONS
response due to exhaustive computations. In addition, multiple
PLLs utilized in one system tend to compete with each other, The unified controller presented in [29] is comprised of
jeopardizing the system stability [31], [32]. A more attractive predictive current estimator linked with RCDC, and QPR inner
solution has been presented in [33]–[35] exploiting the droop regulator as shown in Fig. 3. This controller can accept any
function to obtain the reference frequency, thus acquiring the current set-point Iset* ranged from zero to Irated provided that an
voltage angle information without using a dedicated PLL. ideal DC-link source is available. Accordingly, Iset* could be
Although these methods bring a PLL-less design, but they still adjusted at the rated current during all times. Hence, the
embrace the other limitations of conventional VCM based inverters are always pushed up to their maximum power rating
droop control, as explained before. during GCM, while sharing the common load proportionally
during ISM. Nonetheless, this unified setting of Iset* cannot
In this paper, new enhancements are presented to enrich the directly be used when the inverter is interfaced to a PV source
control flexibility of the unified RCDC-QPR controller since the DC-link voltage can no longer be maintained. For
introduced in [29]. Following this line of research, the scheme clarity, this effect can be noticed when solar insolation level is
is modified to handle DC-link voltage variations post to PV decreased to a certain level such that the current at the MPP
input power changes, besides fulfilling active synchronization (Imp) is smaller than the specified current set-point, Iset*. This
with the main grid without using PLLs. A flexible operation is mismatch between the input power and the controller settings
thoroughly achieved during both ISM and GCM with the ability leads to a sudden collapse in the DC-link voltage since the
to switch over between these two modes seamlessly through a control set-point cannot be physically met. Thus, the controller
unified CCM. Highlighting the main contributions as follows; tries to increase the output current for tracking Iset*, but at the
1) Proposing a modified RCDC with mitigated resonance by
expense of DC voltage relegation. Recalling that the DC-link
eliminating the predictive current estimator originally
voltage Vdc can be denoted by the equation below [3], [25].
proposed in [29], while maintaining the operation in a
unified CCM with no need of islanding detection (ID) and 2√2 𝑉𝐿𝐿𝑟𝑚𝑠
𝑉𝑑𝑐 = × (1)
transient mitigation strategies witnessed in previous √3 𝑚𝑎
researches.
2) Developing a new simplified MPPT for single stage PV-
Irefpk [n-
E*
]
Irefpk [n]
inverter, which uses only one current sensing element at Vratio
the AC side, obviating the need of additional current Vopk Predictive current
estimator
sensors at the DC-link. In addition, regulating DC-link
voltage without affecting the unified control architecture. E* Robust current
Vopk droop controller
3) A PLL-less self-synchronization mechanism (SSM) is + ke
extended on the unified RCDC instead of VCM based Iset* Iref,mag [n]
droop. In addition, general guidelines are outlined through Iopk + mp + ∫ ++
quantitative analysis for the intrinsic droop characteristics
QPR Controller
of the employed QPR regulator. Hence, an accurate PLL- Iref,mag [n]
less SSM is incorporated supporting both ISM and GCM. ki ωc s Eref
+ kp
s + ωc s+ωPR
II. MICRO-GRID CASE STUDY sin(θv)αβ
ILαβ
The case study considers a low voltage (LV) MG system as
shown in Fig. 2. Two three phase VSIs fed by multi-string PV Fig. 3 Block diagram of combined RCDC-QPR scheme
array are interfaced through an output LC filter and coupling Hence, under the maximum amplitude modulation index
lines with parallel linkage at the PCC. The adopted PV module (ma_max =1) in linear range, the minimum DC-link voltage
parameters are extracted from the Sunpower (SPR-315E-WHT- (Vdc_min) permissible for the operation of VSI is 508.0682 Volt.
D) module data encompassed within the library of Taking a factor of safety (10-20%) into account for considering
MATLAB/Simulink software [36].
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
4
the power and switching losses, then Vdc_min is estimated as 600 IV. MODIFIED CONTROL SCHEME PROPOSED FOR PV
Volt. Consequently, when the DC-link voltage becomes far INTEGRATION
beyond Vdc_min, then a completely deteriorated response may be To incorporate a PV array with the unified CCM, instead of
resulted, leading to entire system instability. Thereby, it can be ideal DC source, the control at the DC-link side is modified
stated that RCDC posed in [29] cannot facilitate the integration comprising two main regulating Iopk and DC-
of multi-string PV inverter in case the current set-point Iset* is
Vdc_ref blocks, namely MPPT
link
VPV voltage controller, as shown in Fig. 7. The MPPT is only
remained fixed, disregarding the DC-link voltage variations. activated D GCM.
during Vdc −
Boost Meanwhile, DCMPPT
*
link Iset is halted Eabc
Hybrid during
IPV MPPT
Converter + controller RCDC-QPR
Another limitation is brought by resonance interactions ISM, as the system operates in power sharing mode, with the
between the inverter's harmonics and MG network impedances. ILαβof load shedding, if needed.
aid
It is found that those resonant harmonics are essentially (a)
stimulated by the predictive current scaling method proposed in Iopk
[29] using feed-forward current multiplier (Vratio). The latter is VPV Vdc_ref DC link Iset
* Eabc
−+
basically oscillatory, adding harmonics distortions to the MPPT
Hybrid
reference signal, as depicted in Fig. 4. Thus, resonance
IPV controller RCDC-QPR
phenomenon is emerged in both the output voltage at the PCC, ILαβ
in addition to output active and active power. This undesired Fig. 7 DC-link voltage regulation of single
(b) stage PV multi string inverter.
effect took place after (2.5 seconds) from simulation run in real
time, as illustrated in Figs. 5 and 6, respectively. A. Design of DC-link voltage controller
This issue is addressed in this paper, where Vratio multiplier Since that VSI is directly coupled to the PV array, then the
has been disabled without influencing the system response, MPPT algorithm continuously changes Vdc_ref in compliance
considering that the RCDC already possesses a branch for with the tracked MPP voltage (Vmpp). Hence, the new Vdc_ref
voltage regulation connected in parallel to the active current determined by the MPPT must be reflected in the magnitude of
droop controller, as shown in Fig. 3. This enables voltage the AC current setpoint Iset* for controlling the exchanged
regulation during islanding without further efforts. power with the main grid. For this reason, a proportional
integral (PI) voltage controller is employed to regulate the
voltage error detected between the operating voltage of the PV
array (VPV) and Vdc_ref, thus Iset* is generated accordingly. In this
sense, the DC-link voltage (Vdc) is always pushed towards Vmpp
without using an intermediate power circuit for MPP extraction
like the case of double stage topology utilizing DC-DC boost
converter [2], [3]. This emphasizes that the DC-link control
structure is remarkably simplified in the case of single stage
topology, as shown in Fig. 7.
For tuning the DC-link control parameters, the following
system model has been designated. Considering a balanced stiff
Fig. 4 Ratio of nominal over output voltage applied for current scaling. grid with fixed frequency 50 Hz at the steady state, i.e. no phase
angle change (Vgq= 0), then the power exported to the main grid
is defined as follows;
3 3
𝑃𝑔𝑟𝑖𝑑 = (𝑉𝑔𝑑 𝐼𝑔𝑑 + 𝑉 ⏟𝑔𝑞 𝐼𝑔𝑞 ) = 𝑉𝑔𝑑 𝐼𝑔𝑑 (2)
2 2
≈0
where Vgd, Vgq, Igd, Igq are the direct and quadrature axes of the
main grid voltage and current, respectively. Hence, the
dissipated power at the DC-link capacitor PCap can be given as;
𝑃𝐶𝑎𝑝 = 𝑃𝑃𝑉 − 𝑃𝑔𝑟𝑖𝑑 (3)
where PPV is the output power of the PV array. Thus,
Fig. 5 The output voltage at the PCC of the MG with resonance effect.
𝐶𝑑𝑐 3
𝑠𝑉𝑑𝑐 × 𝑉𝑑𝑐 = (𝑉𝑑𝑐 𝐼𝑃𝑉 − (𝑉𝑔𝑑 𝐼𝑔𝑑 )) (4)
2 2
1 3 (𝑉𝑔𝑑 𝐼𝑔𝑑 )
𝑉𝑑𝑐 = (𝐼 − ) (5)
𝐶𝑑𝑐 /2 𝑠 𝑃𝑉 2 𝑉𝑑𝑐
From (5), the block diagram shown in Fig. 8 is derived for DC-
link voltage regulation, where Gc_dc (s) is a PI voltage controller
used to compare the DC-link voltage Vdc fed by the PV array
against the reference DC-link voltage Vdc_ref . According to the
voltage error, the magnitude of the AC current set point Iset*
(equivalent to Igd*) is varied as per (6) until the DC-link voltage
Fig. 6 Output powers of DG1,2: (a) active power. (b) reactive power. becomes regulated at the designated Vdc_ref .
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
5
𝑘𝑖𝑑𝑐
𝐼𝑠𝑒𝑡 ∗ = 𝑉𝑑𝑐_𝑒𝑟𝑟 . 𝐺𝑐𝑑𝑐 (𝑠) =× 𝑘𝑝𝑑𝑐 (1 + ) (6) IPV / PPV ILph / PPV Power
𝑠 Current
where kpdc and kidc are the proportional and integral gains of the DC/AC
DC-link controller. Note that Iset* or (Igd*) is calculated
independently of the inverter output impedance or the grid
voltage, as it only changes based on the DC-link voltage error VPV VPV
(i.e., PV power changes). Meanwhile, the power sharing (a) (b)
accuracy is guaranteed through the RCDC-QPR hybrid control. Fig. 9 I-V and P-V characteristic of PV array realized at DC and AC sides. (a)
with DC current measured (b) with AC phase current measured.
Based on the control model depicted in Fig. 8, the PI
coefficients have been tuned using Ziegler–Nichols method. By is fed to the RCDC-QPR controller to manage the power flow
driving the system to oscillatory response, two parameters have accordingly. The indicated simplifications can be inferred from
been captured, namely Kcr and Tcr, which are the critical gain the exhibited flow charts shown in Fig. 10 and 11, respectively
and time period of the oscillatory cycle. Accordingly, the tuned by discriminating the conventional against the proposed
parameters, kpdc and kidc, have been set equal to (0.4×Kcr) and simplified P&O algorithm.
(1.2/Tcr), respectively as will be demonstrated later in Table I.
Start
IPV
Vdc_ref Vdc_err Igd* ICdc Vdc Measure VPV and IPV
− Gc_dc(s) Vgd −+
+
(Cdc/ ) s
Vdc Calculate PPV (n) = IPV (n) .VPV (n)
are those measured at the DC-side, which are normally used for No
MPPT in previous researches. On the other hand, using AC Increase Vdc_ref Decrease Vdc_ref
current measurements, Fig. 9 (b) shows that both curves (ILph
vs. VPV) and (PPV vs. VPV) are linearly related. This emphasizes ILph (n− )= ILph (n)
the feasibility of using the measured AC current (inverter side)
for tracking the MPP directly. In this context, the system Return
monitors only the AC side current, which is already measured Fig. 11 Flow chart of the proposed simplified MPPT using P&O for single stage
across the LC filter inductance as a part of the unified process multi-string PV inverter.
controller. Thus, as long as the measured AC current is
increased, Vdc_ref is perturbed in the same direction by the P&O Furthermore, it is worth to be noticed that, the current
algorithm either by an increase or decrease for tracking MPP. amplitude set-point Iset* readjustment at zero within droop
Hence, the DC-link PI voltage controller alters the magnitude equation is not mandatory upon sudden islanding opposed to
of the inverter's AC current setpoint Iset* till eliminating the conventional VCM based droop methods. This is a unique
voltage error between the perturbed voltage reference (Vdc_ref) feature offered by the proposed RCDC since it can freely accept
and the PV array operating voltage (VPV). In the meantime, Iset* any setpoint value ranged between 0 to Irated during ISM, while
maintaining proportional power sharing among parallel DGs.
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
6
Thus, the last Iset* value determined by the MPPT prior to two functions yield the frequency of inverter's output voltage
islanding can be directly used without affecting the power (fvDG), and time varying frequency change (ΔfvDG), which is set
sharing accuracy. On the contrary, conventional VCM based temporarily until the inverter output current and grid voltage
approaches requires islanding detection to return the current become synchronized. Fig. 12 (a) shows that the intrinsic droop
setpoint to zero when islanding takes place for reformulating characteristics of the inner QPR regulator can be directly
the droop equation. exploited to obtain fvDG. Hence, a PLL-less frequency detector
is attained instead of the conventionally used PLL. Using the
Accordingly, using the proposed MPPT strategy alongside control parameters shown later in Table I, while considering
with single stage- based PV array topology, the following varied reactive loading conditions between (±3.0 kVAr), then
advantages could be attained: the linear fitted curves shown in Fig. 13 yields an approximately
• The proposed method provides a simple yet accurate P&O linear relation between the inverter's output reactive power (Q)
algorithm, reinforcing the flexibility of modified RCDC to and frequency, as defined in (9) for parallel CCVSIs.
integrate with PV systems under all operating conditions. Δ𝑓 Δ𝑓 𝑘𝑝
• Only one AC current sensor is required to sense the output 𝑓𝑣𝐷𝐺 = 𝑓𝑛𝑜𝑚 + × 𝑄, 𝑤ℎ𝑒𝑟𝑒 ≡ (9)
ΔQ ΔQ 𝑘𝑖
for MPPT purpose. This removes the necessity of current The slope of the linearized curve (Δf /ΔQ) represents the
sensing element in the DC-link side, as well as signal frequency boost ratio. Noticeably, the latter is equal to the
conditioning and DC power calculation. proportional gain over the resonant gain (kp/ki) belonged to the
• For three-phase systems, only one sensor of smaller rating inner QPR regulator, as inferred from Fig. 13 (a)-(c). It is found
will be required to measure the phase AC current compared that these gains are responsible for shaping the relation between
to the conventional P&O MPPT method, which needs to Q vs. fvDG. This implies that the gain kp determines the
consider the entire rated power of the VSI in the DC-link. maximum frequency deviation from the nominal value fnom,
• The system is slightly perturbed compared to other preceding whereas ki influences the frequency rate of change
P&O methods as power conditioning delays are removed. In corresponding to reactive load variations. Hence, the lower the
addition, the incremental voltage variations are compromised
ratio kp/ki, the smaller the frequency deviation is resulted.
with MPPT sampling rate for minimized oscillations.
Additionally, the slope of the linearized curve is always equally
• It is also worth noting that under homogeneous irradiance
matched to the ratio kp/ki, as depicted in Fig. 13. Therefore, this
conditions, the single stage PV-inverter topology proposed
herein is preferred in most industries, as it is more efficient ratio can be directly used as the frequency boost ratio, thus;
𝑘𝑝
and economical compared with double stage topology [1], 𝑓𝑣𝐷𝐺 = 𝑓𝑛𝑜𝑚 + ( ) (−𝐸 ∗ 𝐼𝑜𝑞 ) (10)
[2]. In this case, a suitable number of PV strings has to be 𝑘𝑖
connected in series respecting the minimum design value for where, Vod, Voq are the direct and quadrature axes of the output
DC-link voltage; meanwhile, parallel PV strings are fnom
fvDG
designated accordingly based on the desired power level. ωvDG
−Ioq kp / ki E* π
• The droop equation formula can be kept unchanged upon fboost (ωvDG)t ≡ (θv)
ILαβ ∫
αβ θv
switching between different mode in the MG as the proposed dq
PLL-less frequency detector
RCDC accepts different current set-point Iset* during ISM (a)
ranged from 0 to Irated, while still being capable to share the (lag/lead) sign
load proportionally among parallel inverters. This δ(t) (ΔfvDG)t ΔfvDG ΔfvDG
(rad)
++ / π d/dt
advantageous feature does not necessitate current set-point . .
Iset* manipulations post to islanding, which in turn eliminates θv S
+ sin ≥
− Trigger signal
the respective needs of ID as well as the undesired transients Vgβ θg
imposed during switching events. Vgα Tan-
SSM with the main grid
(b)
V. AN IMPROVED SELF SYNCHRONIZATION STRATEGY FOR Fig. 12 Active self-synchronization. (a) PLL-less frequency detector. (b) SSM
THE INTEGRATION WITH THE GRID with the main grid.
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
7
voltage. Noting that Voq equals zero when the frequency is information, e.g. output frequency fvDG and voltage phase angle
maintained at the steady state. Ioq is the quadrature axis current θv can be easily obtained from the measured output reactive
intrinsically controlled by the QPR regular. E* is the nominal power depending on the intrinsic droop attributes of QPR
voltage magnitude substituting Vod since that the voltage is regulator. Note that this concept has been discussed in earlier
firmly regulated by the RCDC at the nominal value. In this publications given for conventional VCM based droop
essence, the quantitative analysis described above gives basic techniques [33], [34], but it has not been studied yet before with
guidelines for tuning the response of the PLL-less detector resonant controllers taking advantage of their associated
using the inner QPR regulator. Hence, the reference current inherent droop characteristics. Therefore, the relation given by
angle can be made in phase with inverter's output voltage, while (10) is newly introduced in to obviate the normally used PLLs.
controlling the reactive droop characteristics and maximum Note that FFRES is also an essential part of this approach since
frequency deviations. Upon transition to grid connected mode, that frequency is always changeable by the QPR regulator upon
the voltage angle is not mandatorily matched with that of the any reactive load variations [29], [37].
main grid as per the phasor diagram exhibited in Fig 14. As fnom
shown, a transformation from αβ stationary frame (αβ-STF) to
PI controller
dq synchronous reference frame (dq-SRF) is implemented to fvDG + + fPR(t)
evaluate the phase shift angle δ between the inverter and the −+ kpr ++
+
main grid's voltages, as per (11). ΔfvDG
kir ∫ dt
𝛿 = 𝜔𝑣𝐷𝐺 𝑡 − 𝜔𝑛𝑜𝑚 𝑡 (11)
where, ωvDG and ωnom are the inverter's output and nominal Fig. 15 Frequency restoration block embedded with the proposed SSM.
angular frequencies. Considering that, θg can be derived using
the arctangent function denoted in (12) VI. OVERALL CONTROL SCHEME AND REAL TIME
SIMULATION RESULTS
𝜃𝑔 = 𝑡𝑎𝑛−1 (𝑉𝑔𝛽 /𝑉𝑔𝛼 ) (12)
And, The overall control scheme, including the improved RCDC,
𝜔𝑛𝑜𝑚 𝑡 = 𝜃𝑔 + 90 (13) the simplified MPPT, and the accurate PLL-less SSM, is
From (12) and (13), (11) can be rewritten as follows; presented in Fig. 17. System performance has been validated
𝛿 = 𝜔𝑣𝐷𝐺 𝑡 − 𝜃𝑔 − 90 (14) using real time simulation (RTS) during both ISM and GCM
Voβ Vgβ with random switching between these two modes. Two PV
Vgq
arrays rated as (15 kW) and (7.5 kW) at STC have been
Vg Vgd
assigned as the main source of DG1 and DG2, while feeding two
ωnomt parallel CCVSI with maximum ratings equal to 20 kVA and 10
Voα kVA, respectively. A fixed time step solver has been employed
θg
-Vgα θg− for RTS with a sampling rate (fs =10 kHz). Hence, the
Vgα
θg−
incremental step voltage of the MPPT has been relegated to
(Vstep=0. 00025) in compromise with the RTS sampling rate to
avoid large perturbations in the system output. The other
-Vgq network and control system parameters have been calculated
Fig. 14 Phasor diagram of the grid voltage transformation from αβ-STF to dq- based on the tuning guidelines outlined in [29], [37], as listed
SRF. in Table I. Note that each PV array consists of a specific number
of parallel and series strings as indicated in Table II. All those
Accordingly, the angle δ must be nullified at the steady state parameters are employed together for executing the real-time
in order to achieve synchronism, which sets out the following simulation scenarios which are illustrated in Table III. The
condition given in (15) [37]. implemented RTS adopts the model in the loop prototype,
𝜔𝑣𝐷𝐺 𝑡 − 𝜃𝑔 = 90
{ (15) where both the plant model and the designed controller are
𝑠𝑖𝑛(𝜔𝑣𝐷𝐺 𝑡 − 𝑡𝑎𝑛−1 (𝑉𝑔𝛽 /𝑉𝑔𝛼 )) = 1.0 testified using RTS. The hardware used in the simulation is
dSPACE MicroLabBox. In addition, a graphical user interface
To meet the condition of (15) , the approach shown in Fig. 12 (GUI) has been created using ControlDesk software that is
(b) is implemented to eliminate the phase error by embedding a installed on a host PC. This GUI is used to set and modify the
time varying frequency change (ΔfvDG) to the inverter for active MG operating mode and PV climatic conditions by the user
synchronization with the main grid. For this purpose, a fast during simulation run in real time, while exporting the feedback
frequency restoration loop (FFRES) loop is implemented as results to an external Digital Storage Oscilloscope (DSO)
depicted in Fig. 15. During ISM, it restores the frequency fvDG through the real time simulator output ports. The general layout
to its nominal value upon any reactive load changes caused by of the RTS laboratory mounting that has been established as
the reactive boost droop of the QPR regulator. Meanwhile, it depicted in Fig. 16.
activates a gradual change ΔfvDG, upon transition to GCM. The As delineated in Table III, the simulation scenario
parameter ΔfvDG remains activated until meeting the commences with the inverters' operation in ISM. Two parallel
synchronization condition defined in (15), then it becomes PV-inverters proportionally share the common loads as
nullified as indicated in Fig. 12 (b). Accordingly, the necessary indicated before in Fig. 2. It is preliminary assumed that the PV-
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
8
TABLE III
THE SIMULATION SCENARIO APPLIED ON THE CASE STUDY.
Common MPP of
Simulation MG Insolation Temp.
Loads DG1,2
time (s) Mode (W/m2) (° C)
(kVA) (kW)
0.0 –2.0 1000 25 6.0+2.0j No
2.0 –4.0 ISM 1000 25 12.0+4.0j tracking
4.0 –8.0 1000 25 0.0 15.12/7.53
8.0 –12.0 GCM 300 25 12.0+4.0j 4.43/2.21
12.0 –16.0 800 30 6.0+2.0j 11.63/5.9
No
16.0 –20.0 ISM 800 30 12.0+4.0j
tracking
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
9
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
10
Fig. 23 Output peak currents proportionally shared between DG1 and DG2.
Fig. 24 Measured direct and quadrature axes voltages at the PCC. Fig. 25 The output phase voltage at the PCC with the main grid is shifted by:
(a) 120° (b) −90°, under the control of PLL-less SSM.
the system. This proves that PCC output voltages have been
maintained with less 5% from the nominal voltage values in In order to explore additional verifications on the control
efficacy and robustness under rapidly changed insolation and
compliance with IEEE 519 emphasizing the robust voltage
temperature levels with wide variations, a more stringent
regulation supported by the proposed controller. Likewise, the
simulation scenario in GCM has been followed, as envisaged
output peak currents of the two parallel inverters illustrated in
through Table IV and Fig. 26, while assuming the
Fig. 23 are completely matched with the reference AC current interconnected common loads are (6+2j kVA). From the RTS
set point which have been identified by the MPPT algorithm as results shown in Fig. 27, the proposed simplified P&O
depicted before in Fig. 20. No considerable overshoots exist algorithm has precisely tracked the MPP of both PV arrays
upon various condition, e.g. transient load variations either rated (15 kW) and (7.5 kW), respectively, in matching with the
during ISM or GCM, the climatic weather changes including reference values outlined in Table IV. This emphasizes that the
insolation and temperature changes, and switching events of the tracking accuracy has not been compromised even under
MG operating mode. This highlights the superiority of the stringent insolation temperature changes plus keeping tenuous
unified current control architecture to guarantee seamless perturbations. The DC-link voltage Vdc has been also
operation in the MG under miscellaneous transient conditions. maintained as illustrated in Fig. 28 showing that the proposed
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
11
VIII. REFERENCES
[1] A. K. Podder, N. K. Roy, and H. R. Pota, “MPPT methods for solar PV
systems: a critical review based on tracking nature,” IET Renewable
Power Generation, vol. 13, no. 10, pp. 1615–1632, 2019.
[2] R. Ahmad, A. F. Murtaza, and H. A. Sher, “Power tracking techniques
Fig. 28 DC-link voltage under stringent insolation temperature changes. for efficient operation of photovoltaic array in solar applications–A
review,” Renewable and Sustainable Energy Reviews, vol. 101, pp. 82–
102, 2019.
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
12
[3] M. M. Hanif, “Investigation to Improve the Control and Operation of a [21] K. Yan, Y. Du, and Z. Ren, “MPPT Perturbation Optimization of
Three-phase Photovoltaic Grid-tie Inverter,” PhD Thesis, Dublin Photovoltaic Power Systems Based on Solar Irradiance Data
Institute of Technology, 2011. Classification,” IEEE Transactions on Sustainable Energy, vol. 10, no.
[4] H. Bounechba, A. Bouzid, H. Snani, and A. Lashab, “Real time 2, pp. 514–521, Apr. 2019, doi: 10.1109/TSTE.2018.2834415.
simulation of MPPT algorithms for PV energy system,” International [22] M. Killi and S. Samanta, “Modified Perturb and Observe MPPT
Journal of Electrical Power & Energy Systems, vol. 83, pp. 67–78, Algorithm for Drift Avoidance in Photovoltaic Systems,” IEEE Trans.
2016. Ind. Electron., vol. 62, no. 9, pp. 5549–5559, Sep. 2015, doi:
[5] D. C. Huynh and M. W. Dunnigan, “Development and Comparison of 10.1109/TIE.2015.2407854.
an Improved Incremental Conductance Algorithm for Tracking the [23] Y. Han, H. Li, P. Shen, E. A. A. Coelho, and J. M. Guerrero, “Review
MPP of a Solar PV Panel,” IEEE Trans. Sustain. Energy, vol. 7, no. 4, of active and reactive power sharing strategies in hierarchical controlled
pp. 1421–1429, Oct. 2016, doi: 10.1109/TSTE.2016.2556678. microgrids,” IEEE Transactions on Power Electronics, vol. 32, no. 3,
[6] X. Li, H. Wen, Y. Hu, Y. Du, and Y. Yang, “A Comparative Study on pp. 2427–2451, 2017.
Photovoltaic MPPT Algorithms under EN50530 Dynamic Test [24] Q.-C. Zhong and Y. Zeng, “Universal Droop Control of Inverters With
Procedure,” IEEE Transactions on Power Electronics, pp. 1–1, 2020, Different Types of Output Impedance.,” IEEE Access, vol. 4, pp. 702–
doi: 10.1109/TPEL.2020.3024211. 712, 2016.
[7] X. Zhang, D. Gamage, B. Wang, and A. Ukil, “Hybrid Maximum [25] Y. Zeng, “Droop Control of Parallel-Operated Inverters,” PhD Thesis,
Power Point Tracking Method Based on Iterative Learning Control and University of Sheffield, 2016.
Perturb Observe Method,” IEEE Transactions on Sustainable Energy, [26] G. G. Talapur, H. Suryawanshi, L. Xu, and A. Shitole, “A Reliable
pp. 1–1, 2020, doi: 10.1109/TSTE.2020.3015255. Micro-grid with Seamless Transition between Grid Connected and
[8] T. N. Gupta, B. Singh, and S. B. Q. NAQVI, “Performance Evaluation Islanded Mode for Residential Community with Enhanced Power
of Single-Phase PV-BES Based Microgrid with Seamless Transition Quality,” IEEE Transactions on Industry Applications, 2018.
Capability,” IEEE Transactions on Industrial Electronics, pp. 1–1, [27] K.-R. Kim, C.-Y. Oh, T.-J. Kim, J.-P. Lee, and H.-J. Kim,
2020, doi: 10.1109/TIE.2020.3016256. “Implementation of a Smart Power Conditioning System for Energy
[9] W. Zhu, L. Shang, P. Li, and H. Guo, “Modified hill climbing MPPT Storage System with a Novel Seamless Transfer Strategy,” Energies,
algorithm with reduced steady-state oscillation and improved tracking vol. 11, no. 5, p. 1108, 2018.
efficiency,” The Journal of Engineering, vol. 2018, no. 17, pp. 1878– [28] X. Hou et al., “Distributed Hierarchical Control of AC Microgrid
1883, 2018, doi: 10.1049/joe.2018.8337. Operating in Grid-Connected, Islanded and Their Transition Modes,”
[10] N. Kumar, B. Singh, and B. K. Panigrahi, “PNKLMF-Based Neural IEEE Access, vol. 6, pp. 77388–77401, 2018.
Network Control and Learning-Based HC MPPT Technique for [29] M. A. Aboushal and M. M. Z. Moustafa, “A new unified control
Multiobjective Grid Integrated Solar PV Based Distributed Generating strategy for inverter-based micro-grid using hybrid droop scheme,”
System,” IEEE Transactions on Industrial Informatics, vol. 15, no. 6, Alexandria Engineering Journal, vol. 58, no. 4, pp. 1229–1245, Dec.
pp. 3732–3742, Jun. 2019, doi: 10.1109/TII.2019.2901516. 2019, doi: 10.1016/j.aej.2019.10.006.
[11] M. Al-Soeidat, D. D.-C. Lu, and J. Zhu, “An analog BJT-tuned [30] S. Golestan, J. M. Guerrero, and J. C. Vasquez, “Three-Phase PLLs: A
maximum power point tracking technique for PV systems,” IEEE Review of Recent Advances,” IEEE Transactions on Power
Transactions on Circuits and Systems II: Express Briefs, vol. 66, no. 4, Electronics, vol. 32, no. 3, pp. 1894–1907, Mar. 2017, doi:
pp. 637–641, 2018. 10.1109/TPEL.2016.2565642.
[12] M. Zolfaghari, S. H. Hosseinian, S. H. Fathi, M. Abedi, and G. B. [31] Z. Ali, N. Christofides, L. Hadjidemetriou, E. Kyriakides, Y. Yang, and
Gharehpetian, “A New Power Management Scheme for Parallel- F. Blaabjerg, “Three-phase phase-locked loop synchronization
Connected PV Systems in Microgrids,” IEEE Trans. Sustain. Energy, algorithms for grid-connected renewable energy systems: A review,”
vol. 9, no. 4, pp. 1605–1617, Oct. 2018, doi: Renewable and Sustainable Energy Reviews, vol. 90, pp. 434–452, Jul.
10.1109/TSTE.2018.2799972. 2018, doi: 10.1016/j.rser.2018.03.086.
[13] B. Guo et al., “Optimization Design and Control of Single-Stage [32] F. Blaabjerg, Control of power electronic converters and systems, vol.
Single-Phase PV Inverters for MPPT Improvement,” IEEE 2. Academic Press, 2018.
Transactions on Power Electronics, vol. 35, no. 12, pp. 13000–13016, [33] Q.-C. Zhong and D. Boroyevich, “Structural resemblance between
Dec. 2020, doi: 10.1109/TPEL.2020.2990923. droop controllers and phase-locked loops,” IEEE Access, vol. 4, pp.
[14] N. Kumar, B. Singh, and B. K. Panigrahi, “LLMLF-Based Control 5733–5741, 2016.
Approach and LPO MPPT Technique for Improving Performance of a [34] J. He, Y. W. Li, and F. Blaabjerg, “Flexible microgrid power quality
Multifunctional Three-Phase Two-Stage Grid Integrated PV System,” enhancement using adaptive hybrid voltage and current controller,”
IEEE Transactions on Sustainable Energy, vol. 11, no. 1, pp. 371–380, IEEE Transactions on Industrial Electronics, vol. 61, no. 6, pp. 2784–
Jan. 2020, doi: 10.1109/TSTE.2019.2891558. 2794, 2014.
[15] S. K. G, S. Kinattingal, S. P. Simon, and P. S. R. Nayak, “MPPT in PV [35] Q.-C. Zhong, W.-L. Ming, and Y. Zeng, “Self-Synchronized Universal
systems using ant colony optimisation with dwindling population,” IET Droop Controller.,” IEEE Access, vol. 4, pp. 7145–7153, 2016.
Renewable Power Generation, vol. 14, no. 7, pp. 1105–1112, 2020, doi: [36] N. Blair et al., “System advisor model, sam 2014.1. 14: General
10.1049/iet-rpg.2019.0875. description,” National Renewable Energy Lab.(NREL), Golden, CO
[16] T.-W. Hsu, H.-H. Wu, D.-L. Tsai, and C.-L. Wei, “Photovoltaic Energy (United States), 2014.
Harvester With Fractional Open-Circuit Voltage Based Maximum [37] M. A. Aboushal, M. M. Z. Moustafa, and M. A. El-Gammal, “A New
Power Point Tracking Circuit,” IEEE Trans. Circuits Syst. II, vol. 66, Self-Synchronized Strategy for Grid-Connected Three Phase Voltage
no. 2, pp. 257–261, Feb. 2019, doi: 10.1109/TCSII.2018.2838672. Source Inverters,” in 2019 IEEE PES Asia-Pacific Power and Energy
[17] H. A. Sher, K. E. Addoweesh, and K. Al-Haddad, “An Efficient and Engineering Conference (APPEEC), Macao, Macao, Dec. 2019, pp. 1–
Cost-Effective Hybrid MPPT Method for a Photovoltaic Flyback 6, doi: 10.1109/APPEEC45492.2019.8994704.
Microinverter,” IEEE Transactions on Sustainable Energy, vol. 9, no.
3, pp. 1137–1144, Jul. 2018, doi: 10.1109/TSTE.2017.2771439.
[18] M. Lasheen, A. K. A. Rahman, M. Abdel-Salam, and S. Ookawara,
Mohamed M. Z. Moustafa (S’06-M’13)
“Adaptive reference voltage-based MPPT technique for PV received the B.Sc. and M.Sc. degrees in
applications,” IET Renewable Power Generation, vol. 11, no. 5, pp. electrical engineering from Alexandria
715–722, 2017. University, Egypt in 2001 and 2004,
[19] X. Li, H. Wen, Y. Zhu, L. Jiang, Y. Hu, and W. Xiao, “A Novel
Sensorless Photovoltaic Power Reserve Control With Simple Real-
respectively, and the Ph.D. degree in
Time MPP Estimation,” IEEE Trans. Power Electron., vol. 34, no. 8, electrical engineering from University of
pp. 7521–7531, Aug. 2019, doi: 10.1109/TPEL.2018.2880461. Manitoba, Canada in 2012. He was with
[20] S. Ozturk and I. Cadirci, “A Generalized and Flexible Control Scheme OPAL-RT Technologies and RTDS
for Photovoltaic Grid-Tie Microinverters,” IEEE Trans. on Ind.
Applicat., vol. 54, no. 1, pp. 505–516, Jan. 2018, doi:
Technologies Inc. in Canada. He is currently an Associate
10.1109/TIA.2017.2753175. Professor at the Electrical Engineering department, Alexandria
University, Egypt. His research interests include smart grids,
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2021.3074248, IEEE
Transactions on Sustainable Energy
13
renewable energy systems, HVDC and power electronics H. H. Zeineldin (M’06–SM’13) received
applications in power systems. He is a Registered Professional the B.Sc. and M.Sc. degrees in electrical
Engineer in the Province of Manitoba, Canada. engineering from Cairo University, Giza,
Egypt, in 1999 and 2002, respectively,
Mohamed Aboushal received the B.Sc. and the Ph.D. degree in electrical and
and M.Sc. degrees in electrical engineering computer engineering from the University
from Alexandria University, Egypt in 2007 of Waterloo, Waterloo, ON, Canada, in
and 2012, respectively, and the Ph.D. 2006. He was with Smith and Andersen
degree from Alexandria University, Egypt Electrical Engineering, Inc., North York, ON, USA, where he
in 2020 in the field of parallel operation of was involved in projects involving distribution system designs,
distributed generators and related control protection, and distributed generation. He was a Visiting
strategies. Since 2013, he worked at the Professor with the Massachusetts Institute of Technology,
company of Middle East Oil Refinery Cambridge, MA, USA. He is currently with the Faculty of
(MIDOR co), Alexandria, Egypt. He is currently a section head Engineering, Cairo University, Egypt. His current research
at the electrical and automation department. His research interests include distribution system protection, distributed
interests include power system analysis, power quality, control generation, and micro grids. He is currently an Editor for the
strategies for micro-grid operation, and smart grids. IEEE Transactions on Energy Conversion.
1949-3029 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSTIY OF ALEXANDRIA. Downloaded on May 13,2021 at 14:51:23 UTC from IEEE Xplore. Restrictions apply.
View publication stats