You are on page 1of 11

0

0
73
Powder and Bulk Engineering, October 1996 37 v

0
cn
0
L
E
-.
cn
s
Analyzing design problemswith your -0
0

baghouse dust collection system d


Q
%
P,
3
Garren E. Tooker Air Control Science Q

rn
3
But nothing could be further from the truth! A properly
engineered, fabricated, and installed dust collection sys-
Can you spot and fix design problems that are af- tem requires very little maintenance and will operate 10
fecting your dust collection system’s performance? years after installation as reliably as it did at startup. [Edi-
Based on over 30 years experience in diagnosing tor’s note: For basics on dust collection system com-
and correctingdust collection system problems, this ponents and operation, see the articles listed under
article’s author estimates that up to 90 percent of “Suggested reading” at the end of this article.]
such systemsinstalled in the US don’t perform toex-
pectations. Up to 80 percent of these problems occur
in ducting and pickup hoods, and the other 20 per- How to make preliminary checks and measurements
cent:are related to equipment design capacity or se-
lection, or both.
Y ou can usually pinpoint dust collection system
problems by first making some simple checks
and measurements. Start by taking some differen-
tial pressure (also called pressure drop or Ap) readings,
which measure the difference between static pressures
In this article, the author presents tips for analyzing
upstream (on the dirty side) and downstream (on the clean
design problems with your baghouse dust collec-
side) of the bags.
tion system. (The information concentrates on sys-
tems that control fugitive dust from enclosed bulk
material handling operations and operate at ambi- If your baghouse has a permanently mounted differential
ent temperatures.) Sections discuss how to make pressure gauge that’s piped across the tubesheet (that is,
the bags), first make sure the gauge isn’t plugged with
preliminary checks and measurements and how to dust by disconnecting the fittings and blowing through
analyze ducting and baghouse problems, with de- the tubing. Then take the readings.
tailed information on sources of some specific bag-
house problems. The final section explains how to
If you have a typical baghouse and the Ap reading is much
avoid design problems by using a systemsengineer- higher than 4 to 6 inches water gauge from the baghouse’s
ing approach. inlet to the outlet or is much higher than 2 to 4 inches
water gauge across the tubesheet, look for partially
blinded bags. One test is to inspect each bag’s clean side.
If it’s coated with dust, the bag is probably partially

T
he first sign of a poorly performing dust collection blinded. But partial blinding can be hard to spot visually,
system is usually an unacceptable level of dust in and you may have to send the bags to a lab for permeabil-
your workplace. If a newly installed system has an ity flow tests. The tests analyze the airflow through a unit
improperly selected collection air volume, the poor per- of filter area to determine whether the fabric is partially
formance shows up immediately. But evidence of other blinded.
design problems often doesn’t show up for weeks or even
months.
If your readings indicate the Ap is normal or low but the
static pressure reading on the baghouse housing has a
Plant staff often assume such long-term problems are nor- high negative value, the ducting is probably partially
mal and that fixing them is a typical maintenance task. plugged.
0
0
38 Powder and Bulk Engineering, October 1996 73
2.
ra
If your baghouse doesn’t have a permanently mounted 5
d

pressure gauge, use a hand-held manometer to take a sta-


tic pressure reading at the baghouse inlet. A high negative 0
cn
reading can mean the ducting is plugged; a low reading 0
can mean the baghouse is plugged. However, this prelimi- 77
nary information may not be conclusive. For instance, a
poorly performing baghouse can cause the ducting to
plug with dust. And poorly performing ducting can cause
baghouse operating problems. So do a thorough investi-
gation before jumping to a conclusion based on a simple -0
0
field check. d
Q
%
And if your system is shut down because both the ducting P,
3
and baghouse are completely plugged, you can’t take Ap Q
or static pressure readings. In this case, bad ducting de- m
sign and poor equipment selection are almost certainly r_
7i
the culprits.

How to analyze ducting problems

I
mproperly designed, fabricated, and installed ducting
that becomes plugged is the source of most dust col-
lection system performance problems and mainte-
nance costs. Designing the system for natural airflow
distribution can prevent plugging. But because this de-
sign method generally requires using a computer, many
designers instead rely on blast gates (throttling devices
with a flat plate that slides across the duct) to achieve bal-
anced airflow.

The result? With a system that has only a marginally cor-


rect collection air volume and barely adequate pickup
hood placement, an operator can be tempted to tamper
with the airflow distribution by taking a hammer to the
blast gates. Such tampering without using flow-measur-
ing instruments or referring to the original airflow distrib-
ution design usually results in plugging because the
tampering reduces air velocity in the ducting. As the fan
begins to climb its pressure-volume characteristiccurve,
because of flow restriction, airflow redistributes itself
through the ducting and spreads plugging throughout the
system.

To look for plugging, tap horizontal ducting runs and the


baghouse’s dust hopper. A dull thud suggests the ducting
or hopper is partially plugged. As you keep tapping the
ducting throughout the system to find plugging, look for
its cause. Potential causes are the ducting layout; butter-
fly dampers; multiple ducting entries; undersized, poorly
located pickup hoods; lack of thermal insulation;and low
air volume.

Ducting layout. If the ducting layout doesn’t comply with


generally accepted, published criteria (such as that in the
latest edition of Industrial Ventilation:A Manual of Rec-
ommended Practice’), here are some of the problems
you’ll find:
o
0
40 Powder and Bulk Engineering, October 1996 73
2.
ra
Branch ducting that enters the main ducting run 5. bot- designing the hoods to reduce dust loading can be cost-ef- 5
d
tom. The ducting has no place for the fallout dust (large fective solutions.
particles not entrained in the airflow) to go. o
cn
o
Lack of thermal insulation. In a cold climate, watch for -0
Blast gates that are throttled way down and located in a ducting without thermal insulation that emerges from a S

horizontal ducting run. E


-.
heated space. In any climate, look for uninsulated ducting cn
that runs from process equipment or for a product that hu- s
Long inclined ducting runs that, again, have no place midifies the air flowing inside the dust collection system. ca3
for thefalZout dust to go. Vertical and horizontal runs are Mixed with dust, the condensate gradually reduces the -0
ducting’s working diameter until the fan can no longer 0
best; if you must use inclined ducting, keep the airveloc- d
ity high to reduce dust fallout and rollback. pump air through it. [Editor’s note: Find more informa- Q
tion on using thermal insulation in the later section, “Con- %
P,
densation problems.”] 3
Q
Elbows with a short radius. The elbow’s centerline ra-
dius should be at least 1%the elbow’s diameter and 2%
m
Low air volume. Check that the system’s collection air r_
diameters if possible. 7i
volume matches the design volume. Often the actual air rn
volume is less than the design volume because of features 3
built into the system that degrade its performance.A com- E.
Branch ducting that enters at an angle greater than 45 3
(D
degrees, enters at an elbow, or doesn’t use an expanding mon design flaw is a poor ducting entry into a centrifugal
transition, or multiple branch ducting entries into the fan. A poor fan entry can reduce the ducting’s volumetric 2.
3
same transition piece. capacity by as much as 15 percent, which requires a ra
nearly 40 percent increase in static pressure rating to com-
pensate for this loss. Such problems often go undetected
Ducting sections that are rectangulal; flat, and wide. because airflow through the system isn’t confirmed at in-
Keep ducting round if possible; if you must use rectan- stallation. An especially poor fan entry that’s often used
gular ducting, make it as nearly square as possible. to save space is a mitered inlet box connected to a cen-
trifugal fan without turning vanes; such a box really kills
Butterfly dampers. Using butterfly dampers for control- fan performance. If the reduced air volume remains unde-
ling air volume and system balancing with dust loadings tected the ducting will continue to plug. To prevent this
greater than 3 grains per cubic foot can cause the dust to problem, either speed up the fan, use a bigger fan, or in-
fall out of the airstream because the damper’s valve plate stall a fan that uses turning vanes.
and shaft partially obstruct the ducting. Instead, locate a
blast gate in a vertical ducting run immediately upstream
of the pickup hood for such an application. How to analyze baghouse problems

A
properly specified and selected baghouse will
Multiple ducting entries. It’s nearly impossible to bal- typically require little maintenance and offer high
ance airflow in a system that has multiple ducting entries availability (that is, won’t require excessive
into the baghouse housing. Almost always, one of the downtime or off-line time for service or cleaning). But if
ducting branches is plugged. To avoid problems, use only your baghouse has problems, you’ll notice symptoms like
one ducting entry into the housing. these:

Excessive stack emissions.


Undersized, poorly located pickup hoods. If a pickup
hood is undersized and located near a source of dust-gen-
erating turbulence (such as a transfer chute’s end, a vibrat- High or unstable Ap.
ing screen’s surface, or a bucket elevator’s discharge),’
the resulting dust loading can be more than the system is
designed to handle. You can frequently detect heavy dust Dust buildup or hangup in the baghouse.
loading by observing the dust collector’s operation. For
instance, a high but stable Ap across the baghouse or a Bag blinding.
rapid pulse-cleaning cycle can indicate excessive dust
loading. If your bag life is short or your system can’t meet
stack emissions requirements because of excessive bag Premature bag failure.
cleaning, moving some pickup hood locations and re-
0
0
42 Powder and Bulk Engineering, October 1996 73
2.
ra
Underlying the symptoms are these common baghouse ably. The ratio also expresses the dust-laden air’s face ve- 5
d
problems: locity as the air approaches the filter media surface.
0
cn
The A/C ratio is the baghouse’s primary cost factor: 0
The baghouse capacity is undersized for your applica- -0
tion, so a high air-to-cloth (A/C) ratio causes an unstable When all other factors are constant, the A/C ratio deter- S
mines the baghouse size. Doubling the allowable A/C E
-.
AP. ratio will cut the baghouse’s cost roughly in half. If your cn
s
baghouse performs poorly, check the filter media type 3
The baghouse housing is undersized for your applica- and its A/C ratio. If the ratio is too high for the media ca
tion, so a high can velocity re-entrains dust on the bags. -0
type, the system’s long-term operating stability will be 0
impaired.
d
Q
The bag cleaning air supply is unreliable and under- %
P,
cleans or allows partial blinding of the bags. Finding an acceptableA/C ratio. But how do you deter- 3
Q
mine an acceptable A/Cratio? So many factors contribute
to selecting the correct ratio that you must establish the m
Your bag cleaning method overcleans the bags or pro- r_
selection criteria very carefully. While no simple, fixed 7i
duces excessive stack emissions. rules apply, you can start by comparing your application rn
3
with successfully operating baghouses that handle the E.
same dust. For instance, about 6-to-1 is a reasonable A/C 3
Improperly selected bag media is shortening the bag life (D
ratio for a pulse-cleaning baghouse with felted media in a 2.
and producing an unstable Ap.
material handling operation for a dry, nonsticky dust, 3
ra
such as coal dust. If your application is similar and your
An improperly designed inlet air diffuser is causing high ratio is less than 7-to-1, look elsewhere for the problem.
internal air recirculation,premature bag failure, and an But if the ratio is greater than 8-to-1, it could be causing
unstable Ap. dust to migrate through and partially blind the bags.

Condensation runs from the baghouse walls and mixes Use caution when finding the right A/C ratio for your
with dust in the hopper, causing hopper buildup and baghouse. Be sure you have information on and compare
hangup. all the operating factors. If you have any doubt, it can be
well worth the cost -typically $7,500 to $10,000 -to
have a qualified lab (such as that of an environmentalcon-
The dust hopper’s shape prevents smooth dust discharge. sultant) test your dust in different baghouse designs and
sizes while varying A/C ratios, media types, and other op-
erating factors.
Your dust return equipment is undersized, causing dust
buildup and hangup in the dust hopper.
A/Cratioproblems. The effects of a high A/C ratio can be
insidious, taking weeks or months to show up. The first
Your untreated collected dust is returned within the bag- symptom is typically “Ap creep” - a gradually increas-
house’s collection perimeter (that is, the area in which ing pressure drop as dust begins to migrate through the
the system picks up dust-laden air), recycling large vol- bag media, partially blinding the bags. This is followed by
umes of dust. reduced airflow, which causes increasing amounts of dust
to be released in the workplace.
Although the source of each problem can interact with
other sources,let’s discuss the problems separately. The Ap creep can also be followed by visible stack emis-
sions as dust migrates from the dirty to the clean side of
the bags. While these emissions may start as a barely visi-
Capacity problems ble puff as the bags are pulse-cleaned (to be discussed
A baghouse’s design capacity is established by its A/C later in this article), the emissions eventually become
ratio -that is, for a given air volume that passes through steady and very visible as dust migration progresses.
the baghouse, a certain minimum filter media area is re- Such “bleed-through” emissions can also be from broken
quired to ensure the baghouse runs continuously and reli- bags that result from the ap creep-
0
0
46 Powder and Bulk Engineering, October 1996 73

lem: Also check your baghouse’s can velocity before


2.
ra
Replacing leaking bags probably won’t significantly 5
reduce stack emissions because by now the bags’ clean making any changes. d

sides may be coated with migrated dust. In fact, the 0


migration is sometimes so heavy that the cleaning pulse
cn
The can velocity, given in feet per minute, is determined 0
drives the dust back into the media, blinding the bags
from both sides. If you suspect your baghouse has a high by dividing the volume of dust-laden air entering the bag-
A/C ratio, shine a light down the clean side of one bag and house chamber (or housing) by the netflow area available
rub the media surface. If it’s coated with dust, you can be in the airflow direction. The net flow area is determined
fairly sure the ratio is too high. by subtracting the total axial cross-sectional area of all
bags from the total cross-sectional area of the baghouse
-0
chamber (or can size). A baghouse can be made cheaper 0
by reducing its housing size -that is, by increasing the d
Q
can velocity. %
A properly engineered, fabricated, and installed dust P,
3
Q
collection system requires very little maintenance and In a baghouse where the dust-laden air enters at the bag
will operate 7 0 years after installation as reliably as it
m
chamber’s top or side, can velocity isn’t a factor in sizing r_
did at startup. the housing, which allows use of a smaller, less costly 7i

housing. But in a baghouse where the air enters at the bot-


tom, the collected dust released from the bags passes
through the entering dust-laden air, which makes can ve-
locity an important sizing factor.
Another telltale sign of a high A/C ratio is short-interval
pulse cleaning. When a baghouse’s performance begins Can velocity is also directly related to A/C ratio: For a
to fail, the operator may increase the pulse-cleaning fre- given baghouse size, increasing the A/C ratio also typi-
quency to overcome the Ap creep. The optimal pulse in-
cally increases the can velocity. Remember this when
terval is about 2 to 5 minutes. Using shorter intervals can
you’re considering switching bag media to reduce prob-
indicate the bags are partially blinded.
lems caused by a high A/C ratio. One solution is to use
surface-filtrationmedia, which can tolerate a higher A/C
Don’t simply replace the bags with the same media or use ratio using fewer bags and thus reduce the can velocity
off-line cleaning to clean the bags. If you don’t solve the and associatedmaintenance costs.
problem, the blinding will just start again. First, check
that the actual air volume through the baghouse matches
the design volume. Often a fan is oversized for a dust col-
lection system so that it can be throttled back to the design
air volume after installation. Or the system’s airflow re- Pulse cleaning is easy to misuse and abuse.
sistance can be lower than the designer expected. In either Continuous, unnecessay pulse cleaning prematurely
case, more air can be flowing through the baghouse than wears the bags.
was intended, producing a very high A/C ratio. Reducing
the fan speed can help. And to prevent future problems,
make sure you restore the system’s design air volume
after you make any change to the system.
If the can velocity is too high, dust released during bag
But if the actual air volume matches the design volume, cleaning can be re-entrained in the entering dust-laden air
you need to find another solution. Although you could re- and redeposited on the bags. Excessive can velocity pre-
place the baghouse with a bigger unit or supplement it sents symptoms similar to those for a high A/C ratio, in-
with a parallel baghouse to prevent blinding, a more cost- cluding a rising Ap, but the solution is different. Rather
effective solution is to use bags made of surface-filtration than blinding the bags, dust is just accumulatingon the bag
media such as Gore-Tex or P-84. These media are less surfaces because it can’t be expelled from the bag cham-
susceptible to blinding at higher A/C ratios. [Editor’s ber, thus causing the rising Ap. Switching media may not
note: For more information on bag media, see “Bag filter help unless the new media can handle a much higher A/C
fabrics: Getting the most for your filtering dollar” by ratio, which allows you to remove some bags to reduce the
James W. Griffin in Powder and Bulk Engineering, June can velocity. Off-line cleaning is a less frequentlyused so-
1992,pages 18-26.] lution because it can be expensive: Often you need to in-
stall another baghouse module to isolate bags for off-line
cleaning.
Housing size, can velocity problems
If you suspect your baghouse housing is undersized, A/C But how can you determine an acceptable can velocity for
ratio may not be the only factor contributing to the prob- your baghouse? Although it depends somewhat on your
0
0
48 Powder and Bulk Engineering, October 1996 73
2.
ra
5
d

0
cn
0

dust’s physical characteristics,particularly the strength of bleshooting advice in this section concentrates on bag-
the dust’s bonding (agglomerating) forces, a can velocity houses equipped with pulse cleaning.
below 300 fpm is usually acceptable. A can velocity
above 600 fpm can cause serious re-entrainment prob-
lems for many dusts. There are exceptions for specific Pulse cleaning is easy to misuse and abuse. Continuous,
dusts: For instance, can velocity shouldn’t exceed 200 unnecessary pulse cleaning prematurely wears the bags.
fpm for alumina dust. Bauxite’s upper limit is about 250 And because some dust retained on the bags, called the
fpm. But Western coal or lignite dust can have a can ve- filter cuke, actually does the filtering work, removing too
locity near 600 fpm. much dust from the bags during cleaning means the enter-
ing dust-laden air won’t be properly cleaned. As a result,
dust can bleed through the bags, causing excessive stack
If you have doubts about your can velocity, send samples emissions and even bag blinding.
of your dust to a qualified lab for an elutriation test. The
test measures can velocity by measuring the air velocity
at which your dust can be supported by an aircolumn. One way to control pulse cleaning is to use a pulse-on-de-
mand cleaning cycle control. This requires replacing the
baghouse differential pressure gauge with one that has an
Bag cleaning problems adjustable Ap setting and is coupled to an electrical
switch. The switch is wired in series with the control’s
A typical baghouse uses one of three bag cleaning meth- power supply. The control simply turns on the cleaning
ods: pulse (also called pulse wave or pulse jet), which control cycle when the Ap across the bags reaches a preset
uses high- or low-pressure compressed air during on-line value and turns off the control when the pressure drops
cleaning; reverse air, which typically uses low-pressure below that value. This technique automatically adjusts to
air such as from a centrifugalfan during off-line cleaning; variable dust loading at the inlet.
or bag shaking, which is also during off-line cleaning.
[Editor’s note: For more information on bag cleaning
methods, see articles listed under “Suggested reading” at With pulse-on-demand cleaning, being able to reliably
the end of this article.] read the Ap is important. To ensure reliable readings, use
compressed air to purge dust from the pressure lines lead-
ing from the baghouse housing.
Pulse cleaning is the most common for baghouses up to
about 400,000 acfm. This method typically uses either
high-pressure (100-psig), low-volume (HPLV) dried and Another common problem with pulse cleaning is that the
filtered (instrument-quality)compressed air or low-pres- manufacturer-set control parameters -including pulse
sure (7- to 15-psig), high-volume (LPHV) compressed air frequency, duration, and amplitude -are often tweaked
supplied by a positive displacement blower. The trou- by the baghouse operator to optimize bag cleaning. This
0
0
Powder and Bulk Engineering, October 1996 49 73
2.
ra
can easily upset the cleaning process. For instance, if the bag failure as the bags are slapped against the bag cage 5
d
operator’s first reaction to a rising Ap is to think the bags with increasing force from the increased Ap, and plugged
aren’t being properly cleaned, the operator may crank up ducts as reduced airflow cuts the dust transport velocity. 0
cn
the air pressure and pulse frequency to hit the bags harder 0
and faster. 77
So when troubleshooting the HPLV cleaning system, de-
termine whether a sharp bag-snapping pulse is being de-
But this can be exactly the wrong response. Increasing the livered to every bag at regular intervals and the cleaning
air pressure merely breaks up the agglomerated filter air pressure is set to the manufacturer’s spec. Also check
cake, causing the released dust to be re-entrained on the that each pulse valve snaps open and shut and no dust or
bags. Even slight partial blinding can’t be solved by sim- moisture in the air is slowing down the valve’s closure.
ply pulsing the bags harder and faster while on-line. In-
stead, you can usually gain reasonable, sometimes
temporary, flow through the bags using flow recovery P,
3
methods such as off-line cleaning and sparging (using an Q
air sparger to backflush the bags with high-pressure air). If all the bags in your baghouse are partially blinded m
But before attempting any solution, make sure you know and many bags require replacement, replace all the r_
x
what caused the blinding -for instance, an unreliable bags.
supply of cleaning air.

Cleaning air supply problems


The reliability of your cleaning air supply depends on Check the Ap as you check the HPLV cleaning cycle con-
whether the unit uses LPHV or HPLV pulse cleaning. An trols and operation. If the pulse interval and amplitude are
LPHV baghouse has a reliable cleaning air supply and correctly set, the Ap across the bags should be 2 to 4
distribution system: The nondried, low-pressure com- inches water gauge. If it’s much below 2 inches, the bags
pressed air is distributedthrough only one pulse valve and are being overcleaned; if it’s much above 4 inches, partial
rotating manifold, which services all the bags. Not much bag blinding can be occurring. For overcleaning,
can go wrong with the system. lengthen the pulse interval to bring the Ap back up to
about 2 inches. For partial blinding, immediately restore
full design airflow to preserve bag life and stop further de-
In contrast, the more commonly used HPLV baghouse re- terioration in system performance. Try the following
quires careful maintenance and instrument-quality com- remedies, in this order, to restore the airflow:
pressed air to keep the many pulse valves (about 1 for
every 16 bags) operating reliably. If the baghouse is the
only equipment in your plant using instrument-quality air, 1.Periodically pulse-clean the bags off-line (when the
the air quality is more likely to suffer. For instance, in a baghouse fan isn’t running).
cold climate, someone can forget to service the desiccant
in the compressed-air dryer, allowing moisture to reach
2. Apply high-pressure air (80 psig minimum) through an
and freeze the baghouse pulse valves. In very cold condi-
air sparger down into each bag cage to backflush each
tions, freezing can put the baghouse out of operation. bag.

There are problems in more temperate climates too. 3. Send the blinded bags to a commercial bag cleaning
Sometimes unconditioned plant compressed air is used service.
for the HPLV cleaning air supply, allowing dust and
moisture to affect the pulse valves. And neglecting to ser-
vice airline filters and traps can reduce the air pressure to Having to replace bags because your cleaning air supply is
the pulse valves. unreliable or your pulse valves have failed can be expen-
sive. Normal bag life is typically more than 2 years, but a
blinded bag can last less than 6 months. It costs about $7 to
The HPLV baghouse is quite sensitive to even a tempo- replace a typical 10-foot-long, 16-ounce polyester bag.
rary reduction or loss in the cleaning air supply’spressure. For a baghouse with 100bags (with a typical collection ca-
The resulting improperly cleaned bags cause dust to mi- pacity of 6,000 cfm), the unreliable air supply could cost
grate deep into the media, partially blinding the bags. And over $1,000 in unnecessary bag replacement, which
design airflow through the bags isn’t typically fully re- doesn’t include downtime or installationcosts.
stored once the air pressure is restored.
If all the bags in your baghouse are partially blinded and
This temporary reduction or loss contributes to other sec- many bags require replacement, replace all the bags. 0th-
ondary problems, such as shortened bag life, mechanical erwise, the new bags will soon become blinded as in-
0
0
Powder and Bulk Engineering, October 1996 73
50
dust doesn’t help filter the air. In fact, little dust is retained
2.
ra
creased airflow through them brings the Ap up to that of 5
the old bags. on the media. d

0
cn
P-84 uses a very fine denier filament with a cross section 0
Whenever you replace bags, throttle back the fan before
shaped like three lobes (instead of the round cross section
you put the baghouse back on-line. This allows the air-
of conventional media filament) that is needled into con-
flow to gradually increase as dust starts to coat the bags.
If the fan airflow is too high, the clean bags’ low airflow ventional felt. The filament provides extensive surface
resistance will allow dust to drive deeply into the media, area. The dust captured in the media provides the filtration,
immediately causing partial blinding. as with conventional felted media. But because of each fil-
-0
ament’s substantial surface area and a resident electrosta- 0
tic charge, most of the trapped dust stays near the media d
Q
surface. This enables the media to resist blinding. %
Bag media problems P,
3
Your bag media has a big effect on baghouse perfor- Q
mance. Bags are available in several media, from the m
r_
most common felted media such as 14- or 16-ounce 7i
polypropylene or polyester to surface filtration media Use thermal insulation as a cost-effective condensation
such as P-84 or Gore-Tex. Surface filtration media can be safeguard. But make sure you need the insulation,
five times as costly as felted media. But all have one thing because it’s costly if you don‘t.
in common: They don’t depend on depth filtration to sep-
arate dust from air.

You can reduce a high A/C ratio by switching from felted


to surface filtration media, but the media won’t cure bag
Your baghouse may have a poor inlet duct design that cleaning problems caused by the equipment or excessive
causes large eddy currents to return much of the condensation, nor can you use P-84 or Gore-Tex media
released dust back to the bags. instead of providing thermal insulation. But in some
cases, surface filtration media can solve high can velocity
problems (as described in the previous subsection,
“Housing size, can velocity problems”).

Depth filtration means dust deeply embedded in the Inlet diffuser problems
media’s inner structure is doing the filtering work. If your How airflow is distributed after entering your baghouse
baghouse A/C ratio is correct, depth filtration will work also impacts the unit’s performance. Various inlet duct
fine. But if you push the A/C limit, dust driven deeply into designs that don’t enhance flow distribution have been
the media can’t be removed by on-line cleaning. And any
used in baghouses: In some, the inlet duct is merely
free moisture, such as condensation caused by dewpoint
stubbed to the baghouse hopper so the dust has to find its
excursions, acts as a binder to the dust, decreasing the
way to the bag chamber. In others, a flat-plate target is in-
media’s permeability and locking dust deeply in the
media structure. stalled at the inlet duct’s end or a deflector plate is used to
turn the airflow down into the hopper.

In contrast, surface filtration occurs totally (or nearly to- Some baghouse manufacturers have researched the air-
tally) on the media surface, so that little or no dust pene- flow distribution after the dust-laden air enters the bag-
trates the media structure. This enables surface filtration house, finding that large secondary eddy currents affect
media to resist blinding. The media can also tolerate a air circulation between the bag chamber and dust hopper
much higher A/C ratio under tougher operating condi- when these inlet duct designs are used. As a result, the
tions while maintaining a very stable Ap. For instance, manufacturers have developed linear diffusers that re-
both P-84 and Gore-Tex recover very well from blinding duce eddy currents to provide uniform airflow into the
caused by dewpoint-excursion condensation on the bag bag chamber. The diffusers can be retrofitted to an exist-
surface. ing baghouse or included in a new one.

P-84 and Gore-Tex provide surface filtration in different Your baghouse may have a poor inlet duct design that
ways. Gore-Tex has a permeable polytetrafluoroethylene causes such large eddy currents to return much of the re-
(PTFE)membrane bonded to a substrate fabric’s surface. leased dust back to the bags. The dust can be re-entrained,
All filtration occurs on the membrane surface, and the and the currents can abrade the bag bottoms and create a
0
0
52 Powder and Bulk Engineering, October 1996 73
2.
ra
false dust loading. If your baghouse seems to have an ex- the baghouse also serves other collection points that don’t 5
d
cessive A/C ratio or can velocity, consider retrofitting a humidify the system air. Calculations determined that
linear diffuser. when the airstreamsfor all the system’spickup hoods mix 0
cn
as they travel through the ducting and baghouse, the hu- 0
midity doesn’t drop below the dewpoint. -0
S
Condensationproblems E
-.
Within your ducting or baghouse, vapor condensation cn
(which can result when you handle air or gases with But in a coke processing plant on the Gulf Coast, the ducting s
3
higher-than-ambient moisture content) can be disastrous, and baghouse servicing an outdoor hammermill plug up ca
especially if it occurs over a long period. But noncon- just days after plant startupin hot, humid summer weather. -0
The coke steams as it dischargesfrom the hammermill, and 0
densing vapor passing through the dust collection system d
usually causes no problems. In fact, even an occasional the ambient air humidity is more than 95 percent. Ther- Q

dewpoint excursion doesn’t typically have a serious ef- mally insulating the ducting and baghouse is the only way %
P,
fect on system operation. to prevent condensation and the resulting plugging. In a 3
Q
cold climate,the insulation probably also would be needed
in the baghouse dust hopper and dust return equipment m
r_
Use thermal insulation as a cost-effective condensation (such as a screw conveyor or pneumatic conveyor). 7i
safeguard. But make sure you need the insulation, be- m
cause it’s costly if you don’t. It can also be costly if you
need it and don’t install it. Dust hopper problems
The shape of the baghouse dust hopper affects the dust
Be aware that even in a very cold climate the baghouse discharge rate. A pyramidal hopper shape is the most
doesn’t always require thermal insulation, nor does a common because most baghouses have a square housing.
warm climate always mean you don’t need it. Instead, But a pyramidal hopper is subject to dust hangup on the
consider thermal insulation for preventing condensation hopper walls. Such hangup is not only inconvenient but
if moisture is released to the baghouse airor if the air’shu- dangerous in applications such as coal dust collection. In
midity can potentially increase above ambient. This can fact, dust hangup in the hopper is the most common cause
occur when cold outdoor air is drawn into the heated of baghouse fires in coal handling applications.A conical
workplace, enters a pickup hood, and then travels through hopper, which is used on the round housing of a LPHV
ducting to an outdoor baghouse. baghouse, is better than the pyramidal hopper.

But sometimes the need for thermal insulation isn’t obvi-


ous. For instance, if you mechanically work a material,
such as crush it in a hammermill, as much as 90 percent of Common problems are an undersized rotary airlock
the mill’s drive power is converted to heat as the material at the dust hopper discharge and undersized dust
is reduced. Much of that heat goes into raising the mate- return equipment.
rial’s temperature. If the crushed material has any surface
or inherent moisture, any makeup dust collection air serv-
ing the crushing operation will be humidified, which can
cause condensation in the ducting and baghouse.
If you can’t replace your square baghouse with a LPHV
unit, one reasonably quick fix is to coat the dust hopper
But first, before assuming you must add thermal insula- walls and the airlock rotor vanes at the hopper discharge
tion to the dust collection system in your crushing or simi- with a stick-resistantmaterial, such as a liquid Teflon-im-
lar operation, make some calculations to prevent pregnated epoxy that can be applied like paint.
spending money unnecessarily.The following two exam-
ples illustratewhy.
Dust return equipment problems
In a Wyoming coal plant where the outside air tempera- In a baghouse application, little attention is typically paid
ture frequently drops to -30°F, a 200-horsepower roll to dust return, especially if the dust is valuable and re-
crusher and a dust collection system are located outdoors. turned to the product stream. Common problems are an
The coal has over 30 percent inherent moisture. But ther- undersized rotary airlock at the dust hopper discharge and
mal insulation for the ducting and baghouse isn’t re- undersized dust return equipment, such as a screw con-
quired, because at -30°F the ambient air is very dry and veyor or pneumatic conveyor.
0
0
54 Powder and Bulk Engineering, October 1996 73
2.
ra
When the baghouse fan shuts down, much dust usually Problems with untreated dust returned to the system 5
d
falls from the bags. If you think of the baghouse dust hop- If you return untreated dust within the system’s collection
per as a funnel, not a storage hopper, you can understand 0
perimeter, some of the dust will be re-entrained in the sys- cn
why the dust must be quickly dischargedfrom the hopper: tem. This creates a compounding dust loading to the bag- 0
Fast discharge prevents the hopper from filling, which house, which ultimately will overload the unit. Depending -0
S
can cause eddy currents to throw dust up into the bag on the compoundingdust percentage, this process can take E
-.
chamber and create the same problems as an excessive hours, days, or weeks. But it will happen unless you find a cn
A K ratio or can velocity. s
way to agglomerate the dust to avoid re-entraining it or 3
hide the dust in the process stream to prevent the dust from ca
being picked up again. Symptoms of compounding dust -0
The airlock discharge can be undersized for any of the fol- 0
loading to watch for include dust filling the hopper, a re- d
lowing reasons: duction in the percentage of returned dust, and apparent
Q
%
bag blinding. P,
3
The designer underestimates the dust collection sys- Q
tem’s actual dust loading, especially when the system’s m
If your baghouse has compounding dust loading, there’s r_
dust enclosures are undersized and pickup hoods are lo- 7i
no simple cure for it. The only solution may be to retrieve rn
cated close to dusty, turbulent material flow.
the dust at the hopper and move it to some downstream lo- 3
cation, outside the collection perimeter, and let it be han- E.
3
The designer assumes the bulk density of a material is dled by another dust collection system. This option is (D

the same as that for the dust, when the dust’s density is costly, however. 2.
3
actually much less. For instance, Western coal’s bulk ra
density is about 50 lb/ft3but its aerated dust has a bulk
density of only about 24 lb/ft3. In a ductless dust collection system, such as a bin vent
or portable baghouse directly inserted into a conveyor
transfer chute, the bin or conveyor transfer chute also
*The designer assumes the wrong volumetric dis- doubles as the baghouse housing and dust hopper. In
placement rating for the airlock. The airlock rotor, this case, the dust is returned directly to the pickup
which is at atmospheric pressure, blows the dust hood and is agglomerated as it returns to the process
away from its empty pocket as it becomes exposed to stream, which can eliminate problems with com-
the dust hopper. The hopper is under negative pres- pounding dust loading. However, avoid placing the
sure, effectively reducing the airlock’s rated volu- baghouse too close to the process stream; the resulting
metric displacement. air turbulence can disturb the airflow at the baghouse
inlet.

The airlock rotor speed is too high. When the airlock


rotor is turning too fast, the pockets aren’t completely How to avoid design problems by using a systems
filled as they pass by the dust hopper outlet, further re- engineering approach
ducing the airlock’srated volumetric displacement.

P
erformance problems are inevitable when you buy
a baghouse from one manufacturer, a fan from an-
other, and dust return equipment from another, and
then procure ducting while the system is being installed.
Compounding these problems is the common practice of
Symptoms of compounding dust loading to watch for using your plant’s iron workers and millwrights to put
include dust filling the hopper, a reduction in the the system together, then starting up the fan and other
percentage of returned dust, and bag blinding. equipment without the services of a testing and balanc-
ing contractor.

You can avoid many of the problems discussed in this ar-


ticle by taking a systems engineering approach to design-
Correctly sizing the rotary airlock and dust return equip- ing your dust collection system. Such an approach will
ment will ensure dust is smoothly discharged from the save money not only in equipment selection but also in
hopper. Size the airlock’s volumetric capacity for at least the following ways:
200 percent of the peak dust loading you estimate for the
dust collection system - and don’t skimp on the esti-
mate. Also ensure the airlock’s rotor speed doesn’t have The ducting will be properly designed, fabricated, and
to exceed 20 rpm to satisfy the airlock manufacturer’s installed, and the airflow distribution will be balanced,
rated displacement. reducing ducting maintenance costs.
0
0
Powder and Bulk Engineering, October 1996 55 73
v
The pickup hoods and other containment devices (such
as enclosures and related equipment housings) will re-
duce the calculated air volume, cutting the system’s cap- 0
ital and operating costs. cn
0
L

The dust collectionequipment will be properly specified E


-.
cn
for your operating environment and performance crite- s
ria to ensure reliable operation and reduce operating and
maintenance costs.
-0
0
d
Q
*The system’s air volume will be properly distributed,
often substantially reducing the dust cycled by the bag- %
P,
house and lengthening bag life. PBE 3
Q

rn
3
Reference
1. Industrial Ventilation: A Manual of Recommended Practice, The
American Conference of Governmental Industrial Hygienists.

Suggested reading
For more information on baghouse dust collection sys-
tems, see these articles in Powder and Bulk Engineering:

“Eight steps for designing a dust control system and esti-


mating its cost,” John A. Constance, October 1991,pages
24-30.

“Factors to consider when selecting a baghouse or car-


tridge dust collector,” Thomas J. Vidmar and Marcel
Jolin, October 1992,pages 47-52.

“Guidelines for operating and maintaining your dust


control system,” John A. Constance, October 1994,
pages 67-75.

“How to troubleshoot your baghouse,” Gary P. Greiner,


October 1990,pages 40-46.

Garren E. Tooker is senior vice president of engineering


at Air Control Science, 6560 Ode11 Place, Boulder, CO
80301; 303/581-1070. He holds a mechanical engineer-
ing degreefrom Cogswell Polytechnic College,San Fran-
cisco, and has more than 30 years experience in dust
collection, industrial ventilation, and engineering, design-
ing,and constructing bulk material handling systems.

You might also like