LANDSIDE
UTHURU THILA FALHU (UTF) HARBOUR, MALDIVES.
JANUARY 2024
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
INDEPENDENT ENGINEER :
MADRAS
IMPLEMENTING ENGINEER :
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
EPC CONTRACTOR
TABLE OF CONTENTS
CHAPTER 1 - INTRODUCTION....................................................................................................5
1.1 BACKGROUND 5
CHAPTER 5 – LOADS................................................................................................................9
5.1 DEAD LOAD (DL) 10
5.2 WALL LOAD CALCULATION 11
5.3 FLOOR LOAD CALCULATION 11
5.4 TANK LOAD CALCULATION 11
5.5 TIME PERIOD CALCULATION 11
5.6 LIVE LOAD: 12
5.7 SEISMIC LOAD (EQ): 12
5.8 WIND LOAD (WL): 12
CHAPTER 1 - INTRODUCTION
1.1 BACKGROUND
The Structure Design Basis Report of the full Project has been submitted vide Report No.
2324/010/DBR/STR/REC/RP043-REV-0, JANUARY 2024. Further, this Structure Design Report presents
the details related to the proposed project for construction of
VISITOR’S TOILET building, according to the architectural plans, sections & elevations. The various
provisions in accordance with Indian codes and methodology used in detailed design has been provided.
The building is designed for Ground floor only with Built-up Area of 900.18 SqFt., using M30grade of
concrete (confirming to IS: 456: 2000) for all other structural members i.e., Beams, slabs, column, etc.
The superstructure is designed as a Special moment resisting system frame (SMRF) building. All columns,
beams, slab, staircases are in R.C.C.
The structure has been as per the Architectural requirement for civil and structural works, standard
specifications, National Building Code (NBC-2016), relevant I.S codes and local regulations.
Requirements governing Reinforcement and detailing of structural elements, maximum diameter and
spacing of the reinforcement is restricted as per detailing indicated in clause 26.0 of IS-456:32000.
Lateral Frame Deflection (Storey Drift) Under Seismic Load as per Clause 7.11.1.1 of 1893 (Part-
1):2016.
Storey Drift in any Storey shall not exceed 0.004 times the Storey height, under the action of design base of
shear VB with no load factors.
Modes of Oscillation in Two Principal Plan Directions (As per Clause 7.1 Table 6 (vii) of1893 (part
1):2016)
It shall been assured the first three modes together contribute at least 65% The Mass participation factor in
each principal plan direction.
COLUMN 320x320
COLUMN 320x400
COLUMN 320x450
BEAM 200X300
BEAM 200x450
BEAM 200X600
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
Soil bearing capacity is considered as 20.0 ton/m2 at 1.5m Depth from filled up level for the design as per
the soil report/ Recommendation.
Footing design and drawings has been designed based on the Bearing capacity (20 ton/m2 at 1.5m) of the
soil and based on Structure design of building.
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
CHAPTER 5 – LOADS
5.1 DEAD LOAD (DL)
The dead load on structure includes all the permanent loads attached with structure i.e. self-weight of
structure, slab, floor, finish, walls and partition load. The loading pattern is trapezoidal and triangular
depending upon the panel size in the floor slab. The wall loads have been calculated based on wall
thickness and same applied on beam members as UDL.
Following are the permanent loads which have been considered in design & analysis.
Self-Weight of Structure members have been considered on the basis of the following criteria: -
Component DENSITY
Density Of Concrete = 25 kN/cu.m
Density Of Soil = 20 kN/cu.m
Density Of Steel = 78.5 kN/cu.m
Density of Plain Concrete = 24 kN/cu.m
Density Of Finishes = 20 kN/cu.m
Density of Concrete block = 24 kN/cu.m
Density of Mortar = 24 kN/cu.m
Density of Tile = 20 kN/cu.m
Density of Ceiling plaster = 20.2 kN/cu.m
Filling Load = 18 kN/cu.m
RECEPTION BUILDING
H (m) 4.65
X Direction Y Direction
Area
Thicknes Number Number Area of
Length of Aw Length Thickness Aw
s of walls of walls wall
wall
S. VALUE
USAGE
NO.
1 Terrace 200 kg/sq.m
Reduction in live load has been considered as per the clause 3.2 of IS: 875 (Part II)
Design load shall be as per IS1893:2016 (Part – I), Seismic Parameters are as per soil report.
Parameter Value
Z - i.e. Zone Factor 0.16 (For zone III)
I - Importance Factor 1.5 (Cl. 7.2.3(ii) of IS 1893:2016.)
R - Response Reduction Factor 5 (Table-9 of IS: 1893-2016)
Soil Type Type II
Analysis type Static analysis
Fundamental natural time period is taken as per Clause 7.6.2 of IS: 1893-2016, for R.C.C Frame Building.
Ta =0.09h/√d
h = Height of building in meter
d = base dimension of building(m)
The time period of the structure has been entered after manual calculation. The building has been designed
for base shear based on BIS code where time period is in accordance with clause 7.2 of IS: 1893-2016
using scale factor = V̅ B/VB where V̅ B is calculated base shear based on BIS code, the time period Ta
=0.09h/√d and VB is calculated base shear based on time period manual calculation. The horizontal
earthquake force has been calculated for the full dead load & reduce live load as per clause 7.3.1 Table-10
of IS: 1893-2016.
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
The wind load has been taken as per IS: 875 (Part-III) and wind pressure calculated : -
pz = 0.6 Vz2 N/sq.m
Vz = K1. K2. K3. K4.Vb
Vz = Design wind velocity
= 83.33m/sec
= 4.166 KN/sq.m
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
The load combinations that are considered for the design of the foundations are as below:
• 1.0 (D.L +L.L)
• 1.0 (D.L+EQX/WL)
• 1.0 (D.L-EQX/WL)
• 1.0 (D.L+EQY/WL)
• 1.0 (D.L-EQY/WL)
• 1.0 (D.L+L.L +EQX/WL)
STRUCTURAL DESIGN
CALCULATION REPORT
– VISITOR’S TOILET EPC CONTRACTOR
Where:
D.L =Dead Loads
L.L = Live Loads
EQ = Earthquake Loads
WL = Wind Loads
BASE SHEAR
Step
Outpu Numbe
t Case r FX FY FZ MX MY MZ
1486.845
SIDL 0 0 1 7887.3028 -6719.1447 0
-
161.048
WLX 1 6 0 0 0 -748.8759 660.2992
-
133.514
WLX 2 0 5 0 620.8423 0 -586.1285
-
160.932
WLY 1 6 0 0 0 -748.3368 659.8238
-
142.636
EQX 1 9 0 0 0 -631.1369 697.2109
-
142.636
EQX 2 9 0 0 0 -631.1369 742.504
-
142.636
EQX 3 9 0 0 0 -631.1369 651.9178
-
142.636
EQY 1 0 9 0 631.1369 0 -642.085
-
142.636
EQY 2 0 9 0 631.1369 0 -665.5242
-
142.636
EQY 3 0 9 0 631.1369 0 -618.6457
Ah = 142.64/3136.85 = 0.06
sec
0.00000964
Modal 1 0.442 0.5182 6 0