You are on page 1of 5

LOGSHEET HYPERMART

LIPPO MALL KEMANG


JANUARI 2024
Tanggal 01/01/2024 01/01/2024 01/01/2024 02/01/2024
Jam 3.36 4.19 12.14 11.16
Chiller H2 H2 H2 H1
Petugas TOMI / MAULANA TOMI / MAULANA DJOHARI-REZHA DJOHARI-REZHA
Ampere
L1 215 199 204 198
L2 223 208 208 199
L3 210 197 201 189
AB 388 389 387 391
BC 391 387 387 390
CA 391 387 389 390
Active
Chilled Limit Setpoint 7 7 7 8
Current Limit Setpoint 1 1 1 1
Compressor
Starts 2468 2468 2468 2627
Running Time 2515;44 25155;45 25157:14 25954:08
Discharge Temp 51 52 53 51
Evaportaor
Entering Water Temp 9 9 9 10
Leaving Water Temp 7 7 7 8
Sat RFGT Temp 6 6 6 7
RFGT Pressure 256 257 256 266
Approach Temp 1 1 1 2
Water Flow Switch Temp FLOW FLOW FLOW FLOW
Condenser
Entering Water Temp 31 30 31 32
Leaving Water Temp 35 35 35 35
RFGT Temp 37 36 37 36
RFGT Pressure 842 814 826 801
Approach Temp 2 2 2 1
Flow Swtich Status FLOW FLOW FLOW FLOW
LOGSHEET HYPERMART
LIPPO MALL KEMANG
JANUARI 2024
Tanggal 05/01/2024 05/01/2024 06/01/2024 06/01/2024
Jam 7.26 6.14 1.12 11.16
Chiller H1 H1 H2 H2
Petugas lukman/ipan lukman/ipan LUKMAN & IRFAN tomi/ipan
Ampere
L1 263 184 198 192
L2 269 185 204 203
L3 255 180 197 184
AB 388 389 394 397
BC 391 390 393 399
CA 385 387 391 393
Active
Chilled Limit Setpoint 7 8 7 7
Current Limit Setpoint 10 1 1 1
Compressor
Starts 2467 2629 2470 2470
Running Time 25141;37 25982;23 25180:58 25184;12
Discharge Temp 51 50 52 49
Evaportaor
Entering Water Temp 10 10 9 9
Leaving Water Temp 7 8 6.9 C 7
Sat RFGT Temp 6 7 5.7 C 6
RFGT Pressure 256 267 256 257
Approach Temp 1 2 1.3 C 1
Water Flow Switch Temp FLOW FLOW FLOW FLOW
Condenser
Entering Water Temp 32 30 30 28
Leaving Water Temp 37 33 34 32
RFGT Temp 39 34 35.8 C 33
RFGT Pressure 900 752 806 749
Approach Temp 2 1 2 2
Flow Swtich Status FLOW FLOW FLOW FLOW
LOGSHEET HYPERMART
LIPPO MALL KEMANG
JANUARI 2024
Tanggal 07/01/2024 07/01/2024 08/01/2024 08/01/2024
Jam 6.57 2.09 2.09 6.57
Chiller H1 0 H1 H1
Petugas Lukamn - Aji saka tomi/ipan TOMI / MAULANA TOMY-MAULANA
Ampere
L1 222 172 189 186
L2 226 179 196 187
L3 213 169 188 181
AB 387 394 391 389
BC 392 396 393 388
CA 389 390 392 388
Active
Chilled Limit Setpoint 8 8 8 8
Current Limit Setpoint 1 1 1 1
Compressor
Starts 2630 2630 2631 2631
Running Time 25996;13 25999;31 26004;49 26008;44
Discharge Temp 49 53 49 52
Evaportaor
Entering Water Temp 31 9 10 10
Leaving Water Temp 35 8 8 8
Sat RFGT Temp 36 6 7 7
RFGT Pressure 819 266 267 268
Approach Temp 1 2 2 1
Water Flow Switch Temp FLOW FLOW FLOW FLOW
Condenser
Entering Water Temp 31 29 31 30
Leaving Water Temp 35 31 34 34
RFGT Temp 36 32 35 34
RFGT Pressure 819 715,9 782 761
Approach Temp 1 1 1 1
Flow Swtich Status FLOW FLOW FLOW FLOW
LOGSHEET HYPERMART
LIPPO MALL KEMANG
JANUARI 2024
Tanggal 08/01/2024 09/01/2024 09/01/2024 09/01/2024
Jam 6.28 5.45 6.28 2.09
Chiller H1 H2 H2 H2
Petugas TOMI-REZHA TOMI / MAULANA TOMI / MAULANA TOMI-REZHA
Ampere
L1 181 219 204 203
L2 190 222 205 206
L3 179 212 197 195
AB 394 386 386 392
BC 392 390 390 394
CA 392 384 386 390
Active
Chilled Limit Setpoint 8 7 7 7
Current Limit Setpoint 1 1 1 1
Compressor
Starts 2631 2471 2471 2471
Running Time 26011:58 25191;26 25195;37 25199:17
Discharge Temp 51 50 52 51
Evaportaor
Entering Water Temp 10 9 9 9
Leaving Water Temp 8 7 7 7
Sat RFGT Temp 7 6 6 6
RFGT Pressure 268 256 256 257
Approach Temp 2 1 1 1
Water Flow Switch Temp FLOW FLOW FLOW FLOW
Condenser
Entering Water Temp 30 30 30 30
Leaving Water Temp 33 34 34 34
RFGT Temp 34 36 36 36
RFGT Pressure 753 818 809 808
Approach Temp 1 2 2 2
Flow Swtich Status FLOW FLOW FLOW FLOW
LOGSHEET HYPERMART
LIPPO MALL KEMANG
JANUARI 2024
Tanggal 10/01/2024 10/01/2024 11/01/2024 12/01/2024
Jam 0.43 5.02 1.55 7.40
Chiller H1 H1 H1 H1
Petugas ARIFIN-REZHA ARIFIN-REZHA Arifin - Aji saka LUKMAN & IRFAN
Ampere
L1 221 212 187 187
L2 230 217 192 192
L3 218 207 180 180
AB 395 390 391 391
BC 397 391 389 389
CA 392 387 389 389
Active
Chilled Limit Setpoint 8 8 8 8
Current Limit Setpoint 1 1 1 1
Compressor
Starts 2632 2632 2633 2633
Running Time 26019:37 26022:56 26034;39 26039:51
Discharge Temp 49 50 52 51
Evaportaor
Entering Water Temp 10 10 10 9
Leaving Water Temp 8 8 8 8
Sat RFGT Temp 6 7 7 6
RFGT Pressure 266 267 268 268
Approach Temp 2 2 1 1
Water Flow Switch Temp FLOW FLOW FLOW FLOW
Condenser
Entering Water Temp 32 32 31 30
Leaving Water Temp 36 35 33 32.0 c
RFGT Temp 37 36 34 32.9 c
RFGT Pressure 836 822 769 736
Approach Temp 1 1 1 1
Flow Swtich Status FLOW FLOW FLOW FLOW

You might also like