RESERVED FOR AHJ

PHOTOVOLTAIC ROOF MOUNT SYSTEM


(E) 44 + (N) 08 MODULES-ROOF MOUNTED - 19.04 KWDC, 16.33 KWAC
12102 OR-234, GOLD HILL, OR 97525 USA
SYSTEM SUMMARY: DESIGN CRITERIA: GOVERNING CODES: SHEET INDEX
(N) 08 - ZNSHINE SOLAR ZXM7-SH108 (400W) MODULES ROOF TYPE: - ASPHALT SHINGLE 2020 NATIONAL ELECTRICAL CODE (NEC) PV-0 COVER SHEET PURELIGHT POWER
(N) 04 - AP SYSTEMS DS3-S MICRO-INVERTERS NUMBER OF LAYERS: - 01 2022 OREGON FIRE CODE (OFC) PV-1 SITE PLAN WITH ROOF PLAN 3521 AVION DRIVE STE 200,
2021 OREGON RESIDENTIAL SPECIALTY CODE (ORSC) MEDFORD, OR 97504
(N) 02 - JUNCTION BOXES ROOF FRAMING: - 2"X6" RAFTERS @24" O.C. PV-2 ROOF PLAN WITH MODULES CSLB : 226333
(E) 200A METER MAIN SERVICE PANEL WITH (E) 150A MAIN BREAKER STORY: - ONE STORY 2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC) PV-3 ATTACHMENT DETAILS PHONE: (541) 816-4047
(E) 44 - YINGLI SOLARYL360D-34D 1/2 (360W) MODULES SNOW LOAD : - 25 PSF 2021 OREGON SPECIALTY ELECTRICAL CODE (OSEC) PV-4 BRANCH LAYOUT EMAIL: ADMIN@PURELIGHTPOWER.COM

(E) 10 - AP SYSTEMS QS1 MICRO-INVERTERS WIND SPEED :- 96 MPH (ASCE 7-16) PV-5 ELECTRICAL LINE DIAGRAM VERSION
(E) 03 - AP SYSTEMS YC600 MICRO-INVERTERS WIND EXPOSURE:- B PV-6 ELECTRICAL CALCULATION DESCRIPTION DATE REV
(E) 100A FUSED AC DISCONNECT WITH (N) 90A FUSES RISK CATEGORY:- II PV-7 WARNING LABELS INITIAL RELEASE 07/21/2023 UR
(E) 100A SOLAR LOAD CENTER OCCUPANCY: R-3 RESIDENTIAL PV-7.1 PLACARD
(E) PRODUCTION METER PV-7.2 MICRO INVERTER CHART
(E) 200A NON- FUSED AC DISCONNECT PV-8 ADDITIONAL NOTES
PV-9+ EQUIPMENT SPEC SHEETS

GENERAL NOTES:
1. PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLY 29-AUG-2023
WITH REQUIREMENTS OF 2021 OESC & 2022 OSSC. EXP.: 31-DEC-2023
2. 3111.3.2 - PV RACKING AND ATTACHMENTS SHALL BE UL 1703 STRUCTURAL ONLY
CERTIFIED. (N) ARRAY
3. 3111.3.4 - PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION
LOCATIONS PROJECT SITE
THAT IS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLY
PROJECT NAME
REQUIRED BY OSSC SECTION 1505.1.
4. 3111.4.3 - 3111.4.7- PV LAYOUT SHALL NOT RESTRICT EGRESS,
LIGHT VENTILATION, OR ROOF DRAINAGE REQUIREMENTS.

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


5. 3111.4.8.1 - GENERAL PATHWAY REQUIREMENTS:

AHJ: JACKSON COUNTY


· 36" WIDE PATHWAY SHALL NOT BE REQUIRED ON
STRUCTURES WITH A PV ARRAY AREA OF 1,000 SF OR LESS

BRIAN MAXWELL

APN# 10162612
INSTALLED ON A ROOF WITH A SLOPE THAT EXCEEDS 2:12 AND

12102 OR-234,
WITH AN INTERSECTING ADJACENT ROOF AND WHERE NO
SECTION IS LARGER THAN 150 FEET MEASURED IN LENGTH OR
WIDTH.
· WHERE PV ARRAY DOES NOT EXCEED 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF A STRUCTURE, A
MINIMUM OF 12" UNOBSTRUCTED PATHWAY SHALL BE
MAINTAINED ALONG EACH SIDE OF ANY HORIZONTAL RIDGE.
· WHERE THE SOLAR ARRAY EXCEEDS 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF THE STRUCTURE, A
MINIMUM OF ONE 36" UNOBSTRUCTED PATHWAY SHALL BE
PROVIDED IN ADDITION TO A MINIMUM 12" UNOBSTRUCTED
ALONG EA. SIDE OF ANY HORIZONTAL RIDGE.
6. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOOD
CONSTRUCTION WITH RAFTERS @ 24" O.C. REFER TO
ALLOWABLE SPAN REQUIREMENTS IN TABLE 305.4.1.
7. 3111.4.8.5.1 - DISCONNECTS, J-BOXES, COMBINER BOXES OR
GUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAY SHEET NAME
OR CUTOUT.
8. PV MODULES AND RACKING SHALL BE DIRECTLY ATTACHED TO COVER SHEET
ROOF FRAMING AS SHOWN IN PV-2. WHEN ATTACHMENT
LOCATED WITHIN 3' OF ROOF EDGE, HIP, EAVE, RIDGE SHALL
SHEET SIZE
BE 24" O.C. MAX.
9. 3111.5.4 - MAX MODULE HEIGHT < 18" OFF ROOF SURFACE. ANSI B
11" X 17"
1 AERIAL PHOTO 2 VICINITY MAP SHEET NUMBER
PV-0 SCALE: NTS PV-0 SCALE: NTS
PV-0
RESERVED FOR AHJ
ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE
PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR
DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN
LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD
~339.03' PROPERTY LINE
OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.

PROPERTY LINE
NOTE: CHECK WITH CITY/COUNTY OR LAND SURVEYOR
FOR ACCURATE PROPERTY LOCATION.

NOTE: PV AC DISCONNECT LOCATED WITHIN


10 FEET OF THE MAIN BILLING METER
(E) GATE

~10
VISIBLE, LOCKABLE, LABELED AC DISCONNECT PURELIGHT POWER
3521 AVION DRIVE STE 200,

40'
LOCATED WITHIN 10' OF UTILITY METER (E) POOL MEDFORD, OR 97504
CSLB : 226333

-0 "
0'-0" ROOF #2
PHONE: (541) 816-4047

~27
EMAIL: ADMIN@PURELIGHTPOWER.COM

(E) (24) YINGLI SOLARY L360D-34D 1/2 (04) ZNSHINE SOLAR ZXM7-SH108 VERSION
(360W) SOLAR MODULES (400W) SOLAR MODULES 29-AUG-2023 DESCRIPTION DATE REV
EXP.: 31-DEC-2023
SEE ENLARGED VIEW - 1A INITIAL RELEASE 07/21/2023 UR
(E) FENCE STRUCTURAL ONLY

M SLC
D PV
AC
B
SU

'-0"

~1214.15'
~30
(E) (20) YINGLI SOLARY L360D-34D 1/2

JB
JB
(360W) SOLAR MODULES
(E) STRUCTURE (TYP.)
SEE ENLARGED VIEW - 1C
ROOF #1

M
M
AC
D
(04) ZNSHINE SOLAR ZXM7-SH108 (400W)
SOLAR MODULES
SEE ENLARGED VIEW - 1B (E) 200A MATER MAIN
SERVICE PANEL PROJECT NAME
WITH (E) 150A MAIN BREAKER

GOLD HILL, OR 97525 USA


(E) PEDESTAL

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
M
~26
(E) 200A NON-FUSED AC DISCONNECT

EX EWA
DR
0'-0

BRIAN MAXWELL
IST

AC
IV

APN# 10162612
12102 OR-234,
"

ING

D
~1381.34'

(E) 100A FUSED AC DISCONNECT

Y
WITH (N) 90A FUSES
(E) PRODUCTION METER
(E) 100A SOLAR LOAD CENTER ENLARGED VIEW - 1B

SLC LEGEND
M 84'
PROPERTY LINE

PV 2. MM METER MAIN PANEL

AC
D ~ 38 SUB SUB PANEL

B ACD AC DISCONNECT
SU
(N) 3/4" OR GREATER EMT

INE
CONDUIT RUN (IN ATTIC) JB JUNCTION BOX

34
L SHEET NAME

RTY (N) JUNCTION BOX (TYP.)

-2
(E) 200A SUB PANEL E PVM PRODUCTION METER SITE PLAN WITH
OP
WITH (E) 200A MAIN BREAKER
PR
O R SLC SOLAR LOAD CENTER ROOF PLAN
SHEET SIZE
PROPERTY LINE

JB
ENLARGED VIEW - 1A ANSI B
GATE
FENCE
11" X 17"
SHEET NUMBER
SITE PLAN WITH ROOF PLAN CONDUIT

1 SCALE: 1/64" = 1'-0"


ENLARGED VIEW - 1C
TREES
PV-1
RESERVED FOR AHJ
MODULE TYPE, DIMENSIONS & WEIGHT BILL OF MATERIALS ARRAY AREA & ROOF AREA CALC'S ROOF DESCRIPTION
NUMBER OF MODULES = 08 MODULES EQUIPMENT QTY DESCRIPTION ROOF TYPE ASPHALT SHINGLE ROOF
MODULE TYPE = ZNSHINE SOLAR ZXM7-SH108 (400W) MODULES
# OF ARRAY AREA ROOF AREA
MODULE WEIGHT = 45.19 LBS / 20.5 KG. RAIL 06 CHIKO RAIL (CK-FT-R7B2-4200) ROOF
MODULES (Sq. Ft.) (Sq. Ft.) ROOF RAFTERS
MODULE DIMENSIONS = 67.87"X 44.65" = 21.04 SF ROOF AZIMUTH RAFTERS SIZE
SPLICE 04 RAIL SPLICE TILT SPACING
UNIT WEIGHT OF ARRAY = 2.15 PSF MID CLAMP 12 MODULE MID CLAMP #1 04 84.18 320.81
#1 12° 246° 2"x6" 24" O.C.
ARRAY AREA & ROOF AREA CALC'S END CLAMP 08 MODULE END CLAMP #2 04 84.18 320.81
#2 12° 66° 2"x6" 24" O.C.
ATTACHMENT 20 UNIRAC FLASHKIT PRO
AREA OF NEW AREA OF EXISTING AREA OF ROOF TOTAL ROOF AREA
ARRAY (Sq. Ft.) ARRAY (SQ. FT.) PLAN VIEW) (Sq. Ft.) COVERED BY ARRAY % GROUNDING LUG 02 GROUNDING LUG
PURELIGHT POWER
168.36 862.40 2302.79 45% 36" FIRE PATHWAY 3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
45% ROOF AREA (ARRAY >25% OF ROOF AREA) CSLB : 226333

3'-0"
R
PHONE: (541) 816-4047

A
EMAIL: ADMIN@PURELIGHTPOWER.COM

Y
EAR
VERSION
NOTE TO INSTALLERS: VERIFY THE ROOF 12" FIRE PATHWAY DESCRIPTION DATE REV
FRAMING INFORMATION BEFORE
R INITIAL RELEASE 07/21/2023 UR

12"
INSTALLATION AND
NOTIFY THE EOR IF 2"x6" RAFTERS @ 24"
O.C. SPACING WITH MAX UNSUPPORTED
SPAN EQUAL OR GREATER THAN 10'-9". 29-AUG-2023
EXP.: 31-DEC-2023
STRUCTURAL ONLY
PV RACKING DESIGNED BY OTHERS

(E) (24) YINGLI SOLARY


L360D-34D 1/2 (360W) SOLAR PROJECT NAME

MODULES

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
1'-7

BRIAN MAXWELL
(E) 2"X6" RAFTERS @ 24" O.C. (TYP.)

"

APN# 10162612
12102 OR-234,
12"
12"

15'
FIR
FIR

EP

-2"
EP
(E) (20) YINGLI SOLARY (N) (20) UNIRAC FLASHKIT PRO

AT

JB
AT
HW
HW
L360D-34D 1/2 (360W) SOLAR ATTACHMENTS SPACED AT 48" O.C.

AY
AY
MODULES ROOF #2
JB
(04) ZNSHINE SOLAR ZXM7-SH108 PHOTOVOLTAIC MODULES
1'-7

ZNSHINE SOLAR

3'-3
(E) ASPHALT SHINGLE ROOF (TYP.) (400W) SOLAR MODULES
ZXM7-SH108 (400W)
"

"
(N) JUNCTION BOX (TYP.) WA
15'

A TH 67.87"
EP
-2"

IR "
(N) CHIKO RAIL (CK-FT-R7B2-4200) 36"
F 4'-0 OF
#2
°
" RO - 12 66°
5'-8
Y
WA T

44.65"
A TH TIL TH -
E P IMU
ROOF #1 FIR '-6" AZ
(04) ZNSHINE SOLAR ZXM7-SH108 (400W) 36" " 6 " 2
5'-8 2'-
D
3'-3

SOLAR MODULES
#1 4'-0
"
A R
"

TY
OF °
RO - 12 46° SHEET NAME
T 2
TIL TH -
N 4 LEGEND
FRO R-23
I M U ROOF PLAN
AZ
JB - JUNCTION BOX WITH MODULES
O - VENT, ATTIC FAN SHEET SIZE

(ROOF OBSTRUCTION) ANSI B


NOTE: ACTUAL ROOF CONDITIONS AND - ROOF ATTACHMENT 11" X 17"
ROOF PLAN WITH MODULES RAFTERS (OR SEAM) LOCATIONS MAY VARY. - RAFTERS SHEET NUMBER

1 SCALE: 3/32" = 1'-0"


INSTALL PER MANUFACTURER(S) INSTALLATION
GUIDELINES AND ENGINEERED SPANS FOR
ATTACHMENTS
- FIRE PATHWAY PV-2
RESERVED FOR AHJ
NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM)
LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S)
INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR
ATTACHMENTS

1.1
8"
PURELIGHT POWER

~4"
3521 AVION DRIVE STE 200,
PV MODULES MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

ASPHALT SHINGLE ENLARGED VIEW


ROOF

(E) 2"X6" RAFTERS @24" O.C.

ATTACHMENT DETAIL
1 SCALE: NTS PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
PV MODULES

BRIAN MAXWELL

APN# 10162612
12102 OR-234,
1.18"
SS SERRATED FLANGE NUT
CHIKO RAIL (CK-FT-R7B2-4200)
L-FOOT

~4"
ASPHALT SHINGLE
ROOF
29-AUG-2023
EXP.: 31-DEC-2023
STRUCTURAL ONLY
SHEET NAME
ROOF / DECK MEMBRANE
2.5" MIN. ATTACHMENT
EMBEDMENT DETAIL
UNIRAC FLASHKIT PRO BUILDING STRUCTURE
SHEET SIZE

ANSI B
5/16" STAINLESS STEEL LAG BOLT
WITH 2-1/2" MIN. EMBEDMENT AND SS EPDM
11" X 17"
ATTACHMENT DETAIL (ENLARGED VIEW) WASHER SHEET NUMBER

2 SCALE: NTS
PV-3
RESERVED FOR AHJ
(N) (08) ZNSHINE SOLAR ZXM7-SH108 (400W) MODULES
PHOTOVOLTAIC MODULES
(N) (04) AP SYSTEMS DS3-S MICRO-INVERTERS ZNSHINE SOLAR
(N) (01) BRANCH OF 08 MODULES CONNECTED IN PARALLEL PER BRANCH ZXM7-SH108 (400W)
(E) (44) YINGLI SOLAR YL360D-34D 1/2 (360W) MODULES
(E) (10) AP SYSTEMS QS1 MICRO-INVERTERS 67.87"
(E) (03) AP SYSTEMS YC600 MICRO-INVERTERS
A R D

44.65"
(E) (02) BRANCHES OF 12 MODULES CONNECTED &
(E) (01) BRANCHES OF 10 MODULES CONNECTED IN PARALLEL PER BRANCH
R Y
REA PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
36" FIRE PATHWAY CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

3'-0"
VERSION
DESCRIPTION DATE REV

12" FIRE PATHWAY INITIAL RELEASE 07/21/2023 UR

12"
(E) (24) YINGLI SOLARY
L360D-34D 1/2 (360W) SOLAR PROJECT NAME
MODULES

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
12"
12"

FIR
FIR

EP
EP

AT
AT

HW
HW

AY
AY
(E) (20) YINGLI SOLARY
L360D-34D 1/2 (360W) SOLAR ROOF #2
MODULES (04) ZNSHINE SOLAR ZXM7-SH108
(400W) SOLAR MODULES

ROOF #1
AY
(04) ZNSHINE SOLAR ZXM7-SH108 (400W)
T HW
SOLAR MODULES E PA
FIR
(04) AP SYSTEMS DS3-S 36"
MICRO-INVERTERS AY SHEET NAME
THW
BRANCH #1
36"
F IRE
PA

A R D BRANCH LAYOUT

T Y
O N 4
SHEET SIZE

FR - 2 3 ANSI B

BRANCH LAYOUT OR 11" X 17"

1
SHEET NUMBER

SCALE: 1/8" = 1'-0" PV-4


RESERVED FOR AHJ
(N) (08) ZNSHINE SOLAR ZXM7-SH108 (400W) MODULES BILL OF MATERIALS
(N) (04) AP SYSTEMS DS3-S MICRO-INVERTERS EQUIPMENT QTY DESCRIPTION
(N) (01) BRANCH OF 08 MODULES CONNECTED IN PARALLEL PER BRANCH SOLAR PV MODULE 08 ZNSHINE SOLAR ZXM7-SH108 (400W) MODULES
(E) (44) YINGLI SOLAR YL360D-34D 1/2 (360W) MODULES
INVERTER 04 AP SYSTEMS DS3-S MICRO-INVERTERS
(E) (10) AP SYSTEMS QS1 MICRO-INVERTERS
600V, 55A MAX, 4 INPUTS, MOUNTED ON ROOF FOR WIRE &
(E) (03) AP SYSTEMS YC600 MICRO-INVERTERS JUNCTION BOXES 02
CONDUIT TRANSITION
(E) (02) BRANCHES OF 12 MODULES CONNECTED & (E) AC DISCONNECT 100A FUSED, VISIBLE, LOCKABLE, LABELED,
AC DISCONNECT 01
(E) (02) BRANCHES OF 10 MODULES CONNECTED IN PARALLEL PER BRANCH DISCONNECT SQUARE-D D323NRB, WITH (N) 90A FUSES, 240 VAC

PURELIGHT POWER
3521 AVION DRIVE STE 200,
(E) 03x AP SYSTEMS QS1 MICRO-INVERTERS WITH 10 PV MODULES IN BRANCH CIRCUIT #1 SYSTEM SIZE:- ((E) 44 x 360W + (N) 08 x 400W)/1000 = 19.04 kWDC MEDFORD, OR 97504
CSLB : 226333
SYSTEM SIZE:- 16.33 kWAC BI-DIRECTIONAL
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM
UTILITY METER
AC DISCONNECT SHALL BE LOCATED 1-PHASE, 3-W,
VERSION
WITHIN 10 FEET OF UTILITY METER 120V/240V, 60Hz
DESCRIPTION DATE REV

(03) AP SYSTEMS QS1 INITIAL RELEASE 07/21/2023 UR


MICRO-INVERTERS (240V)
(E) 02x AP SYSTEMS QS1 MICRO-INVERTERS WITH 08 PV MODULES &
(E) 02x AP SYSTEMS YC600 MICRO-INVERTERS WITH 04 PV MODULES IN BRANCH CIRCUIT #2 (E) METER MAIN
SERVICE PANEL, L
(E) 100A SOLAR LOAD 200A RATED,
CENTER 120/240V

(E) JUNCTION EXISTING


(E) PRODUCTION (E) 200A
BOX CONDUCTORS
(02) AP SYSTEMS QS1 (02) AP SYSTEMS YC600 METER SUB PANEL
MICRO-INVERTERS (240V) MICRO-INVERTERS (240V) (E) AC DISCONNECT 100A
FUSED, VISIBLE, LOCKABLE,
(E) 02x AP SYSTEMS QS1 MICRO-INVERTERS WITH 08 PV MODULES & LABELED, DISCONNECT (N) AC DISCONNECT 200A
20A LINE NON-FUSED, VISIBLE
(E) 01x AP SYSTEMS YC600 MICRO-INVERTER WITH 02 PV MODULES IN BRANCH CIRCUIT #3 L1 L1 SQUARE-D D323NRB, WITH LOCKABLE LABELED,
(N) 90A FUSES, 240 VAC DISCONNECT, 240 VAC
L2 L2
20A
(SQUARE-D DU324RB) 150A
(N) 90A FUSES
L1 L1 M
L2 L2
20A L1 L1 L1 L1
L2 L2
L2 L2 200A
L1 L1 20A LOAD N N
(02) AP SYSTEMS QS1 (01) AP SYSTEMS YC600 N N G
L2 L2
MICRO-INVERTERS (240V) MICRO-INVERTER (240V)
20A G PROJECT NAME
(E) 03x AP SYSTEMS QS1 MICRO-INVERTERS WITH 12 PV MODULES IN BRANCH CIRCUIT #4
L1 L1 LOAD SIDE
TAP

GOLD HILL, OR 97525 USA


L2 L2

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
LUG KIT
(3) #3 AWG THWN-2 (E) MAIN BREAKER
G
GEC
G
N (1) #6 AWG THWN-2 EGC 200A/2P, 240V
EXISTING
IN 1" EMT CONDUIT RUN GROUNDING

BRIAN MAXWELL
SYSTEM

APN# 10162612
12102 OR-234,
(03) AP SYSTEMS QS1
MICRO-INVERTERS (240V) (E) MAIN BREAKER
EXISTING WIRES EXISTING WIRES 150A/2P, 240V

(N) JUNCTION
BOX

(N) 08 x ZNSHINE SOLAR MODULES WITH 04 AP SYSTEMS DS3-S MICRO-INVERTERS IN BRANCH CIRCUIT #1
L1 L1

L2 L2 NOTE:- RACEWAY MAY BE SUBJECT TO CHANGE AT


G
TIME OF INSTALL BY QUALIFIED PERSONS
ACCORDING TO CHAPTER 3 OF THE NEC

(04) AP SYSTEMS DS3-S MINIMUM WIRE SIZES SPECIFIED.USE OF


MICRO-INVERTERS (240V) (1) #12 AWG CU THWN-2 + RED
(1) TRUNK CABLE (1) #12 AWG CU THWN-2 - BLACK LARGER WIRE IS ACCEPTABLE
TERMINATOR CAP ON LAST CABLE #6 BARE CU IN FREE AIR (1) #12 AWG CU THWN -2 EGC
CONNECTOR AC TRUNK CABLE (TYP) IN 3/4" EMT CONDUIT RUN VISIBLE, LOCKABLE, LABELED
DISCONNECT NOTES: AC DISCONNECT LOCATED
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH WITHIN 10' OF UTILITY METER
IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS
MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) NOTE: PV AC DISCONNECT LOCATED
INTERCONNECTION NOTES: 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY WITHIN 10' OF THE MAIN BILLING METER SHEET NAME
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH.
DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.54]. 3. FUSED AC DISCONNECT TO BE USED. SERVICE INFO. ELECTRICAL
3. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9], GROUNDING & GENERAL NOTES: LINE DIAGRAM
[NEC 230.95] AND [NEC 690.4] 1. A SECOND FACILITY GROUNDING ELECTRODE IS NOT REQUIRED PER [NEC 690.47(C)(3)] UTILITY PROVIDER: PACIFIC POWER
SHEET SIZE
4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 2. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. MAIN SERVICE VOLTAGE: 240V
5. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE 3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE MAIN PANEL BRAND: N/A ANSI B
BUSBAR RELATIVE TO THE MAIN BREAKER. 4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS MAIN SERVICE PANEL: (E) 200A
FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION.
11" X 17"
MAIN CIRCUIT BREAKER RATING: (E) 150A
ELECTRICAL LINE DIAGRAM 5. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE SHEET NUMBER

1 SCALE: NTS
FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
MAIN SERVICE LOCATION:
SERVICE FEED SOURCE:
NORTH-EAST
UNDERGROUND PV-5
RESERVED FOR AHJ
AC CONDUCTOR AMPACITY CALCULATIONS:
SOLAR MODULE SPECIFICATIONS
FROM JUNCTION BOX TO SOLARLOADCENTER:
ELECTRICAL NOTES
ZNSHINE SOLAR ZXM7-SH108 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED
MANUFACTURER / MODEL #
(400W)MODULES EXPECTED WIRE TEMP (°C): 36° FOR ITS APPLICATION.
TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
VMP 30.90V
# OF CURRENT CARRYING CONDUCTORS: 2 DEGREE C WET ENVIRONMENT.
IMP 12.95A CONDUIT FILL CORRECTION PER NEC 310.15(C)(1): 1.0 3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL
VOC 37.10V CIRCUIT CONDUCTOR SIZE: 12 AWG BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO
CIRCUIT CONDUCTOR AMPACITY: 30A THE NEAREST RIDGE, HIP, OR VALLEY.
ISC 13.70A
MODULE DIMENSION 67.87"L x 44.65"W x 1.18"D (In Inch) 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. PURELIGHT POWER
1.25 X # MICRO-INVERTERS (MAX. BRANCH LENGTH) X MAX OUTPUT 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. 3521 AVION DRIVE STE 200,
(N) INVERTER SPECIFICATIONS
CURRENT CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
MEDFORD, OR 97504
CSLB : 226333
MANUFACTURER / MODEL # AP SYSTEMS DS3-S 1.25 X 04 X 2.66A = 13.30A SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM
NOMINAL AC POWER 640W CODES AND STANDARDS.
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE VERSION
NOMINAL OUTPUT VOLTAGE 240 VAC 310.15(B)(1) DESCRIPTION DATE REV
NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
NOMINAL OUTPUT CURRENT 2.66A TEMP CORR. PER NEC TABLE 310.15(B)(1) X 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND INITIAL RELEASE 07/21/2023 UR
CONDUIT FILL CORR. PER NEC 310.15(C)(1) X
READILY VISIBLE.
CIRCUIT CONDUCTOR AMPACITY =
(E) INVERTER SPECIFICATIONS 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
0.91 X 1.0 X 30 = 27.30A
FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
MANUFACTURER / MODEL # HOYMILES HM-1200N
MANUFACTURER'S INSTRUCTION.
NOMINAL OUTPUT VOLTAGE 240 VAC
RESULT SHOULD BE GREATER THAN (9.98A) OTHERWISE LESS THE 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
NOMINAL OUTPUT CURRENT 5.00 ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE

(E) INVERTER SPECIFICATIONS AC CONDUCTOR AMPACITY CALCULATIONS:


MANUFACTURER / MODEL # HOYMILES HM-600N
FROMSOLARLOADCENTERTOINTERCONNECTION:
# OF INVERTERS: 17 ((N) 04-AP SYSTEMS DS3-S + (E) 10-HOYMILES
NOMINAL OUTPUT VOLTAGE 240 VAC
HM-1200N + 03-HOYMILES HM-600N)
NOMINAL OUTPUT CURRENT 2.46 EXPECTED WIRE TEMP (°C): 36°
TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91
# OF CURRENT CARRYING CONDUCTORS: 3 PROJECT NAME
AMBIENT TEMPERATURE SPECS CONDUIT FILL PER NEC 310.15(C)(1): 1.0
CIRCUIT CONDUCTOR SIZE: 3 AWG

GOLD HILL, OR 97525 USA


WEATHER STATION: MEDFORD ROGUE VALLEY INTL AP
CIRCUIT CONDUCTOR AMPACITY: 100A

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
RECORD LOW TEMP -8°
AMBIENT TEMP (HIGH TEMP 2%) 36° REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B):

BRIAN MAXWELL
1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT =

APN# 10162612
12102 OR-234,
CONDUIT HEIGHT RUN (IN ATTIC)
1.25 X (N) ((04 X 2.66) + (E) (10 x 5) + (03 x 2.46)) = 85.03A
CONDUCTOR TEMPERATURE RATE 90°
MODULE TEMPERATURE COEFFICIENT OF Voc -0.29%/°C DERATEDAMPACITYOFCIRCUITCONDUCTORSPERNECTABLE310.16:
NUMBER OF CURRENT
TEMP CORR. PER NEC TABLE 310.15(B)(1) X
PERCENT OF VALUES CONDUIT FILL CORR. PER NEC 310.15(C)(1) X
CARRYING CONDUCTORS IN EMT
.80 4-6 CIRCUIT CONDUCTOR AMPACITY =
0.91 X 1.0 X 115 = 104.65A
.70 7-9
.50 10-20 RESULT SHOULD BE GREATER THAN (85.03A) OTHERWISE LESS THE
ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY

VOLTAGE DROP CALCULATIONS


WIRE RUN # OF INV V (VOLTS) I (AMPS) L (FT) VD (%) WIRE SIZE* RACEWAY
SHEET NAME
BRANCH (MODULE) TO PASS THRU J. BOX 04 240 10.64 40 0.62% 12 AWG FREE AIR
ELECTRICAL
PASS THRU SOLAR J. BOX TO LOAD CENTER
(MAX BRANCH) 04 240 10.64 50 0.77% 12 AWG 3/4" EMT CALCULATION
LOAD CENTER TO AC DISCONNECT (E+N) 17 240 68.02 10 0.13% 3 AWG 1" EMT SHEET SIZE

AC DISCONNECT TO INTERCONNECTION (E+N) 17 240 68.02 10 0.13% 3 AWG 1" EMT ANSI B
MAX VOLTAGE DROP: 1.65% 11" X 17"
ELECTRICAL CALCULATION SHEET NUMBER

1 SCALE: NTS PV-6


RESERVED FOR AHJ
! WARNING DUALPOWERSOURCE
2
SECONDSOURCEISPHOTOVOLTAICSYSTEM

LABEL LOCATION:
12
! WARNING 8
SOLAR PV SYSTEM EQUIPPED
POINT OF INTERCONNECTION
PRODUCTION METER PHOTOVOLTAIC SYSTEM WITH RAPID SHUTDOWN
NEC 705.12(C) & NEC 690.59 COMBINER PANEL
DO NOT ADD LOADS
TURNRAPIDSHUTDOWN
SWITCHTOTHE"OFF" PURELIGHT POWER
NEC 690.15(B) : AC COMBINER PANEL SOLAR ELECTRIC 3521 AVION DRIVE STE 200,
POSITIONTOSHUTDOWN PV PANELS MEDFORD, OR 97504
CSLB : 226333
PVSYSTEMANDREDUCE PHONE: (541) 816-4047
SHOCKHAZARDINTHE EMAIL: ADMIN@PURELIGHTPOWER.COM
PHOTOVOLTAIC SYSTEM ARRAY. VERSION

6
! AC DISCONNECT !
ELECTRIC SHOCK HAZARD
RAPID SHUTDOWN DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

RATED AC OUTPUT CURRENT 65.56A


NOMINAL OPERATING CURRENT 240V
10
FOR SOLAR PV LABEL LOCATION:

LABEL LOCATION: SYSTEM ON OR NO MORE THAT 1 M (3 FT) FROM THE


SERVICE DISCONNECTING MEANS TO WHICH THE
AC DISCONNECT, PHOTOVOLTAIC SYSTEM LABEL LOCATION: PV SYSTEMS ARE CONNECTED.
POINT OF INTERCONNECTION UTILITY SERVICE ENTRANCE/METER, INVERTER/DC PER CODE: NEC 2020 : IFC 605.11.3.1(1) & 690.56(C)
(PER CODE: NEC 2020.690.54 & 690.13(B) DISCONNECT IF REQUIRED BY LOCAL AHJ, OR
OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
PER CODE(S): NEC 2020: 690.56(C)(2)

MAIN PHOTOVOLTAIC
9
SYSTEM DISCONNECT
LABEL LOCATION: 11
PARALLEL
MAIN SERVICE DISCONNECT / UTILITY METER
(PER CODE: NEC 690.13(B)) GENERATION ON SITE PROJECT NAME

GOLD HILL, OR 97525 USA


LOCATION: AT UTILITY SERVICE METER

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
METER MAIN SERVICE PANEL
SOLAR LOAD CENTER -
IF USED TO COMBINE
2
PV OUTPUT CIRCUITS
11
SUB PANEL
8

NOTES AND SPECIFICATIONS: 2


NON-FUSED AC FUSED AC 12
· SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE DISCONNECT DISCONNECT
2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS DIRECTORY
ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE
6 SHEET NAME
LOCAL AHJ.
9
· SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS 9 JUNCTION BOX
USING EFFECTIVE WORDS, COLORS AND SYMBOLS.
· LABELS SHALL BE PERMANENTLY AFFIXED TO THE
OR COMBINER BOX WARNING LABELS
10
EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND
WRITTEN. SHEET SIZE
· LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND
THE ENVIRONMENT INVOLVED.
ANSI B
· SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, 11" X 17"
PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE
SPECIFIED. SHEET NUMBER
· DO NOT COVER EXISTING MANUFACTURER LABELS.
LABELING DIAGRAM: PV-7
CAUTION MULTIPLE SOURCES OF POWER !
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN
AT: UTILITY METER AND MAIN SERVICE PANEL,
PV RAPID SHUTDOWN

MAIN RAPID SHUTDOWN

UTILITY METER AND


MAIN SERVICE PANEL

4
-23
OR
02
121

PV RAPID SHUTDOWN

PV MODULES TYP.
RESERVED FOR AHJ
1. EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT PER
MANUFACTURER'S REQUIREMENTS. ALL SOLAR MODULES, EQUIPMENT, AND METALLIC
COMPONENTS ARE TO BE BONDED. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CAN
NOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE.
PURELIGHT POWER
2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF NATIONAL ELECTRICAL 3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CODE. LABEL SHALL BE METALLIC OR PLASTIC, ENGRAVED OR CSLB : 226333
PHONE: (541) 816-4047
MACHINE PRINTED IN A CONTRASTING COLOR TO THE PLAQUE. PLAQUE SHALL EMAIL: ADMIN@PURELIGHTPOWER.COM

BE UV RESISTANT IF EXPOSED TO SUNLIGHT. VERSION


DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR


3. AC CONDUCTORS SHALL BE RUN IN EMT AND SHALL BE LABELED, "CAUTION AC CIRCUIT" OR
EQUIV. EVERY 5 FT.

4. EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE


GROUNDED IN ACCORDANCE WITH 250.134 OR 250.138(A).

5. CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE PRIOR TO CONNECTING INVERTER.
VERIFY SERVICE VOLTAGE IS WITHIN INVERTER VOLTAGE OPERATIONAL RANGE.

6. OUTDOOR EQUIPMENT SHALL BE NEMA-3R RATED OR BETTER.

PROJECT NAME
7. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT
RUNS AS REQUIRED PER NEC.

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
8. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED
AND LISTED FOR SUCH USE, AND FOR ROOF-MOUNTED SYSTEMS, WIRING MUST BE

BRIAN MAXWELL

APN# 10162612
12102 OR-234,
PERMANENTLY AND COMPLETELY HELP OFF OF THE ROOF SURFACE. NEC 110.2 - 110.4 / 300.4

9. ALL ROOF PENETRATIONS MUST BE FLASHED. SIMPLY CAULKING DOES NOT SUFFICE.

SHEET NAME

ADDITIONAL
NOTES
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-8
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-9
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-10
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-12
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-13
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-14
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-15
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-16
RESERVED FOR AHJ
PURELIGHT POWER
3521 AVION DRIVE STE 200,
MEDFORD, OR 97504
CSLB : 226333
PHONE: (541) 816-4047
EMAIL: ADMIN@PURELIGHTPOWER.COM

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 07/21/2023 UR

PROJECT NAME

GOLD HILL, OR 97525 USA

UTILITY: PACIFIC POWER


AHJ: JACKSON COUNTY
BRIAN MAXWELL

APN# 10162612
12102 OR-234,
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-17