Professional Documents
Culture Documents
Date of Performance:02/12/2023
Date of Submission: 10/02/2024
Submitted by:
Name: Md Refat khan
ID:2006131
Level:3 Term:1
Department: EEE
Section: c1
Objectives:
1. In this experiment, fault analysis for a test network will be
performed.
2. CYMEPSAF software will be used for this purpose.
Circuit Diagram:
Bus03:
Bus04:
Bus05:
Bus06:
Observation for different fault situation(Bus01):
Line currents in all three phases are illustrated as faulty Bus Current Report.
LLL fault: Here at bus 1, Io, I1, I2 are same. This value is zero. This means that the three
phases are currently not supplying any load.
LG fault: Io= I1=I2=2461.84 ∠-85.631. This means that the three phases fault current is
flowing from phase to neutral.
LL fault: |I1| ~ |I2| and |Io| ~ 0. I1 and I2 are almost 180° apart in phase. I1 = 3529.9672∠-
85.0516 A and I2 = 3529.9672∠94.9483 A.
LLG fault: I0 = 2579.7616∠93.177 A, I1 = 4819.67∠-85.36 A and I2 =2240.51∠95.62
Observation of First Ring Contributor G2 for B2:
The first ring contributions are fault currents from connections directly adjacent to
the fault bus. Three the ring contributions are observed for defect at bus 2. In the
simulation, G2 was added as a Voltage Controlled source in the system, and it was
in Yg configuration, signifying solidly grounded with the neutral line. As a
consequence, the generator neutral current is zero for all four conditions.
LLL fault: A balanced fault current flow through all A and C phases is observed.
LG fault: All currents are identically same.
LL fault: Currents of equal magnitude but contrary phases run through phases B and C
just as seen in the Bus.
LLG fault: Lines B and C are shorted.
Observation of First Ring Contributor L32 and L52:
LLL fault: For both lines, balanced fault current is observed to flow into all three phases.
LG fault: All phase currents are equal in magnitudes with phases 0, -90and 0 respectively
for phase sequence A, B and C for both lines.
LL fault: Similar to LG fault.
LLG fault: Exactly identical to LL.
Observation of faulted bus voltage report:
LLL fault: All phase voltages have identical zero values for obvious reasons.
LG fault: A,B and C phases has 180,0,180 phase angles
LL fault: Phase A is unaltered, but per unit voltage magnitude for other two phases drop
to 0.5 with phase angles 0 for each.
LLG fault: Per unit voltage for phase A,B,C are 0.5.
2.Fault analysis for sliding fault at different locations on different lines
LINE14 for 5%:
LINE14 for95%:
Discussion:
In this experiment we simulated different types of fault conditions and observed the fault
voltages and fault currents. Later, we compared it with theoretical calculations and the
results were pretty similar to the PSAF reports. The power of system must be able to
withstand all types of faults except the permanent ones. For example, for LG fault due to
storm or timber fall, manual repairing of the system is the only solution. In the other cases,
we have to design the circuit breakers and the other protective equipment accordingly.