Professional Documents
Culture Documents
Submitted By:
Abdul Ahad
Abdul Wahab
Mian Sajawal Shah
BSEE 2016-2020
Semester 8
Instructor: Dr. Naeem Iqbal
Course: Power System Operation & Control
Date: June 13, 2020
Objectives
The objectives of this lab are:
• User different components of SIMPOWERSYSTEM
• Observe the fault severity
• Select suitable position for protective and measurement devices
Theory
In any power system there are many faults, like short circuit fault, open circuit fault etc. These
faults may occur in phases, phase to ground, transformer faults, generator faults, bus bar faults,
induction motor faults etc. Electrical networks, machines and equipments are often subjected to
various types of faults while they are in operation. When a fault occurs, the characteristic values
(such as impedance) of the machines may change from existing values to different values till the
fault is cleared. There are eleven types of faults between phase(s) and ground. Some of them will
be introduce here in this lab using MATLAB Simulink and the behavior of the power system will
be observed. The circuit to be simulated is shown below in figure (1)
There are mainly two types of faults in the electrical power system. Those are symmetrical and
unsymmetrical faults.[1]
Symmetrical faults
These are very severe faults and occur infrequently in the power systems. These are also called
balanced faults and are of two types namely line to line to ground (L-L-L-G) and line to line (L-
L-L).
Only 2-5 percent of system faults are symmetrical faults. If these faults occur, the system remains
balanced but results in severe damage to the electrical power system equipment.
Unsymmetrical faults
These are very common and less severe than symmetrical faults. There are mainly three types
namely line to ground (L-G), line to line (L-L), and double line to ground (LL-G) faults.
The line to ground fault (L-G) is the most common fault and 65-70 percent of faults are of this
type. It causes the conductor to make contact with the earth or ground. 15 to 20 percent of faults
are double line to ground and causes the two conductors to make contact with the ground. The line
to line fault occurs when two conductors make contact with each other mainly while swinging of
lines due to winds and 5- 10 percent of the faults are of this type.[1]
Procedure
• Open MATLAB
• Open SIMULINK Library or write Simulink in command prompt and press ENTER
• Select new model or press Ctrl+N By using commonly used blocks, Simulink->Sources
• and Simscap ->. SimPowerSystems, draw the above diagram
• For Three phase source, use values given in following figure (2)
• Make three phase circuit breaker’s initial state as closed and put 100sec as switching time
• In order to configure three phase series load, use following figure (3)
Task
1. In this task we introduced line to ground fault in only phase A in duration of 3 to 3.5sec and
observed the voltage at load terminal and current through the load. This can be seen from
below figure (4) and figure (5).
Figure 4. Voltage at Load Terminal
2. In this task we introduced line to line fault between phase B and C in duration of 2 to 3 sec
and observed the voltage at load terminal and current through the load. This can be seen
from below figure (6) and figure (7).
Figure 6. Voltage at Load Terminal
3. In this task we introduced three phase fault between phase A, B and C in duration of 3.5 to
3.8sec and observed the voltage at load terminal and current through the load. This can be
seen figure (8) and figure (9).
Figure 8. Voltage at Load Terminal
Conclusion
From this simulation based experiment we have concluded that when phase to ground or intra
phase fault occurs in any power system current increases from its normal value and voltage drops
at the load terminal.
References
[1] https://www.elprocus.com/what-are-the-different-types-of-faults-in-electrical-power-systems/