CIRCUIT LOAD SIZE OF WIRE VOLTAGE WATTS AMPERE CIRCUIT SIZE OF WIRE

NO. DESCRIPTION LOAD BREAKER


PROTECTION

SWITCHES LO CO AU POLE AT
1 LIGHTING OUTLET 1 6 230 600 2.61 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
2 LIGHTING OUTLET 1 9 230 900 3.91 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
3 LIGHTING OUTLET 1 8 230 800 3.48 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
4 LIGHTING OUTLET 1 2 230 200 0.87 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
5 LIGHTING OUTLET 1 9 230 900 3.91 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
6 LIGHTING OUTLET 1 6 230 600 2.61 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
7 LIGHTING OUTLET 1 2 230 200 0.87 2P 15A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
8 CONVENIENCE OUTLET 3 230 600 2.61 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
9 CONVENIENCE OUTLET 6 230 1200 5.22 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
10 CONVENIENCE OUTLET 4 230 1080 4.69 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
11 CONVENIENCE OUTLET 2 230 1260 5.48 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
12 CONVENIENCE OUTLET 3 230 540 2.35 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
13 CONVENIENCE OUTLET 4 230 540 2.35 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
14 CONVENIENCE OUTLET 3 230 1080 4.70 2P 20A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
RANGE 1 230 3500 15.22 2P 30A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
5 HP, ACU 1 230 3729 16.21 2P 40A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
5 HP, ACU 1 230 3729 16.21 2P 40A 2-2.00MM 2 THHN STRANDED COPPER WIRE, 15MM FCP
TOTAL 21458 93.3

COMPUTATION
A. SIZE OF MAIN FEEDER B. SIZE OF MAIN PROTECTION
=(IT + 25% OF HIGHEST MOTOR LOAD)xDF =(IT + 25% OF HIGHEST MOTOR LOAD)xDF
=(93.3 + (0.25x16.21)x0.80 =(93.3-16.21) + (2.5 x 16.21) + 0.80
=96.542 =118.415
USE: 2-22MM2 THW, STRANDED COPPER
WIRE, 1-2MM2 THW, GROUNDWIRE

SCHEDULE OF LOADS & COMPUTATION


SCALE NTS.

CIVIL ENGINEERING DEPARTMENT DESIGNERS/OWNERS: PROJECT TITLE: CHECKED AND VERIFIED BY: REVISIONS:
NO. DESCRIPTION: REVISED BY: APPROVED BY: DATE:
SHEET NO.

ALLEN RAFAEL VIOS


UNIVERSITY OF SCIENCE AND ELECTRICAL PLAN ENGR. WILLIE D. TAN JR. 02
YEAR: THIRD YEAR DATE SUBMITTED: INSTRUCTOR
TECHNOLOGY OF SOUTHERN PHILIPPINES SECTION: BSCE 3E OCTOBER/ - / 2023 LOCATION / ADDRESS: