You are on page 1of 14

Doc. No.

: 26071-100-V1A-J001-10619

Job No. : 26071 Rev.001

HIPPS SYSTEM INTERNAL WIRING


DIAGRAM FOR ISH-106
PROJECT : Engineering, Procurement and Construction (EPC) Inside
Battery Limits (ISBL) and Outside Battery Limits (OSBL) for
the Refinery Development Master Plan (RDMP) Project
RU V Balikpapan
LOCATION : Refinery Unit V Balikpapan, East Kalimantan,Indonesia
OWNER : PT PERTAMINA (Persero)
PO NO. : 26071-100-POA-J000-00001

001 25 JUL 22 ISSUED FOR CONSTRUCTION P.E. BADVE K.J.LEE I.S.KANG

000 01 MAR 22 ISSUED FOR CONSTRUCTION P.E. BADVE K.J.LEE I.S.KANG

00A 16 DEC 21 ISSUED FOR APPROVAL P.E. BADVE H.R.KIM I.S.KANG

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED


Doc. No. : 26071-100-V1A-J001-10619

Job No. : 26071 Rev.001

REVISION LOG

REV.
REV. DATE REVISED PAGE DESCRIPTION
NO.
00A 16 DEC 21 - ISSUED FOR APPROVAL
000 01 MAR 22 - ISSUED FOR CONSTRUCTION
001 25 JUL 22 - ISSUED FOR FINAL
HIPPS SYSTEM INTERNAL WIRING
DIAGRAM FOR ISH-106

RDMP RU V BALIKPAPAN

RDMP BALIKPAPAN JO

PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA

HIPPS SYSTEM INTERNAL WIRING


DIAGRAM FOR ISH-106
INDEX

REVISION
SHEET DRAWING CONTENTS
NO. 00A 000 001

01 COVER SHEET X
02 INDEX X
03 LEGEND SHEET X
04 COMPONENT NAMING PHILOSOPHY X
05 CPH-I106-001 : HIPPS SYSTEM CABINET AC POWER DISTRIBUTION (UPS) (CH_0601,UNIT-059) X
06 CPH-I106-001 : HIPPS SYSTEM CABINET AC POWER DISTRIBUTION (NON UPS) (CH_0601,UNIT-059) X
07 CPH-I106-001 : HIPPS SYSTEM CABINET 24VDC POWER DISTRIBUTION (CH_0601,UNIT-059) X
08 CPH-I106-001 : HIPPS SYSTEM CABINET 24VDC POWER DISTRIBUTION (CH_0601,UNIT-059) X
09 CPH-I106-001 : HIPPS SYSTEM CABINET IO MODULE COMMUNICATION WIRING (CH_0601,UNIT-059) X
10 CPH-I106-001 : HIPPS SYSTEM CABINET CONTROLLER COMMUNICATION WIRING (CH_0601,UNIT-059) X
11 CPH-I106-001 : HIPPS SYSTEM CABINET ALARM WIRING (CH_0601,UNIT-059) X
12 CPH-I106-001 : HIPPS SYSTEM CABINET GROUND WIRING (CH_0601,UNIT-059) X

RDMP RU V BALIKPAPAN

RDMP BALIKPAPAN JO

PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA

HIPPS SYSTEM INTERNAL WIRING


DIAGRAM FOR ISH-106
LEGEND SHEET

ABBREVIATION SYMBOLS

AC : ALTERNATING CURRENT ISH : INSTRUMENTATION SATELLITE HOUSE


FAN POWER DISTRIBUTION BOARD
AI : ANALOG INPUT LB : LEFT BLOCK
AI-R : ANALOG INPUT REDUNDANT LS : LIMIT SWITCH FOR LIGHT
AIO : ANALOG INPUT / OUTPUT LT : LIGHT (LED LAMP)
INLET FILTER
AIO-R : ANALOG INPUT / OUTPUT REDUNDANT MB : MIDDLE BLOCK BUSBAR
AO : ANALOG OUTPUT MCC : MOTOR CONTROL CENTER
AO-R : ANALOG OUTPUT REDUNDANT MOD : MODULE / MODEL
BB : BUS BAR NIS : NON INTRINSIC SAFE
A3 SIZE DOCUMENT HOLDER
BK : BLACK NO : NORMALLY OPEN
BLU : BLUE NON-RED : NON REDUNDANT POWER SUPPLY AC110V TO DC24V, 24A
BPCS : BASIC PROCESS CONTROL SYSTEM (P) : PRIMARY 55

1 2 3 4 5 6 7
45
35

25

THERMOSTAT
15
5

BRN : BROWN P/S : POWER SUPPLY AC 110 V TO DC 24 V


C : COMMON PDB : POWER DISTRIBUTION BOARD

- +

- +
C300 : HONEYWELL BPCS CONTROLLER PE : PROTECTIVE EARTH
C9 : CONTROL FIREWALL PR : PORT MOXA ETHERNET SWITCH
POWER SUPPLY AC110V TO DC24V, 50A
CAB : CABINET R : REAR

CB : CIRCUIT BREAKER RB : RIGHT BLOCK


CD : CONTROLLER BPCS RD : RED
DC : DIRECT CURRENT RED. : REDUNDANT
S300 CONTROLLER
DI : DIGITAL INPUT (S) : SECONDARY
DI-R : DIGITAL INPUT REDUNDANT SIS : SAFETY INSTRUMENTED SYSTEM
UTILITY SOCKET, 220VAC, 13A
SP : SURGE PROTECTOR
DO : DIGITAL OUTPUT
TB : TERMINAL BLOCK
DO-R : DIGITAL OUTPUT REDUNDANT
TBAC : TERMINAL BLOCK FOR AC POWER
ENG : ENGINEERING UNIVERSAL IOTA
TBAL : TERMINAL BLOCK FOR ALARM STP
ESW : ETHERNET SWITCH
TELD : TERMINATION EARTH LEAK DETECTION
ETH : ETHERNET
THT : THERMOSTAT
F : FRONT
UIO : UNIVERSAL INPUT OUTPUT
FTE : FAULT TOLERANT ETHERNET FIBER OPTIC
UKS : UTILITY SOCKET DIGITAL IOTA
G/Y : GREEN/YELLOW
UPS : UNINTERRUPTIBLE POWER SUPPLY
GRN : GREEN
WHT/GRN : WHITE / GREEN
GRN/BRN : GREEN / BROWN
HIPPS : HIGH INTEGRITY PRESSURE PROTECTION SYSTEM
KEY SWITCH
I/O : INPUT OUTPUT WHT/PNK : WHITE/PINK
IOTA : INPUT/OUTPUT TERMINAL ASSEMBLY XXX_SP : WIRED SPARE
IS : INTRINSIC SAFE XXX_UW : UNWIRED SPARE CIRCUIT BREAKER

LIGHT
RDMP RU V BALIKPAPAN
PROTECTIVE EARTH(PE)
RDMP BALIKPAPAN JO
TERMINAL BLOCK FOR AC POWER
PT PERTAMINA
TERMINAL BLOCK FOR ALARM BALIKPAPAN, INDONESIA
PERTAMINA

SURGE PROTECTOR
HIPPS SYSTEM INTERNAL WIRING
Westermo
SDW-550EC
DIAGRAM FOR ISH-106
LINK

PWR
5 4

1
3

2
WESTERMO ETHERNET SWITCH
DPX

1
SPD
DPX

2
SPD
DPX

3
SPD
COMPONENT NAMING PHILOSOPHY

NOTE
1. S300 Naming Rule [A][B]_[CC][DD]
Component Type Example Remark [A]: C= Control, follow 26071-100-3DP-G03-00008 'Component Identifcation'
S300 Controller CS_2101 Naming with note.1 [B]: S= SIS, F=FGS, H=HIPPS, follow 26071-100-3DP-G03-00008 'Compnent Identifcation'
Universal IO CS210101U Naming with note.2 [CC]: Building No. / 01= ISH-101, 02 = ISH-102, 03= ISH-103, 04 = ISH-104, 05 = ISH- 105,
Digital IO CD210104D Naming with note.2 06 = ISH-106, 07= ISH-107, 08 = ISH-108, 09 = ISH-109, 10 = ISH-110, 15 = ISH- 115,
Power Supply F-PWR01 Naming with note.3 16 = ISH-116, 13= SS-113, 14= SS-114, 21= MCR, 22= UCR, 23= OCR, 24= BPP-1, 25= HSSE
[DD]: S300 Node No.
Thermostat F-THT01 Naming with note.3
Cabinet Light F-LT01 Naming with note.3
Naming with note.3 2. SIS/FGS/HIPPS IO Module Naming Rule [A][B][CC][DD][EE][FFF]
DC Circuit Breaker F-ACCB01
[A]: C= Control, follow 26071-100-3DP-G03-00008 'Compnent Identifcation'
AC Circuit Breaker F-DCCB01 Naming with note.3
[B]: S= SIS, F=SIS, H=HIPPS, follow 26071-100-3DP-G03-00008 'Compnent Identifcation'
FAN F-FAN01 Naming with note.3
[CC]: Building No. / 01= ISH-101, 02 = ISH-102, 03= ISH-103, 04 = ISH-104, 05 = ISH- 105,
AC Terminal Block F-TBAC01 Naming with note.3 06 = ISH-106, 07= ISH-107, 08 = ISH-108, 09 = ISH-109, 10 = ISH-110, 15 = ISH- 115,
DC Terminal Block F-TBDC01 Naming with note.3 16 = ISH-116, 13= SS-113, 14= SS-114, 21= MCR, 22= UCR, 23= OCR, 24= BPP-1, 25= HSSE
Alarm Terminal Block F-TBAL01 Naming with note.3 [DD]: S300 Node No.
[EE]: IOM No.
[FFF]: U=UIO Redundant, D=Digital IO Redundant

3. Naming Rule [A]-[BBBB][CC]


[A]: F= Front, R= Rear
[BBBB]: THT= Thermostat, LT= Cabinet Light, DCCB= DC Power Circuit Breaker,
ACCB= AC Power Circuit Breaker, FAN= FAN, PWR= Power Supply, TBAC= AC Terminal Block,
TBDC= DC Terminal Block, TBAL= Alarm Terminal Block
[CC]: Serial No.

RDMP RU V BALIKPAPAN

RDMP BALIKPAPAN JO

PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA

HIPPS SYSTEM INTERNAL WIRING


DIAGRAM FOR ISH-106
CPH-I106-001 CPH-I106-001

CPH-I106-001 : HIPPS SYSTEM CABINET AC POWER DISTRIBUTION (UPS)


(CH_0601,UNIT-059)

FROM CBP-I106-001F FROM CBP-I106-001R


F-ACCB11 R-ACCB11
F-TBL01 (11L,11N) R-TBL01 (11L,11N)
1PH, UPS(P) 1PH, UPS(S)
110 VAC 50HZ 110 VAC 50HZ
L N L N

F-TBAC01 F-TBAC02
1L 1N 1PE 2.5SQ G/Y 1L 1N 1PE 2.5SQ G/Y
6SQ 6SQ 6SQ TO SHEET NO. 6 6SQ 6SQ 6SQ TO SHEET NO. 6
BRN BLU G/Y PE BRN BLU G/Y PE

1 3 PE 1 3 PE

F-ACCB01 (10A) F-ACCB02 (10A)

2 4 PE 2 4 PE
BRN

BRN
BLU

BLU
G/Y

G/Y
3x1.5 3x1.5
(3xA14) (3xA14)

3 3
F-PWR01 F-PWR02
93 - 253 VAC 93 - 253 VAC
~ ~

= =
24 VDC 24 VDC
- + - +
RD

RD
BK
BK

RDMP RU V BALIKPAPAN
PDC-PSU24

PDC-PSU24
RDMP BALIKPAPAN JO

PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA
RD
RD

BK
BK

+ HIPPS SYSTEM INTERNAL WIRING


F-DCBB01 24VDC BUSBAR TO SHEET DIAGRAM FOR ISH-106
24VDC NO. 7 , 8
-
NOTES-
1.
CPH-I106-001 : HIPPS SYSTEM CABINET AC POWER DISTRIBUTION (NON UPS) CABLE COLOR CODE FOR L,N,PE AS BELOW
L : BROWN
N : BLUE
(CH_0601,UNIT-059) PE : GREEN/YELLOW
2.
FRONT REAR PANEL GROUNDING FROM
FRONT, REAR, DOOR & SIDE PANEL
3.
FRONT DOOR REAR DOOR GROUND BUSBAR SPECIFICATION
F-FAN01 F-LT01 R-LT01 R-FAN01 a. 5mm THICK X 20mm WIDE.
b. THREADED WITH M6 SCREW HOLES.
NOTE-1 c. BOLT EQUIPPED TO CONNECT 35 SQ mm
NOTE-1
CABLE
L N E L N E

NOTE-1 F-TB1 NOTE-1 R-TB1

TO R-TBAL01 (5&6) TO R-TBAL01 (7&8)


(SHEET NO. 11 ) (SHEET NO. 11 )
R-LS01
F-LS01 4 3
4 3

2.5 Sq.mm x 3 Core (BRN/BLU/GY )

2.5 Sq.mm x 3 Core (BRN/BLU/GY )

2.5 Sq.mm x 3 Core (BRN/BLU/GY )


2.5 Sq.mm x 3 Core (BRN/BLU/GY )

R-TBAC01
FROM 2.5SQ BRN BRN
1 R-ACCB01 2
CBP-I106-004R AC220V 1L 2.5SQ BLU BLU
NON UPS FEEDER 3 (1A) 4
R-ACCB03 50HZ 1N G/Y
PE PE
R-TBL01 (3L,3N) 2.5SQ BRN BRN
1 R-ACCB02 2
2L 2.5SQ BLU BLU
3 (1A) 4
2N PE PE
G/Y
2.5SQ BRN BRN
1 R-ACCB03 2
3L 2.5SQ BLU BLU
3 (1A) 4
3N G/Y
PE PE
2.5SQ BRN BRN
1 R-ACCB04 2
4L 2.5SQ BLU BLU
3 (1A) 4
4N G/Y
PE PE
2.5SQ BRN BRN
R-UKS01
1 R-ACCB05 2
5L 2.5SQ BLU BLU 2.5 Sq.mm x 3 Core
3 (1A) 4
BRN/BLU/GY
5N G/Y
PE PE R-UKS02
2.5SQ BRN BRN
1 R-ACCB06 2
6L 2.5SQ BLU (1A) BLU 2.5 Sq.mm x 3 Core
3 4
BRN/BLU/GY RDMP RU V BALIKPAPAN
6N G/Y
PE PE
2.5SQ G/Y
1PE
RDMP BALIKPAPAN JO
2.5SQ G/Y
2PE
2.5SQ G/Y PT PERTAMINA
3PE BALIKPAPAN, INDONESIA
PERTAMINA
2.5SQ G/Y
4PE
2.5SQ G/Y
HIPPS SYSTEM INTERNAL WIRING
5PE DIAGRAM FOR ISH-106
6SQ G/Y

6SQ G/Y
FROM SHEET NO 5 6SQ G/Y 2.5SQ G/Y TO EXTERNAL
6SQ G/Y 6PE
PROTECTIVE EARTH(PE)
CABINET FRAME 6SQ G/Y 35SQ G/Y
NOTE-3
VISIBLE CONNECTION
NOTE-2 PE PE NOTE-3
CPH-I106-001 CPH-I106-001

CPH-I106-001 : HIPPS SYSTEM CABINET 24VDC POWER DISTRIBUTION


(CH_0601,UNIT-059)

F-DCBB01
24VDC BUSBAR
24VDC

FROM SHEET
NO. 5

RD

BK

RD

BK
PDC-MBMB-1

PDC-MBMB-1
RD

BK

RD

BK
R-UCAR01 R-UCAR02

+24V COM +24V COM

FC-MCAR-02 FC-MCAR-02

2.5 SQ G/Y
PE +24V COM

RDMP RU V BALIKPAPAN

FC-MCAR-02 RDMP BALIKPAPAN JO

PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA

HIPPS SYSTEM INTERNAL WIRING


2.5 SQ G/Y
PE
DIAGRAM FOR ISH-106
CPH-I106-001 CPH-I106-001

NOTE
1. PDC-FTA24P HAVE 2 CORE CABLES WITH
1.5SQ RED AND BLACK INSIDE.
CPH-I106-001 : HIPPS SYSTEM CABINET 24VDC POWER DISTRIBUTION
(CH_0601,UNIT-059)

FROM SHEET NO. 5 FROM SHEET NO 5


F-DCBB01 F-DCBB01
24VDC 24VDC
+ - + -

PDB-0824P F-PDB01 F-PDB02

F-ESW01 F-ESW02
F1 F1
+ +VA SDW-550 EC + +VA SDW-550 EC
RD NOTE 1 RD RD RD
2T ETHERNET 2T ETHERNET
Out1 PDC-FTA24P SWITCH Out1 PDC-FTA24P SWITCH
- COM - COM
BK BK BK BK

2.5 2.5
(A14) (A14)
PE PE
PE PE

F-ESW03 F-ESW03
F2
+ V1+ MOXA EDS-316 V1+ MOXA EDS-316
2T RD RD F2
V2+ SERIES + V2+ SERIES
Out2 RD RD
PDC-FTA24P ETHERNET 2T ETHERNET
- V1- SWITCH V1- SWITCH
BK BK Out2 PDC-FTA24P
V2- - V2-
+ + BK BK
RD RD RD RD
In In
PDC-MB24-1P 2.5 PDC-MB24-1P 2.5
- (A14) - (A14)
BK BK BK BK
PE PE
PE PE

F-ESW04 F-ESW04
F3
+ V1+ MOXA EDS-316 V1+ MOXA EDS-316
2T RD RD F3
V2+ SERIES + V2+ SERIES
Out3 RD RD
PDC-FTA24P ETHERNET 2T ETHERNET
- V1- SWITCH V1- SWITCH
BK BK Out3 PDC-FTA24P
V2- - V2-
BK BK

2.5 2.5
(A14) (A14)
PE PE
PE PE

F4 F4 RDMP RU V BALIKPAPAN
+ +
2T 2T
Out4 Out4
- - RDMP BALIKPAPAN JO

PT PERTAMINA
(OUTPUTS 1 thru 4) (OUTPUTS 1 thru 4)
PERTAMINA
BALIKPAPAN, INDONESIA
FUSE RATING FUSE RATING
(ALL FUSES) (ALL FUSES)
MAX. 2AT MAX. 2AT HIPPS SYSTEM INTERNAL WIRING
DIAGRAM FOR ISH-106
CPH-I106-001 CPH-I106-001

NOTE
1. CCI-HSE-XX-XX
CPH-I106-001 : HIPPS SYSTEM CABINET IO MODULE COMMUNICATION WIRING RD : RED CAP
BU : BLUE CAP
20 : 2M

(CH_0601,UNIT-059) 30 : 3M
60 : 6M

- FOR STP ETHERNET CABLE


F-ESW03 F-ESW04
EDS-316-SS-SC-HPS EDS-316-SS-SC-HPS

1 1
CCI-HSE-30 -RD J1
CH060101U J2 CCI-HSE-30 -BU
(Red) (Blue)
TUIO11 (NOTE 1)

2 2
CCI-HSE-20 -RD J1
CH060102U J2 CCI-HSE-20 -BU
(Red) (Blue)
TUIO11
3 3
CCI-HSE-20 -RD J1
CH060103U J2 CCI-HSE-20 -BU
(Red) (Blue)
TUIO11
4 4
CCI-HSE-30 -RD J1
CH060104D J2 CCI-HSE-30 -BU
(Red) (Blue)
TDIO11
5 5
CCI-HSE-30 -RD J1
CH060105D J2 CCI-HSE-30 -BU
(Red) (Blue)
TDIO11
6 6

7 7

8 8

9 9

10 SPARE SPARE 10

11 11

12 12

13 13

14 14 RDMP RU V BALIKPAPAN
CCI-HSE-20 -RD Pr-A Pr-A CCI-HSE-20 -BU
(P) CH_0601 (S)

RDMP BALIKPAPAN JO
REFER SHEET NO. 10 FOR THE DETAIL VIEW
15 15
PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA

16 16
HIPPS SYSTEM INTERNAL WIRING
DIAGRAM FOR ISH-106
CPH-I106-001 CPH-I106-001

FOR FTE LAN


WESTERMO DIP SWITCH SETTING (100MBIT/S)

CPH-I106-001 : HIPPS SYSTEM CABINET CONTROLLER COMMUNICATION WIRING ON


F-ESW01
ON

S1 S2

(CH_0601,UNIT-059) OFF
1 2 3
OFF
4 5

F-ESW02
ON ON

S1 S2

OFF OFF
1 2 3 4 5

CH_0601 (SM-SC IOTA :FC-TCNT11) NOTE


1. "FS-CCI-HSE-02" STP ETHERNET CABLE WITH
FTE-A FTE-B ETH-1 ETH-2 Pr-A Pr-B FTE-A FTE-B ETH-1 ETH-2 Pr-A Pr-B
2 METER LENGTH AND YELLOW, GREEN CAP
(S) (P)

STP CABLE
(FS- CCI-HSE-20)
TO
RED
F-ESW03 PORT 14
BLUE TO SHEET NO. 9
F-ESW04 PORT 14

STP CABLE STP CABLE (ETHERNET INTERFACE)


(FS- CCI-HSE-02) (FS- CCI-HSE-02) STP CABLE
F-ESW01
YELLOW
1 CEN-I106-L201Y PORT 11X (FTE SWITCH-Y)
4
2 IN NETWORK CABINET
YELLOW 5 3 CPN-I106-001
(PRIMARY)
STP CABLE
F-ESW02
GREEN
CEN-I106-L201G PORT 11X (FTE SWITCH-G)
4 1
2 IN NETWORK CABINET
GREEN 5 3 CPN-I106-001
(SECONDARY)

(SURGE PROTECTOR SWITCH)


F-SP01
STP CABLE

YELLOW IN OUT CNN-I106-S01A PORT 5X (SIS SAFENET SWITCH-A)


IN NETWORK CABINET
CPN-I106-001
(PRIMARY)
F-SP02
STP CABLE

(NOTE 1) IN OUT
GREEN CNN-I106-S01B PORT 5X (SIS SAFENET SWITCH-B)
IN NETWORK CABINET
CPN-I106-001
(SECONDARY)

KEY SWITCH MODULE WIRING

FC-TCNT11 FC-SSWM01
CN1 J1
Pin1, PROG BLU Pin 1
1 1
Pin 2 BLK Pin 2
2 2
Pin 3, FORCE_EN GRN Pin 3
3 3
RDMP RU V BALIKPAPAN
Pin 4 WHT/GRN Pin 4
4 4
Pin 5, FORCE_RST RED Pin 5
5 5
RDMP BALIKPAPAN JO
Pin 6 GRN/BRN Pin 6
6 6
Pin 7, FAULT_RST WHT Pin 7
7 7 PT PERTAMINA
Pin 8
8
WHT/PNK
8 Pin 8
PERTAMINA
BALIKPAPAN, INDONESIA
9 9
10 10 HIPPS SYSTEM INTERNAL WIRING
11 11
DIAGRAM FOR ISH-106
12 12
CPH-I106-001 : HIPPS SYSTEM CABINET ALARM WIRING
(CH_0601,UNIT-059)

NC NC F-TB1-1 R-TB1-1 3 1

F-FAN01 R-FAN01 F-THT01 F-TELD01


F-PWR01 F-ESW03
C C F-TB1-2 R-TB1-2 5 3

NC NC

F-PWR02 F-ESW04
C C

0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ 0.75SQ
WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK

RDMP RU V BALIKPAPAN

RDMP BALIKPAPAN JO
R-TBAL01
1 2 3 4 5 6 7 8 9 10 11 12
PT PERTAMINA
PERTAMINA
BALIKPAPAN, INDONESIA
POWER FAIL ALARM SWITCH FAIL FAN AND THERMOSTAT ALARM ELD ALARM
ALARM (ANALOG INPUT) HIPPS SYSTEM INTERNAL WIRING
DIAGRAM FOR ISH-106
TO TO TO TO
CMH-I106-001F CMH-I106-001F CMH-I106-001F CMH-I106-001F
F-TBAL01 (1,2) F-TBAL01 (3,4) F-TBAL01 (5,6) F-TBAL02 (1,2)
NOTE
1.
CPH-I106-001 : HIPPS SYSTEM CABINET GROUND WIRING XX : XXSQ CABLE
(AX) : (XAWG) CABLE
(CH_0601,UNIT-059) 2.
PANEL GROUNDING FROM
FRONT, REAR, DOOR & SIDE PANEL
3.
GROUND BUSBAR SPECIFICATION
a. 5mm THICK X 20mm WIDE.
b. THREADED WITH M6 SCREW HOLES.
c. BOLT EQUIPPED TO CONNECT 35 SQ mm
CPH-I106-001 CABLE

PE
F-FAN01
2.5 PE
(A14)
PE
R-FAN01
2.5 PE
(A14)

PE
F-LT01
E.S.D. 2.5 PE
(A14)
PE
BONDING R-LT01
POINT 2.5 PE
(A14)

PE
F-PWR01
2.5 PE
(A14)
PE
F-PWR02
2.5 PE
(A14)

Earth1
(NOTE 1) 2.5 PE
F-ESW01 F-TELD01 (A14)
PE 2.5
(A14)
F-ESW02
PE 2.5
(A14)
F-ESW03
PE 2.5
(A14)
F-ESW04
PE 2.5
(A14)

RDMP RU V BALIKPAPAN

RDMP BALIKPAPAN JO
PROTECTIVE EARTH BAR
PT PERTAMINA
PE NOTE 3 PERTAMINA
BALIKPAPAN, INDONESIA
16
(A6) GROUNDING
BOLT NOTE 2
HIPPS SYSTEM INTERNAL WIRING
DIAGRAM FOR ISH-106