1. This document is a site acceptance test report for the protective relay settings of the 400V LV SWGR that feeds the Belt Conveyor BC-07A at the 1x1000MW coal-fired Cirebon 2 Power Project in Indonesia.
2. The report details the settings, functions, and test results for 5 protection devices on the feeder: Phase TOC 1, Phase IOC 1, Ground TOC 1, Ground IOC 1, and Phase UV.
3. The protection devices were tested and their settings and functions were verified and approved by representatives from the power project developer Pituin Sukses Energi, contractor Dong Hwa, and supplier Hyundai.
1. This document is a site acceptance test report for the protective relay settings of the 400V LV SWGR that feeds the Belt Conveyor BC-07A at the 1x1000MW coal-fired Cirebon 2 Power Project in Indonesia.
2. The report details the settings, functions, and test results for 5 protection devices on the feeder: Phase TOC 1, Phase IOC 1, Ground TOC 1, Ground IOC 1, and Phase UV.
3. The protection devices were tested and their settings and functions were verified and approved by representatives from the power project developer Pituin Sukses Energi, contractor Dong Hwa, and supplier Hyundai.
1. This document is a site acceptance test report for the protective relay settings of the 400V LV SWGR that feeds the Belt Conveyor BC-07A at the 1x1000MW coal-fired Cirebon 2 Power Project in Indonesia.
2. The report details the settings, functions, and test results for 5 protection devices on the feeder: Phase TOC 1, Phase IOC 1, Ground TOC 1, Ground IOC 1, and Phase UV.
3. The protection devices were tested and their settings and functions were verified and approved by representatives from the power project developer Pituin Sukses Energi, contractor Dong Hwa, and supplier Hyundai.
Pituin Sukses Energi 400V LV SWGR PROTECTIVE SETTING RELAY Location Feeder No. Feeder Name Date COAL HANDLING P2BGA02GS002 BELT CONVEYOR (BC-07A) SYSTEM I. SETTING RELAY Checked 1 PHASE TOC 1 Value OK N/A a Phase TOC 1 Function Trip
b Phase TOC 1 Pickup 0.8 CT
c Phase TOC 1 Curve IEC Curve B
d Phase TOC 1 TDM 4
e Phase TOC 1 Reset Instantaneuos
f Phase TOC 1 Direction Disable
g Phase TOC 1 Relays Operate
h Phase TOC 1 Block 1 Off
i Phase TOC 1 Block 2 Off
j Phase TOC 1 Block 3 Off
Checked 2 PHASE IOC 1 Value OK N/A a Phase IOC 1 Function Trip
b Phase IOC 1 Pickup 6.8 CT
c Phase IOC 1 Delay 0.1 sec
d Phase IOC 1 Direction Disable
e Phase IOC 1 Relays Operate
f Phase IOC 1 Block 1 Off
g Phase IOC 1 Block 2 Off
h Phase IOC 1 Block 3 Off
Checked 3 GROUND TOC 1 Value OK N/A a Ground TOC 1 Function Trip
b Ground TOC 1 Pickup 0.2 CT
b Ground TOC 1 Pickup 0.2 CT
c Ground TOC 1 Curve Definite Time
d Ground TOC 1 TDM 0.1
e Ground TOC 1 Reset Instantaneuos
f Ground TOC 1 Direction Disable
g Ground TOC 1 Relays Operate
h Ground TOC 1 Block 1 Off
i Ground TOC 1 Block 2 Off
j Ground TOC 1 Block 3 Off
Checked 4 GROUND IOC 1 Value OK N/A a Ground IOC 1 Function Disable
b Ground IOC 1 Pickup -
c Ground IOC 1 Delay -
d Ground IOC 1 Direction -
e Ground IOC 1 Relays -
f Ground IOC 1 Block 1 -
g Ground IOC 1 Block 2 -
h Ground IOC 1 Block 3 -
Checked 5 PHASE UV Value OK N/A a Phase UV Function Trip
b Phase UV Pickup 0.8 VT
c Phase UV Curve Definite Time
d Phase UV Delay 2 sec
e Phase UV Phases All Three
f Phase UV Min Voltage 0.1 VT
g Phase UV Relays Operate
h Phase UV Block 1 Off
i Phase UV Block 2 Off
j Phase UV Block 3 Off
Note :
Tested by: Witnessed by: Approved by:
PT Pituin Sukses Energy Dong Hwa Hyundai Cirebon Power