Doc. No.

: 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

Performance Test Procedure – EDG U331

PROJECT : Engineering, Procurement and Construction (EPC) Inside


Battery Limits (ISBL) and Outside Battery Limits (OSBL) for
the Refinery Development Master Plan (RDMP) Project
RU V Balikpapan
LOCATION : Refinery Unit V Balikpapan, East Kalimantan,Indonesia
OWNER : PT. Kilang Pertamina Balikpapan (KPB)

00A 5 AUG 22 ISSUED FOR REVIEW GIGIH/I.IRAWAN C.Y.KIM J.H.KIM

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED


Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

REVISION LOG

REV. NO. DATE PAGE DESCRIPTION

00A 11 JUL 22 - ISSUED FOR REVIEW

2 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

HOLD LIST

NO. Paragraph HOLD Content

3 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

TABLE OF CONTENTS

1 PURPOSE ........................................................................................................................................... 6
2 DEFINITION AND ABBREVIATION ............................................................................................... 6
2.1 Definition .................................................................................................................................................. 6
2.2 Abbreviation ............................................................................................................................................ 6
3 REFERENCE........................................................................................................................................ 7
4 SAFETY PRECAUTIONS ................................................................................................................... 8
4.1 General Safety Precaution ..................................................................................................................... 8
4.2 Safety Notes, Caution and Warning ................................................................................................... 9
5 GENERAL ........................................................................................................................................... 9
5.1 Testing Conditions .................................................................................................................................. 9
5.2 Instrument/Equipment Required during Test ................................................................................... 9
5.3 Pre-test Inspection ................................................................................................................................. 10
5.4 Post Work................................................................................................................................................. 11
6 FIRST START, ALARM AND SHUTDOWN TEST AND SYNCHRONIZATION TEST ............. 11
6.1 FIRST START UP ...................................................................................................................................... 11
6.1.1 MCP/DMC Energization and Generator Communication Checks ................................................................11
6.1.2 Generator First Start ..........................................................................................................................................................11
6.1.3 Acceptance Criteria ............................................................................................................................................................14
6.2 SYNCHRONIZATION TEST ..................................................................................................................... 14
6.2.1 Pre-start Checks ...................................................................................................................................................................14
6.2.2 Synchronization Test – Close CB for 1st EDG only, Phasing Check for other EDG ............................16
6.2.3 Synchronization Test – Close CB for 1st & 2nd EDG only..............................................................................18
6.2.4 Synchronization Test – Close CB for all EDG.........................................................................................................20
6.2.5 Acceptance Criteria ............................................................................................................................................................22
6.3 ALARM AND SHUTDOWN TEST .......................................................................................................... 22
6.3.1 Pre-start Checks ...................................................................................................................................................................23
6.3.2 Emergency Stop from LCP ..............................................................................................................................................24
6.3.3 Coolant Temperature High Alarm Test .....................................................................................................................25
6.3.4 Coolant Temperature High Shutdown Test ............................................................................................................27
6.3.5 Lube Oil Pressure Low Shutdown Test .....................................................................................................................28
6.3.6 Engine Fail to Start Shutdown Test ............................................................................................................................29
6.3.7 Battery DC Voltage Low Alarm Test ..........................................................................................................................30
6.3.8 Battery DC Voltage High Alarm Test .........................................................................................................................32
6.3.9 Overspeed Shutdown Test..............................................................................................................................................33
4 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.3.10 Acceptance Criteria .......................................................................................................................................................34


7 PERFORMANCE TEST EXECUTION ............................................................................................. 35
7.1 LOAD TEST ............................................................................................................................................... 35
7.1.1 Pre-start Checks ...................................................................................................................................................................35
7.1.2 Load Test (Manual).............................................................................................................................................................36
7.1.3 Acceptance Criteria ............................................................................................................................................................38
7.2 TRANSIENT TEST ..................................................................................................................................... 39
7.2.1 Pre-start Checks ...................................................................................................................................................................39
7.2.2 Transient Response Test ..................................................................................................................................................41
7.2.3 Acceptance Criteria ............................................................................................................................................................42
7.3 LOAD SHARING TEST ............................................................................................................................. 42
7.3.1 Pre-start Checks ...................................................................................................................................................................43
7.3.2 Load Sharing Test ...............................................................................................................................................................44
7.3.3 Acceptance Criteria ............................................................................................................................................................45
7.4 TEST/CHECK SEQUENCE OF OPERATION (EDG & MCP) ................................................................. 45
7.4.1 Acceptance Criteria ............................................................................................................................................................45
8 ATTACHMENT ................................................................................................................................ 46

5 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

1 PURPOSE
The purpose of this document is to provide an inclusive procedure for performance test for
Emergency Diesel Generator (A-331-05A/B/C) in Refinery Development Master Plan
(RDMP) Project RU V Balikpapan.
This document shall consider normal condition of performance test, if in any case deviation
occurs before or during the execution of this procedure, all parties shall be in an agreement
regarding the best course of action.

2 DEFINITION AND ABBREVIATION


2.1 Definition

Terms Definition

CONTRACTOR RDMP Balikpapan JO

OWNER PT. Kilang Pertamina Balikpapan*

JO Joint Operation, CONTRACTOR’s Joint Operation (JO) Body

PROJECT Engineering, Procurement and Construction (EPC) Inside Battery


Limits (ISBL) and Outside Battery Limit (OSBL) for The Refinery
Development Master Plan (RDMP) Project RU V Balikpapan

SUB-SYSTEM Subdivision of a System

SYSTEM Major subdivision of the plant, being either process or utility,


including all the equipment required for that System to operate.

VENDOR Cummins Sales and Services Korea (CSSK)

*) OWNER included in documents (Plan, Procedure, etc.) shall be deemed to be read as


KPB (PT. Kilang Pertamina Balikpapan.)
2.2 Abbreviation

Terms Definition

ATS Automatic Transfer Switch

AVR Automatic Voltage Regulator

CB Circuit Breaker

DMC Digital Master Control

ECMS Electrical Control and Monitoring System

6 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

EDG Emergency Diesel Generator

E-Stop Emergency Stop

GCP Generator Control Panel

HMI Human Machine Interface

ILS Isochronous Load Sharing

LCP Local Control Panel

MCP Master Control Panel

NER Neutral Earthing Resistor

NEC Neutral Earthing Contactor

PCC PowerCommand® Control

PLC Programmable Logic Controller

PPE Personal Protective Equipment

SIKA Surat Ijin Kerja Aman (Safe Work Permit)

SAT Site Acceptance Test

UCP Unit Control Panel

UCR Utilities Control Room

3 REFERENCE
This document has been prepared with reference to following documents:

Doc No. Title

P&ID Power Gen. & Condensate Sys. (Unit 331)


26071-203-M6-331-00026-01
Diesel Oil Storage Day Tank

P&ID Power Gen. & Condensate Sys. (Unit 331)


26071-203-M6-331-00027
Emergency Diesel Generator (EDG) Package

26071-V67-331-A-105-GEN1-00010 Engine for Diesel Generator Data Sheet

26071-V67-331-A-105-GEN1-00011 Generator Data Sheet

7 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

Doc No. Title

26071-V67-331-A-105-GEN1-00038 P&ID for Diesel Engine Generator

26071-V67-331-A-105-GEN1-00039 Single Line Diagram for Diesel Engine Generator

Operation Philosophy & Block Logic Diagram for


26071-V67-331-A-105-GEN1-00043
EDG

26071-V67A-331-A-105-GEN1-00047 Alarm and Trip Setting Schedules

Operation and Maintenance Procedure and Manual


26071-V67-331-A-105-GEN1-00056
for Diesel Engine Generator

26071-V67-331-A-105-GEN1-00060 Inspection and Test Report (Cummins UK Factory)

26071-V67-331-A-105-GEN1-00074 Inspection and Test Procedure (SAT)

4 SAFETY PRECAUTIONS
4.1 General Safety Precaution
The following requirement shall be complied prior execution of EDG performance test
activities:

No. Preparation Check List Sign

1 Permit to Work and SIKA shall be applied and are obtained prior
to proceeding with the work in the area

2 PPE shall be worn by all personnel

3 Any temporary equipment shall be checked for correctness and


fit for use with valid calibration certificates

4 The area shall be restricted. Only authorized personnel can


access the area.

5 Ensure the fire fighting facility is presented near the EDG when
hydrocarbon or highly flammable material is involved in the
activity.
- Fire Hydrant 333-FHF-020 & 333-FHF-030 to cover all EDGs
- Fire Extinguisher – Portable Dry Chemical in each EDG
8 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Preparation Check List Sign


enclosure
- In the case that no nearby fire hydrant is available, fire truck
shall be available nearby.

6 MSDS shall be available

7 Evacuation/escape plan

4.2 Safety Notes, Caution and Warning

No. Description Remark

1 Hot Pressurized Liquid

2 Moving Parts

3 Toxic Hazards

4 Electrical Generating Equipment

5 Combustible Liquid

6 High Noise Level

7 Hot Surfaces

8 Fire Hazards

9 Fall Hazards

5 GENERAL
5.1 Testing Conditions
The testing will be carried out under ambient temperature condition in open area. The engine
coolant for the test shall be a VENDOR recommended pre-mixed coolant (Fleetguard – ES
Compleat™ Coolant PG Premix or equivalent). The test fuel shall be standard diesel fuel to
grade no. 2-D per ASTM D975 or equivalent with minimum cetane number of 40. The oil
used during the test shall be SAE 15W40, API class CD oil (Valvoline – Premium Blue™
SAE 15W-40 or equivalent).
5.2 Instrument/Equipment Required during Test
The following temporary equipment shall be available and ready on site to perform the
execution work of this procedure.

9 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Description Quantity

1. Load Bank (2.5 MW) 1 set

2. Torque wrench 1 set

3. Vibration meter 1 ea

4. Tachometer 1 ea

5. Temperature gun 1 ea

6. Sound level meter 1 ea

7. Digital Multimeter 1 ea

8. Clamp meter 1 ea

9. Insulation Resistance Meter 5000V 1 ea

10. Phase sequence meter 1 ea

11. Temporary Genset 33 kVA 3 set

12. Manual Hand Pump 2 ea

13. Laptop with required software and communication cables 1 set

All measuring tools shall be calibrated and validly certified during testing.
5.3 Pre-test Inspection
Before performance test is conducted, pre-test inspection (installation checks) of the
package is carried out. In the case that switchgear energization is required in the steps,
switchgear commissioning shall be completed prior to generator start-up. General pre-test
inspection checklist is as follows.

No. Action Remark

1. Installation visual checks

2. Check all piping and electrical interfaces

3. Checks field cabling

4. Generator startup checks including alternator IR test

Auxiliary supplies energization and functional checks including


5.
battery connection and battery charger energization

10 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

5.4 Post Work


After all test is completed for EDG, the unit will be put in ready for service:
a. Remove all temporary equipment (load bank, transformer, generator, etc)
b. Drain the lube oil in the engine and fill the new lube oil.
c. Replace the oil filter and fuel filter
On completion of all testing, the package will be given a final inspection and
OWNER/OWNER’s representative shall make any comments or observations made during
the initial inspection and subsequent testing on the test report. OWNER/OWNER’s
representative will then sign the test reports as acceptance of the testing and copies will be
handed over.

6 FIRST START, ALARM AND SHUTDOWN TEST AND SYNCHRONIZATION TEST


Test listed below should normally be conducted prior to performance test as these tests shall
ensure operability of EDG auxiliary components before applying load to the generator. The
tests listed below generally require no load to be completed.
6.1 FIRST START UP
EDG testing will be carried out using actual LCP of respective EDG. Generator start-up test
aims to check and verify the operation of LCP, MCP (DMC) communication check, CB
open/close control, and ECMS communication check.
The Startup test will be started manually through LCP. Startup test will be done individually
for 3 EDGs (A-331-05A/B/C). Record sheet is provided in Attachment-1.
Periods of no-load operation should be held to no longer than 15 minutes. Long periods of
no-load operation can result in engine damage.
6.1.1 MCP/DMC Energization and Generator Communication Checks

No. Action Remark

1. Energize DMC and establish communication between PCCs and DMC

2. Verify Generator parameters display on DMC

This testing is basically to confirm that all signals/feedback status


between EDG package with plant interface
- LCP
3.
- UCP
- MCP/DMC
- NER

6.1.2 Generator First Start

No. Action Remark


11 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

Ensure the switchgear commissioning has completed as the generator


1.
startup includes switchgear energization along with power cables

2. Ensure all cables has been terminated

Ensure earth switch at generator incomer CBs open and generator NEC
3.
is closed

4. Ensure all outgoing feeders are racked out.

5. Ensure all CBs & Earth switch position is accurately showing at DMC

6. Verify that all engine and generator safety checks have been performed
to ensure the engine and generator are fit to run as below
- Operator to ensure mechanical valves are in position before start- up
such as Diesel, Lube oil, Cooling circuit line
- Operator to check & ensure no heavy fault occurred in the EDG
package such as FGS confirm fire, Emergency stop (UCP & LCP),
Engine protection system
- Battery healthy condition status
All the above are satisfied, engine will be started upon receiving of start
signal and will reach idle RPM immediately.

7. Ensure lube oil level, Coolant level, Fuel Level is enough for EDG run
test
Diesel Oil Storage Day Tank (D-331-01A/B) : __________%
Normal level : 8 – 93 %
Fuel Tank (A-331-05A/B/C-D1) : __________%
Normal level : 50 %
Lube Oil Tank (A-331-05A/B/C-D2) : __________%
Normal level : between L-H
Coolant Radiator (A-331-05A/B/C-E1) : __________%
Normal level : <2.5 cm from top

8. Ensure that no alarm in the PowerCommand 3.3 Control, protection


relay, all faults to be cleared and/or logged before start.

9. Confirm ventilation fan running

10. CONFIRM The status below:


- Circuit Breaker – Open

12 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


Local/No Operation/Remote Selector Switch – Local (Manual)

11. From the LCP HMI,

Press the to put the generator set into Manual mode.

START Engine by pushing from LCP and ensure both ventilation


fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into the
Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line, Coolant
line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

12. Within less than 5 minutes, EDG will reach stability at idle speed, then Test duration
STOP Engine from LCP and confirm Engine stop. will be
confirmed by
After engine stop, reset system and ensure system ready to start
Cummins
during
execution

13. Repeat step 6-12 for all EDGs

14. START the EDG from LCP.

15. After more than 5 minutes, EDG will reach stability at rated speed &
voltage, then STOP Engine from LCP and confirm Engine stop.
Do not run the EDG for more than 15 minutes without load!

16. Repeat step 14-15 above for all EDGs.

17. Once EDG startup completed, ensure start stop of EDG from MCP.

18. Ensure all EDG parameters display on MCP HMI.

19. Carryout EDG respective CB open/close control and status feedback


(operation from LCP & MCP)

13 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

20. If the ECMS communication established, ensure the data transmission is


received.

6.1.3 Acceptance Criteria

No. Action Remark

General operation function for control panel:


1.
Indication lamp, push button, select switch, and so on.

EDG operational system:


2.
Starting system, Exhaust system, Ventilation: works properly.

3. EDG Start/Stop from Local and Remote works properly

Circuit Breaker Open/Close from LCP & MCP works properly, and CB
4.
indication position is correct

6.2 SYNCHRONIZATION TEST


This test aims to check and verify the synchronization parameter of EDG unit.
Synchronization test will be performed manually through LCP. This test will synchronize all
EDG at no load.
If during synchronization EDG is not stabilized or regularly tripped, they can be synchronized
when bus has load by connecting to load bank.
The sequence run of EDG (A-331-05A/B/C) is not mandatory. The following procedure will
run the EDG-C (A-331-05C) first, following by A-331-05A & A-331-05B to synchronize. Any
other sequence based on site condition is acceptable.

6.2.1 Pre-start Checks

No. Action Remark

1. Ensure the Switchgear 101-HSW-C02A/B is not energized (dead)

2. Ensure all outgoing feeders are racked out.

3. Ensure all CB position is accurately showing at LCP.

Verify that all engine and generator safety checks have been
4. performed to ensure the engine and generator are fit to run as below
- Operator to ensure mechanical valves are in position before

14 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


start- up such as Diesel, Lube oil, Cooling circuit line
- Operator to check & ensure no heavy fault occurred in the EDG
package such as FGS confirm fire, Emergency stop (UCP &
LCP), Engine protection system
- Battery healthy condition status.
- Generator NEC is in closed position

Ensure lube oil level, Coolant level, Fuel Level is enough for EDG
synchronization test
- Diesel Oil Storage Day Tank (D-331-01A/B) : __________%
- Normal level : 8 – 93 %
- Fuel Tank (A-331-05A/B/C-D1) : __________%
5.
- Normal level : 50 %
- Lube Oil Tank (A-331-05A/B/C-D2) : __________%
- Normal level : between L-H
- Coolant Radiator (A-331-05A/B/C-E1) : __________%
- Normal level : <2.5 cm from top

Ensure that no alarm in the PowerCommand 3.3 Control, protection


6.
relay, all faults to be cleared and/or logged before start.

7. Confirm ventilation fan running

CONFIRM the status below:


- All Circuit Breaker of switchgear 101-HSW-C02AB – Open
8.
- EDG Local/No Operation/Remote Selector Switch – Local
(Manual)

CLOSE the Bus Tie of switchgear 101-HSW-C02A/B By operator in


Main
9. Note:
Substation 341-
The switchgear 101-HSW-C02 A & B is now connected. Ensure all of step above has SS-101
been done then can continue to the next step.

15 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.2.2 Synchronization Test – Close CB for 1st EDG only, Phasing Check for other EDG

No. Action Remark

From the LCP HMI A-331-05C, Keep


communication
with Main
Press the to put the generator set into Manual mode. Substation 341-
SS-101

START Engine A-331-05C by pushing from LCP and ensure


1. both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into the
Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line, Coolant
line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Inform to Operator in Main Substation 341-SS-101 that switchgear 101-


2.
HSW-C02A/B will be energized by EDG A-331-05C.

CLOSE the CB of EDG A-331-05C by pushing in LCP A-331-


3. 05C
Note:
The switchgear 101-HSW-C02 A & B is now energized.

Phasing Check the EDG A-331-05A & B: Check the bus


voltage in Main
4. The PCC will show the bus voltage.
Substation 341-
SS-101

16 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

5. Record measured values in the test sheet Attachment-2

6. Stop EDG A-331-05C

7. Repeat step 1-6 for EDG A-331-05A and A-331-05B

17 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.2.3 Synchronization Test – Close CB for 1st & 2nd EDG only

No. Action Remark

From the LCP HMI A-331-05C, Keep


communication
with Main
Press the to put the generator set into Manual mode. Substation
341-SS-101

START Engine A-331-05C by pushing from LCP and ensure


1. both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into
the Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Inform to Operator in Main Substation 341-SS-101 that switchgear


2.
101-HSW-C02A/B will be energized by EDG A-331-05C.

CLOSE the CB of EDG A-331-05C by pushing in LCP A-331-


3. 05C
Note:
The switchgear 101-HSW-C02 A & B is now energized.

Synchronize the EDG A-331-05A: Keep


communication
From the LCP HMI A-331-05A,
with Main
Substation
341-SS-101
Press the to put the generator set into Manual mode.

4. START Engine A-331-05A by pushing from LCP and ensure


both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into
the Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

18 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

The Synchronizer will force EDG A-331-05A to come into synchronism


with the switchgear 101-HSW-C02A/B.
The sync check device in PCC then will verify the phase sequence of
the switchgear is same as the EDG A-331-05A, then monitoring the
phase angle of the switchgear voltage to the phase angle of EDG-A
voltage.
When sync check senses that the phase angle difference is within
tolerance, it allows closure of the paralleling CB.
In PCC, the display will be as below:

5.

6.

CLOSE the CB of EDG A-331-05A by pushing in LCP A-331-


05A
Note:
The EDG A-331-05A & C is now in parallel operation in the switchgear 101-HSW-
C02A/B.
Ensure the EDG does not trip with reverse power.

7. Monitor for 2-3 minutes.

8. Stop EDG A-331-05A

9. Repeat the step no. 4-8 for the EDG A-331-05B

19 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.2.4 Synchronization Test – Close CB for all EDG

No. Action Remark

From the LCP HMI A-331-05C, Keep


communication
with Main
Press the to put the generator set into Manual mode. Substation
341-SS-101

START Engine A-331-05C by pushing from LCP and ensure


1. both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into
the Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Inform to Operator in Main Substation 341-SS-101 that switchgear


2.
101-HSW-C02A/B will be energized by EDG A-331-05C.

CLOSE the CB of EDG A-331-05C by pushing in LCP A-331-


3. 05C
Note:
The switchgear 101-HSW-C02 A & B is now energized.

Synchronize the EDG A-331-05A: Keep


communication
From the LCP HMI A-331-05A,
with Main
Substation
341-SS-101
Press the to put the generator set into Manual mode.

4. START Engine A-331-05A by pushing from LCP and ensure


both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into
the Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

20 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

The Synchronizer will force EDG A-331-05A to come into synchronism


with the switchgear 101-HSW-C02A/B.
The sync check device in PCC then will verify the phase sequence of
the switchgear is same as the EDG A-331-05A, then monitoring the
phase angle of the switchgear voltage to the phase angle of EDG-A
voltage.
When sync check senses that the phase angle difference is within
tolerance, it allows closure of the paralleling CB.
In PCC, the display will be as below:

5.

6.

CLOSE the CB of EDG A-331-05A by pushing in LCP A-331-


05A
Note:
The EDG A-331-05A & C is now in parallel operation in the switchgear 101-HSW-
C02A/B.
Ensure the EDG does not trip with reverse power.

7. START Engine A-331-05B

8. Wait until EDG A-331-05B synchronized, and allow the CB to close.

9.

CLOSE the CB of EDG A-331-05B by pushing in LCP A-331-


05B

21 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


Note:
The EDG A-331-05A/B/C is now in parallel operation in the switchgear 101-HSW-
C02A/B.
Ensure the EDG does not trip with reverse power.

10. Monitor for 2-3 minutes.

11. STOP the EDG A-331-05B, then repeat for EDG A-331-05A and EDG
A-331-05C.

6.2.5 Acceptance Criteria

No. Action Remark

1. All EDG can be synchronized properly without trip

6.3 ALARM AND SHUTDOWN TEST


EDG testing will be carried out using actual LCP of respective EDG package.
This test aims to check and verify the alarm and shutdown of EDG unit. Also, this test is to
verify the operation of the starter system and to verify the start-up sequence including the
lube oil, fuel system, ventilation system, and cooling system.
Run test will be started manually through LCP. Run test will be done individually for 3 EDGs
(A-331-05A/B/C). Record the data into Alarm & Shutdown Test Report as attached.
Alarm and Shutdown Test will be applied for the following parameter:
1. Emergency Stop from LCP
2. Coolant temperature high alarm (simulation thru software)
3. Coolant temperature high shutdown (simulation thru software)
4. Lube oil low pressure shutdown (simulation thru software)
5. Engine fault to start shutdown (simulation thru software)
6. Battery DC Voltage Low alarm (simulation thru software)
7. Battery DC Voltage High alarm (simulation thru software)
8. Overspeed shutdown (simulation thru software)
Periods of no load operation should be held to no longer than 15 minutes. Long periods of no
load operation can result in engine damage.

22 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.3.1 Pre-start Checks

No. Action Remark

Grounding (earthing) must be checked prior to performing service or


9. inspection procedures that may expose personnel to conductors
normally energized with high voltage.

10. Insulation Testing must be performed on all generator sets

Check the engine lubrication oil level and ensure the correct level is
11.
always maintained

Check the coolant level and ensure the correct level is always
maintained
12.
Fill the cooling system to the bottom of the fill neck in the radiator fill
or expansion tank.

Diesel fuel is filled to the normal level


Fuel Tank (A-331-05A/B/C-D1) : __________%
Normal level : 50 %
13.
All valves required for operation are open
There are no leak and that all fittings are tight
If equipped, the auxiliary fuel system is properly connected

14. Make sure that the cooling air inlet/outlet are unobstructed

Exhaust components are secured and not warped


The exhaust outlet is unobstructed
15. No combustible materials are near the system
Gases are discharged away from building openings
There are no leaks and that all fittings are tight

Make sure that all batteries are charged, and that all connections are
16. clean, correct and tight
Normal voltage : 24-27 V

Make sure that all auxiliary equipment is received the power from
17.
external source

18. Make sure that the Emergency Stop button is fully operational

Connect the PCC to the Laptop via RS485 port to communicate with Performed by
19.
the InPower software Cummins

23 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.3.2 Emergency Stop from LCP

No. Action Remark

Verify that all engine and generator safety checks have been performed
to ensure the engine and generator are fit to run as below
- Operator to ensure mechanical valves are in position before start-
up such as Diesel, Lube oil, Cooling circuit line
- Operator to check & ensure no heavy fault occurred in the EDG
4.
package such as FGS confirm fire, Emergency stop (UCP & LCP),
Engine protection system
- Battery healthy condition status
All the above are satisfied, engine will be started upon receiving of start
signal.

Ensure lube oil level, Coolant level, Fuel Level is enough for EDG run
test
Diesel Oil Storage Day Tank (D-331-01A/B) : __________%
Normal level : 8 – 93 %
Fuel Tank (A-331-05A/B/C-D1) : __________%
5.
Normal level : 50 %
Lube Oil Tank (A-331-05A/B/C-D2) : __________%
Normal level : between L-H
Coolant Radiator (A-331-05A/B/C-E1) : __________%
Normal level : <2.5 cm from top

Ensure that no alarm in the PowerCommand 3.3 Control, protection


6.
relay, all faults to be cleared and/or logged before start.

7. Confirm ventilation fan running

CONFIRM The status below:


8. - Circuit Breaker - Open
- Local/No Operation/Remote Selector Switch – Local (Manual)

From the LCP HMI,

Press the to put the generator set into Manual mode.


9.

START Engine by pushing from LCP and ensure both


ventilation fan and radiator fan are running.

24 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into the
Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line, Coolant
line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

After 5 minutes, STOP Engine by using E-Stop from LCP and confirm Test duration
Engine can stop by using E-Stop from LCP. will be
confirmed by
10. After engine stop by using E-Stop, reset system and ensure system
Cummins
ready to start
during
execution

6.3.3 Coolant Temperature High Alarm Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3.
- Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface

START Engine from LCP and ensure both ventilation fan and radiator
fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Confirm the Coolant Temperature is increasing on LCP


Check at the HMI display:
5.

Press Home , then select menu “Engine” at bottom bar

25 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

6. Access InPower and change High Coolant Temperature Alarm set Set point
point to be lower than original set point change as per
Cummins
recommendation

7. Confirm that an alarm from LCP display is triggered

8. STOP the engine from LCP

9. Bring the engine back to ready to start status:


- Reset the fault
- Reset the set point to its original set point

26 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.3.4 Coolant Temperature High Shutdown Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3.
- Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface

START Engine from LCP and ensure both ventilation fan and radiator
fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Confirm the Coolant Temperature is increasing on LCP


Check at the HMI display:

Press Home , then select menu “Engine” at bottom bar

5.

6. Access InPower and change High Coolant Temperature Shutdown set Set point
point to be lower than original set point change as per
Cummins
recommendation

27 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

7. Confirm the engine automatically shut down.


Confirm that an alarm from LCP display is triggered

8. Bring the engine back to ready to start status:


- Reset the fault
- Reset the set point to its original set point

6.3.5 Lube Oil Pressure Low Shutdown Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3.
- Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface

START Engine from LCP and ensure both ventilation fan and radiator
fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Confirm the Lube Oil Pressure is increasing on LCP


Check at the HMI display:
5.

Press Home , then select menu “Engine” at bottom bar

28 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

6. Access InPower and change Lube Oil Pressure Low Shutdown set Set point
point to be higher than original set point change as per
Cummins
recommendation

7. Confirm the engine automatically shut down.


Confirm that an alarm from LCP display is triggered

8. Bring the engine back to ready to start status:


- Reset the fault
- Reset the set point to its original set point

6.3.6 Engine Fail to Start Shutdown Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3. - Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface
- Disconnect/Unplug the cable connector to the starter relay

29 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

4. Push engine START button from LCP

5. Wait for few minutes while the EDG tries to crank the engine

6. Confirm that Shutdown lamp indicator lit from LCP display

7. Bring the engine back to ready to start status:


- Connect/Plug the cable connector of the starter relay.
- Reset the fault

6.3.7 Battery DC Voltage Low Alarm Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3.
- Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface

START Engine from LCP and ensure both ventilation fan and radiator
fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Check at the HMI display:


5.
Press Home , then select menu “Engine” at bottom bar

30 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

6. Access InPower and change Battery DC Voltage Low Alarm set point Set point
to be higher than original set point change as per
Cummins
recommendation

7. Confirm that an alarm from LCP display is triggered

8. STOP the engine from LCP

9. Bring the engine back to ready to start status:


- Reset the fault
- Reset the set point to its original set point

31 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

6.3.8 Battery DC Voltage High Alarm Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3.
- Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower interface

START Engine from LCP and ensure both ventilation fan and
radiator fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Check at the HMI display:

Press Home , then select menu “Engine” at bottom bar

5.

6. Access InPower and change Battery DC Voltage High Alarm set Set point
point to be lower er than original set point change as per
Cummins

32 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


recommendation

7. Confirm that an alarm from LCP display is triggered

8. STOP the engine from LCP

9. Bring the engine back to ready to start status:


- Reset the fault
- Reset the set point to its original set point

6.3.9 Overspeed Shutdown Test

No. Action Remark

1. Access PCC and record the original set point

Ensure that no alarm in the PCC, protection relay, all faults to be


2.
cleared and/or logged before start.

CONFIRM The status below:


- Circuit Breaker - Open
3. - Local/No Operation/Remote Selector Switch – Local (Manual)
- Connect the PCC to the Laptop for InPower/InSite interface

START Engine from LCP and ensure both ventilation fan and radiator
fan are running.
Note:
4.
During running check condition of engine, Generator, Aux Equipment, Fuel Line,
Coolant line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

5. Check at the HMI display:

Press Home , then select menu “Engine” at bottom bar

33 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

6. Access InPower and change Overspeed Shutdown set point to be


lower than original set point

7. Confirm the engine automatically shut down.


Confirm that an alarm from LCP display is triggered

8. Bring the engine back to ready to start status:


- Reset the set point to its original set point
- Reset the fault

6.3.10 Acceptance Criteria

No. Action Remark

Alarm simulation test trigger the alarm as required.


1.
The alarm indication lamp lit.

Shutdown simulation test trigger the EDG to shutdown


2.
The shutdown indication lamp lit.

34 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

7 PERFORMANCE TEST EXECUTION


7.1 LOAD TEST
Prior to this test, Genset First Start test up to Alarm & Shutdown test has been performed
with acceptable result.
EDG packages will be load tested individually with a Load Bank of 1.0 power factor.
Parameter mentioned in the test sheets are taken every 15 minutes.
During the load test, the following parameter shall be recorded:
1) Time
2) Duration (hrs)
3) Ambient temperature (oC)
4) Load
5) kW
6) RPM
7) Hz
8) Power Factor
9) All L-L Voltages (V)
10) All Line Currents (A)
11) Coolant temperature (oC)
12) Lube Oil Pressure (kPa)
The loading of the generator will be as per below sequence.
• Warm Up- 5 Minutes
• 30 min at 25% load
• 30 min at 50% load
• 120 min at 100% load
• 60 min at 110% load

7.1.1 Pre-start Checks

No. Action Remark

Grounding (earthing) must be checked prior to performing service or


1. inspection procedures that may expose personnel to conductors
normally energized with high voltage.

2. NER operation to be verified

3. Insulation Testing must be performed on all generator sets

35 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

Check the engine lubrication oil level and ensure the correct level is
4.
always maintained

Check the coolant level and ensure the correct level is always
maintained
5.
Fill the cooling system to the bottom of the fill neck in the radiator fill
or expansion tank.

Diesel fuel is filled to the normal level


All valves required for operation are open
6.
There are no leak and that all fittings are tight
If equipped, the auxiliary fuel system is properly connected

7. Make sure that the cooling air inlet/outlet are unobstructed

Exhaust components are secured and not warped


The exhaust outlet is unobstructed
8. No combustible materials are near the system
Gases are discharged away from building openings
There are no leaks and that all fittings are tight

Make sure that all batteries are charged, and that all connections are
9.
clean, correct and tight

Make sure that all auxiliary equipment is received the power from
10.
external source

Make sure that the Emergency Stop button is fully operational Performed by
11.
Cummins

7.1.2 Load Test (Manual)

No. Action Remark

Verify that all engine and generator safety checks have been performed
to ensure the engine and generator are fit to run as below
- Operator to ensure mechanical valves are in position before start-
1. up such as Diesel, Lube oil, Cooling circuit line
- Operator to check & ensure no heavy fault occurred in the EDG
package such as FGS confirm fire, Emergency stop (GCP & LCP),
Engine protection system

36 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


- Battery healthy condition status
All the above are satisfied, engine will be started upon receiving of start
signal

Ensure that no alarm in the PCC, protection relay, all faults to be cleared
2.
and/or logged before start.

3. Confirm ventilation fan running

CONFIRM The status below:


4. - Circuit Breaker – Open
- Local/No Operation/Remote Selector Switch – Local (Manual)

5. Press the start button from LCP

Engine Starter will be disengaged from the pinion to avoid over


6. crank of engine. After engine started will be ramped up immediately
rated of 1500 RPM

Ensure Engine cranking and full speed no load (1500 RPM) and ensure
7.
aux equipment is running properly

Check the status of the engine after receive start command from LCP up
8.
to ready to load

9. Close the Circuit Breaker

Feed with load:


a. Warm Up- 5 Minutes at 0% load
b. 30 min at 25% load
c. 30 min at 50% load
10. d. 120 min at 100% load
e. 60 min at 110% load

Observe if any abnormal noise, vibration, no fluctuation of current and


voltage and as well the running operating parameters

All parameters for the EDG shall be recorded in the check sheet
11.
(Attachment-5, 6 and 8)

Check lube oil level, Coolant level and fuel level and ensure there is no
12.
leak.

37 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

Ramp down the load to 0 % Load then let the generator run for 3 minutes
13. This allows This allows the lubricating oil and engine coolant to carry
heat away from the combustion chamber and bearings.

STOP EDG by pressing stop push button from LCP and Ensure EDG
14. shall normal stop (cool down runtime) sequence for complete stop of
EDG package

7.1.3 Acceptance Criteria

No. Action Remark

Operating Parameter meets the following criteria:

Description Value Unit

Generator Speed 1500 rpm

Generator Output Voltage 6600 V

Generator Frequency 50 Hz

Generator Output Power @100% 2 MW


1.
Lube Oil Press. ≥ 15 psi

Coolant Temp. ≤ 102 o


C

Alternator DE/NDE Bearing Temp. ≤ 85 o


C

Alternator Winding Temp. ≤ 135 o


C

Fuel Temp. ≤ 120 o


C

Vibration Acceptance Criteria:

Description Value Unit


2.
Engine ≤ 45 mm/s rms

Generator ≤ 28 mm/s rms

38 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark

Noise sound level of EDG enclosure will be measured during 100%


load at 1 meter from enclosure.
3.
Acceptance criteria ≤ 85 dB

7.2 TRANSIENT TEST


The test is aimed to record and evaluate the EDG response test (frequency, voltage, and
duration to recover the frequency/voltage) in case of load changing.
The test will involve all EDGs A-331-05A/B/C, MV switchgear 101-HSW-C02A/B in Main
Substation Building, and Load Bank.
The test will be performed manually through LCP, and will put the EDG with load.
The sequence run between EDG (A-331-05A or B or C) is not mandatory. The following
procedure will run the EDG-A (A-331-05A) first. After completion for EDG A-331-05A,
perform the test for A-331-05B & A-331-05. Any other sequence based on site condition is
acceptable.
The loading of the generator set will be as per below sequence.
a. 0% to 25% load
b. 25% to 50% load
c. 50% to 75% load
d. 75% to 100% load
e. 100% to 75% load
f. 75% to 50% load
g. 50% to 25% load
h. 25% to 0% load
i. 100% to 0% load

7.2.1 Pre-start Checks

No. Action Remark

1. Ensure the Switchgear 101-HSW-C02A/B is not energized (dead)

2. Ensure all outgoing feeders are racked out.

3. Ensure all CB position is accurately showing at LCP.

Verify that all engine and generator safety checks have been
4.
performed to ensure the engine and generator are fit to run as below

39 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

- Operator to ensure mechanical valves are in position before


start- up such as Diesel, Lube oil, Cooling circuit line
- Operator to check & ensure no heavy fault occurred in the EDG
package such as FGS confirm fire, Emergency stop (UCP &
LCP), Engine protection system
- Battery healthy condition status

Ensure lube oil level, Coolant level, Fuel Level is enough for EDG
test
- Diesel Oil Storage Day Tank (D-331-01A/B) : __________%
- Normal level : 8 – 93 %
- Fuel Tank (A-331-05A/B/C-D1) : __________%
5. - Normal level : 50 %
- Lube Oil Tank (A-331-05A/B/C-D2) : __________%
- Normal level : between L-H
- Coolant Radiator (A-331-05A/B/C-E1) : __________%
- Normal level : <2.5 cm from
top

Ensure that no alarm in the PCC, protection relay, all faults to be


6.
cleared and/or logged before start.

7. Confirm ventilation fan running

CONFIRM The status below:


- Circuit Breaker Feeder of switchgear 101-HSW-C02A/B – Close
8. - All Circuit Breaker of switchgear 101-HSW-C02AB – Open
- EDG Local/No Operation/Remote Selector Switch – Local
(Manual)

CLOSE the Bus Tie of switchgear 101-HSW-C02A/B By Operator in


Main Substation
9. Note:
341-SS-101
The switchgear 101-HSW-C02 A & B is now connected. Ensure all of step above has
been done then can continue to the next step.

Make sure that all auxiliary equipment is received the power from
10.
external source

Make sure that the Emergency Stop button is fully operational Performed by
11.
Cummins

Connect the PCC to the Laptop via RS485 port to communicate with
12.
the InPower software

40 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

7.2.2 Transient Response Test

No. Action Remark

From the LCP HMI A-331-05A, Keep


communication
with Main
Press the to put the generator set into Manual mode. Substation
341-SS-101

START Engine A-331-05A by pushing from LCP and ensure


1. both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into the
Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line, Coolant
line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Inform to Operator in Main Substation 341-SS-101 that switchgear 101-


2.
HSW-C02A/B will be energized by EDG A-331-05A.

CLOSE the CB of EDG A-331-05A by pushing in LCP A-331-


3. 05A
Note:
The switchgear 101-HSW-C02 A & B is now energized.

Feed with Load as below sequence:


Every time the load change, record the response of EDG to recover the
frequency and voltage, including response time. See in the InPower strip
chart.
a. 0% to 25% load
b. 25% to 50% load
c. 50% to 75% load
4. d. 75% to 100% load
e. 100% to 75% load
f. 75% to 50% load
g. 50% to 25% load
h. 25% to 0% load
i. 100% to 0% load

41 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

5. All data shall be recorded in the Attachment-7 test sheet.

STOP EDG by pressing stop push button from LCP and Ensure EDG
6. shall normal stop (cool down runtime) sequence for complete stop of
EDG package

7. Repeat the step 1-6 for EDG A-331-05B and A-331-05C

7.2.3 Acceptance Criteria

No. Action Remark

Operating limit value of Class G2 ISO 8528-5 2005:


Increasing Load:

Description Value Unit

Frequency -10% ; Hz
time 5 second

Voltage -20% ; V
time 6 second
1.

Decreasing Load:

Description Value Unit

Frequency +12% ; Hz
time 5 second

Voltage +25% ; V
time 6 second

7.3 LOAD SHARING TEST


Prior to this test, First Start test up to Load test has been performed with acceptable result.
The test will involve all EDGs A-331-05A/B/C, MV switchgear 101-HSW-C02A/B in Main
Substation Building, and temporary load bank as dummy load.
Load sharing test will be performed manually through LCP. This test will synchronize all
EDG, then put the EDG with load.
The sequence run between EDG (A-331-05A or B or C) is not mandatory. The following
procedure will run the EDG-A (A-331-05A) first as the lead, followed by A-331-05B & A-331-
05C to synchronize and share the load. Any other sequence based on site condition is
acceptable.

42 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

7.3.1 Pre-start Checks

No. Action Remark

1. Ensure the Switchgear 101-HSW-C02A/B is not energized (dead)

2. Ensure all unused outgoing feeders are racked out.

3. Ensure all CB position is accurately showing at LCP.

Verify that all engine and generator safety checks have been
performed to ensure the engine and generator are fit to run as below
- Operator to ensure mechanical valves are in position before
start- up such as diesel, lube oil, cooling circuit line
4.
- Operator to check & ensure no heavy fault occurred in the EDG
package such as FGS confirm fire, Emergency stop (UCP &
LCP), Engine protection system
- Battery healthy condition status

Ensure lube oil level, Coolant level, Fuel Level is enough for EDG
test
- Diesel Oil Storage Day Tank (D-331-01A/B) : __________%
- Normal level : 8 – 93 %
- Fuel Tank (A-331-05A/B/C-D1) : __________%
5. - Normal level : 50 %
- Lube Oil Tank (A-331-05A/B/C-D2) : __________%
- Normal level : between L-H
- Coolant Radiator (A-331-05A/B/C-E1) : __________%
- Normal level : <2.5 cm from
top

Ensure that no alarm in the PCC, protection relay, all faults to be


6.
cleared and/or logged before start.

7. Confirm ventilation fan running

CONFIRM The status below:


- All Circuit Breaker of switchgear 101-HSW-C02AB – Open
8.
- EDG Local/No Operation/Remote Selector Switch – Local
(Manual)

CLOSE the Bus Tie of switchgear 101-HSW-C02A/B By operator in


9. Main Substation
Note:
341-SS-101
The switchgear 101-HSW-C02 A & B is now connected. Ensure all of step above has

43 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


been done then can continue to the next step.

Make sure that all auxiliary equipment is received the power from
10.
external source

Make sure that the Emergency Stop button is fully operational Performed by
11.
Cummins

7.3.2 Load Sharing Test

No. Action Remark

From the LCP HMI A-331-05A, Keep


communication
with Main
Press the to put the generator set into Manual mode. Substation
341-SS-101

START engine A-331-05A by pushing from LCP and ensure


1. both ventilation fan and radiator fan are running.
Note:
The start button must be pressed within 10 seconds since switching to Manual mode.
Failure to do this results in the control mode defaulting, putting the generator set into the
Off mode
During running check condition of engine, Generator, Aux Equipment, Fuel Line, Coolant
line, and lube oil line, ensure the unit working properly and no leak.
Check vibration of Engine and Generator

Inform to Operator in Main Substation 341-SS-101 that switchgear 101-


2.
HSW-C02A/B will be energized by EDG A-331-05A.

CLOSE the CB of EDG A-331-05A by pushing in LCP A-331-


3. 05A
Note:
The switchgear 101-HSW-C02 A & B is now energized.

4. START EDG A-331-05B

5. Wait until EDG A-331-05B synchronized, and allow the CB to close.

6. CLOSE the CB of EDG A-331-05B by pushing in LCP A-331-


05B
Ensure the EDG does not trip with reverse power.

44 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

No. Action Remark


Load share control system is switched on by paralleling breaker closure. ILS line is now working.

7. START EDG A-331-05C

Wait until EDG A-331-05C synchronized, and allow the CB to close.


8.
Load share control system is switched on by paralleling breaker closure. ILS line is now working.

CLOSE the CB of EDG A-331-05C by pushing in LCP A-331-


9. 05C
Ensure the EDG does not trip with reverse power.
Load share control system is switched on by paralleling breaker closure. ILS line is now working.

Monitor for 5 minutes.


10.
Record measured values in the Test Sheet (Attachment 2)

STOP EDG by pressing stop push button from LCP and Ensure EDG
11. shall normal stop (cool down runtime) sequence for complete stop of
EDG package

7.3.3 Acceptance Criteria

No. Action Remark

1. Load can be properly shared to all EDG without trip

7.4 TEST/CHECK SEQUENCE OF OPERATION (EDG & MCP)


Test shall be carried out according to EDG logic diagram. Test can be carried out during test
with load.
Operation philosophy of PowerCommand Control 3.3 local control panel, switchgear panel
and MCP panel shall be demonstrated through possible simulation (in the case of
switchgear, grid supply for synchronization are not available during testing. Demonstration of
all tests / scenarios may not be possible).

7.4.1 Acceptance Criteria

No. Action Remark

1. Operation sequence is performed according to logic diagram

45 of 46
Doc. No. : 26071-100-586-GSX-00028

Job No. : 26071 Rev.00A

8 ATTACHMENT
Attachment 1 - EDG First Start Checklist
Attachment 2 - Synchronization Test Report
Attachment 3 - Alarm & Shutdown Test Report
Attachment 4 - Load Sharing Verifying Test Report
Attachment 5 - Noise Measurement Test Report
Attachment 6 - Vibration Measurement Test Report
Attachment 7 – Transient Response Test Report
Attachment 8 – Load Test Report

46 of 46
ATTACHMENT-1

26071‐V67‐331‐A‐105‐GEN1‐00074_Attachment #1

Generator set start-up checklist Coolant heater operational


Open & enclosed generator sets Leak check
This checklist should be used to validate the completion DCA dosing cartridges fitted & valves open
of generator set pre-commissioning. A check-list should
be completed for each generator set of a multiple Remote mounted radiator systems
installation. Radiator, engine & pipework checked for leaks
Project Details Coolant heater operational
Project
Name ...………………………………………………… Fans, pumps and controls checked
………………………………………...…….………………… Leak check

Customer (End User).………………………..……... DCA dosing cartridges fitted & valves open
…………………..……………………… Heat exchanger & cooling tower systems
Address……….…………………...…………………………
………………………………………………………………… System, engine & pipework checked for leaks
………………………………………………………..… Coolant heater operational
Customer representative…………………………….
Secondary cooling system checked
Tel. No
………………………..………………………………… Fans, pumps and controls checked
Email…………………………………………………………
DCA dosing cartridges fitted & valves open
…..
Generator set details Legionnella dosing checked where applicable
Generator set model…………………………… Record dosing chemical & concentration...............
Generator set serial number………………….Set no…
Diesel Fuel System
Control type……………………………………...
Control serial number……………………………………….. Bulk storage facility
Isolating valves correctly positioned
System control type (if applicable)……………… Transfer pump & controls operational
Generator set environment and services Pipeline / tank heating system operational
Fill point alarm operational
Precommissioning work & checklist complete Leaks check
Storage facility secure
Surroundings clean & clear from obstruction

Lighting / heating, etc., systems operational Day tank


Isolating and solenoid valves checked
Observations…………………………………....
Tank filled
………………………………………………………………… Spillage containment & alarms operational
Safety Checks Transfer pump operational
Leak check
Ensure starting is inhibited until start-up is required Fire valves & release tested and operational

Set clean and fully assembled Gas fuel System


No loose materials near generator set Isolating valves correctly positioned
Regulator set to correct pressure
Air ducts clear and clean
Gas leak detection equipment operational
Access & egress routes unobstructed & labelled Double shut-off device operational
Control & maintenance positions unobstructed Leak test complete
Purging complete
Room secure – no unauthorised access

Personnel warned of start-up process Fire alarm / suppression system


Fire alarm / suppression system commissioned
Cooling System
Suppression system lock-off operational
Coolant type………………………………………. Operator instructed in fire system operation
Set mounted radiator
Radiator, engine & pipework checked for leaks Lubrication system
Engine oil pan filled to correct level
Belts & guards checked for security / slipping
Oil make up system operational
ATTACHMENT-1

26071‐V67‐331‐A‐105‐GEN1‐00074_Attachment #1

Starting system Generator set voltage & frequency correct to order


Control system calibrations checked
Battery starting
Batteries filled, installed and connected Phase rotation checked
Battery charger commissioned Paralleling sets phase coincidence check
Generator set switchgear manual operation correct
Compressed air / hydraulic starting
Local stop / emergency stop control checked
Isolating valves correctly positioned
Remote start / stop / emergency stop checked
Compressor operational
HP & LP air / hydraulic pressures checked
Condensate drained
Generator set load test
Note: Load test is carried out on customer’s site load
Exhaust system unless agreed in writing prior to start-up. Artificial load
Check security of bellows, pipework & muffler
bank test will be performed using resistive load unless
Check cowl and/or rain cap are operational
otherwise specified.
Check water drain pipework and valves correct
Leak check
Check for exhaust gas recirculation Load test completed using customer’s load
Record load achieved………………………kW
Ventilation & attenuation Load bank test (if applicable)
Check louvers are clear and operational Check load bank voltage & power capability
Forced ventilation system operational if applicable Check cables installed correctly & tightened

Check for hot air recirculation Energise auxiliary supplies and check functionality
Load test completed
Electrical system
Result sheet completed
Control systems Record load achieved………………………kW
Auxiliary supplies energised Record power factor……………………………
Generator set local controls checked System start-up completion
Generator set remote controls checked Generator set operational
Generator set system controls checked Changeover / transfer switch operational

Customer remote indication / controls checked Paralleling switchgear operational


Automatic operations checked
Master control operational
Changeover switchgear / transfer switch
All safety shutdowns and warnings operational
Auxiliary supplies energised
Electrical HV/MV/LV rules and procedures in place
Voltage / phase rotation checked Comments on any item that may affect acceptance:
All covers in position ……………………………………………………………
……………………………………………………………
……………………………………………………………
Paralleling switchgear ……………………………………………………………
Auxiliary supplies energised ……………………………………………………………

Indications correct Checklist completed by………………………….


Date………………………………………………………
All covers in position ……...
Print Name……………………………………………….
Company…………………………………………………
Note: Completion of this checklist does not relieve the installer of contract
obligations.
Initial start-up
Manual start-up, idle & full speed checks complete
ATTACHMENT-2

SYNCHRONIZATION TEST REPORT


26071-V67-331-A-105-GEN1-00074_Attachment #2

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071-203-PO-MGED-00067 Job No: 26071 Date:
System: Report No.:
Sub-system: Drawing/Area Ref:
Contractor: Equipment No.:

SYNCHRONIZATION TEST

G1 CB closed G1 G2 G3 G4 Bus VT

R-Y (volts)

Y-B (volts)

B-R (volts)

R-N (volts)

Y-N (volts)

B-N (volts)

R-E (volts)

Y-E (volts)

B-E (volts)

N-E (volts)

Phase Rot.

R-R (volts) N/A N/A N/A N/A

Y-Y (volts) N/A N/A N/A N/A

B-B (volts) N/A N/A N/A N/A


G2 CB closed G1 G2 G3 G4 Bus VT
R-Y (volts)
Y-B (volts)
B-R (volts)
R-N (volts)
Y-N (volts)
B-N (volts)
R-E (volts)
Y-E (volts)
B-E (volts)
N-E (volts)
Phase Rot.
R-R (volts) N/A N/A N/A N/A
Y-Y (volts) N/A N/A N/A N/A
B-B (volts) N/A N/A N/A N/A
ATTACHMENT-2

G3 CB closed G1 G2 G3 G4 Bus VT
R-Y (volts)
Y-B (volts)
B-R (volts)
R-N (volts)
Y-N (volts)
B-N (volts)
R-E (volts)
Y-E (volts)
B-E (volts)
N-E (volts)
Phase Rot.
R-R (volts) N/A N/A N/A N/A
Y-Y (volts) N/A N/A N/A N/A
B-B (volts) N/A N/A N/A N/A
G4 CB closed G1 G2 G3 G4 Bus VT
R-Y (volts)
Y-B (volts)
B-R (volts)
R-N (volts)
Y-N (volts)
B-N (volts)
R-E (volts)
Y-E (volts)
B-E (volts)
N-E (volts)
Phase Rot.
R-R (volts) N/A N/A N/A N/A
Y-Y (volts) N/A N/A N/A N/A
B-B (volts) N/A N/A N/A N/A
REMARKS

CERTIFIED, TESTED AND CHECKED:

CONTRACTOR:
Name Signature Date

CUMMINS:
Name Signature Date

CLIENT:
Name Signature Date
ATTACHMENT-3

ALARMS AND SHUTDOWN TEST REPORT


26071‐V67‐331‐A‐105‐GEN1‐00074_Attachment #3

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071‐203‐PO‐MGED‐00067 Job No: 26071 Date:
System: Report No.:
Sub‐system: Drawing/Area Ref:
Contractor: Equipment No.:
Station Reference:
DG Model/S.I. No.
Engine Model/S.I. No.
Type:
Capacity:
No. Description Checked Remarks
1 Emergency Stop N/A
2 Coolant temperature alarm 102 deg.C
3 Coolant temperature shutdown 107 deg.C
4 Lube oil low pressure alarm 15 psi @ idle
5 Lube oil low pressure shutdown 10 psi @ idle
6 Fuel temp high alarm 120 deg.C
7 Fuel temp high shutdown 125 deg.C
8 Over current Shutdown 5%
9 Over voltage Shutdown 5%
10 Over frequency/ Over speed shutdown 5%
11 Alternator temp high shutdown 165 deg.C
12 Bearing temp high shutdown 85 deg.C
13 High exhaust stack temp alarm 677 deg.C
RESULT

CERTIFIED, TESTED AND CHECKED:

Cummins:

Name Signature Date

Contractor:

Name Signature Date

Client:

Name Signature Date


ATTACHMENT-4

LOAD SHARING VERIFYING TEST REPORT


26071‐V67‐331‐A‐105‐GEN1‐00074_Attachment #4

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071-203-PO-MGED-00067 Job No: 26071 Date:
System: Report No.:
Sub-system: Drawing/Area Ref:
Contractor: Equipment No.:
Station Ref: Alternator Model:
LOAD SHARING VERIFICATION TEST

TEST EQUIPMENT USED:

Voltage line Current (A) KW KVA PF Hz RPM


to neutral
Voltage line to line (V) (V)

L1-L2 L2-L3 L3-L1 L1-N L2-N L3-N L1 L2 L3

G-1

G-2

G-3

G-4

G-5

REMARKS

CERTIFIED, TESTED AND CHECKED:

CONTRACTOR:
Name Signature Date

CUMMINS:
Name Signature Date

CLIENT:
Name Signature Date
ATTACHMENT-5

NOISE MEAUREMENT OF ENCLOSURE TEST REPORT


26071‐V67‐331‐A‐105‐GEN1‐00074_Attachment #5

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071-203-PO-MGED-00067 Job No: 26071 Date:
System: Report No.:
Sub-system: Drawing/Area Ref:
Contractor: Equipment No.:
Station Ref: Alternator Model:
Engine Model: Sr. No.
Sr. No Rated Power:
Rated Power: Frequency: 50Hz
Speed: Voltage:
Capacity: Power Factor:
NOISE MEASUREMENT OF ENCLOSURE TEST (REFER TO MEASUREMENT LOCATIONS IN THE FIGURE BELOW)

TEST EQUIPMENT USED:

Load Speed POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 Remarks

REMARKS

CERTIFIED, TESTED AND CHECKED:

CONTRACTOR:
Name Signature Date

CUMMINS:
Name Signature Date

CLIENT:
Name Signature Date
ATTACHMENT-5

NOISE MEASUREMENT LOCATIONS


ATTACHMENT-6

VIBRATION MEASUREMENT OF GENSET TEST REPORT


26071-V67-331-A-105-GEN1-00074_Attachment #6

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071-203-PO-MGED-00067 Job No: 26071 Date:
System: Report No.:
Sub-system: Drawing/Area Ref:
Contractor: Equipment No.:
Station Ref: Alternator Model:
Engine Model: Sr. No.
Sr. No Rated Power:
Rated Power: Frequency: 50Hz
Speed: Voltage:
Capacity: Power Factor:
VIBRATION MEAUSREMENT OF GENSET TEST (REFER TO TEST POSITIONS IN FIGURE BELOW)

TEST EQUIPMENT USED:

Load POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 POS 8 Remark

REMARKS

CERTIFIED, TESTED AND CHECKED:

INSPECTOR:
Name Signature Date

CUMMINS:
Name Signature Date

CLIENT:
Name Signature Date
ATTACHMENT-6

Vibration measurement location

Vibration acceptance limit (ISO 8528-9)

Alternator side-28 mm/sec. (Location – 5y, 5z, 6, 7 & 8)

Engine side – 45mm/sec. (Location – 1, 2, 3& 4)


ATTACHMENT-7
ATTACHMENT-8

SITE PRE-COMMISSIONING,
C
C Sale�and
Service
• Korea COMMISSIONING TEST PRECEDURE
Attachment #2. Genset Load Test Report

55-57-15

C
55-57-15
hl1n11nd
Service
, Korea

GENERATOR LOAD TEST REPORT


PROJECT CUSTONER ::
CUSTONER DATE:
DATE:
ENG NE MODEL
----------
----------
ENGINE SE3ML NO
--------
--------
.0gN0.:
-------
-------
GENSET MODEL
GENSET MODEL GEN3ET SER.
GEN3ET SER.A
ALL NO HOURMETER:
HOURMETER:
NO
------
Loll..r
------
as Loll..r ALTEEM TCR
TCR MOIL
MOIL NO. AL.TEEM TOR SERAL NO.
ENGINE RATING 2PH FE: CPL ::
CPL vaL.TS
vaL.TS
-----
----- ----
---- ----
----
ALTERA TOR RATING VA KN : Pr : BP
-----
----- ----
---- ----
----
PHASE CUE3ENT AMPS .PF
.PF

□ □ [es
nor.as [_] a.on
nor a.on a [lasso
[lasso [es
T'IPE omsr
T'IPE omsr STANDA RD
STANDA RD FACTORY
FACTORY TEST Wlll!NESS TBSI
Wlll!NESS l'/PE OFLUB.
l'/PE OFLUB. OIL TYPE OE RE
RE ::
TEST TBSI OIL
-----
-----
DURA TICN AVE. TEMF VOLTAGE AMPERES WATER TEMP OL PRESSURE
TIM­ L0AD% KN RN 5RE0H
5RE0H PF
PF ·¢ FEM3KS
HRS ¢
Y
Y Y3 3R p 33
·¢ P5
'

L.L.CCW
W OIL
OIL PRESSURE
PRESSURE ALAM
ALAM HIGH WATER TENP ALARM cc 0VERSPEED:
0VERSPEED:
---- BP
----
L.L.CCW
W OIL
OIL PRESSURE
PRESSURE SHLTDON HIGH WATER TEIP SHHJTDOWN ¢ 0THERS ::
0THERS
SHLTDON
---
--- ----------
----------
TESTED
TESTED BYI(NVE
I(NVESIGNATURE]
SIGNATURE] WITNESS BY(NAVESIGNATURE]
SIGNATURE]
DATE TESTED:
TESTED: DATE
DATE WTHNES3