Professional Documents
Culture Documents
TP 1
LECTURED BY:
SORN DARONG
ENGINEERING’S DEGREE
DEPARTMENT OF ELECTRICAL AND ENERGY ENGINEERING
INSTITUTE OF TECHNOLOGY OF CAMBODIA
PHNOM PENH
2021-2022
Student’s name ID
1. PHE MENGHOUR e20190801
2. NOV DAVANN e20190712
3. KEANG LYHOUR e20190363
Table of Content
Objective: ............................................................................................................................ 5
Part 1: Utilize what you’re learned to complete the following tasks: ........................................ 5
Part 2: for the following section below, use your knowledge from course work and the
reference provided to perform calculation aiding by excel (Section 1 and section 2):.............. 5
Section 1: LV System ........................................................................................................... 5
Section 2: MV System .......................................................................................................... 5
Section 3: HV System .......................................................................................................... 6
Part 3: Using software (Etap, Powerworld) to analyze the system and see how well the
designed system in part 2 perform.............................................................................................. 6
Solution ....................................................................................................................................... 7
Part 1: Utilize what you’re learned to complete the following tasks: ........................................ 7
Part 2: for the following section below, use your knowledge from course work and the
reference provided to perform calculation aiding by excel (Section 1 and section 2):............ 17
Section 1: LV System ......................................................................................................... 26
Section 2: MV System ........................................................................................................ 29
Section 3: HV System ........................................................................................................ 32
Part 3: Using software (Etap, Powerworld) to analyze the system and see how well thr
designed system in part 2 perform............................................................................................ 34
Conclusion......................................................................................................................... 36
Reference ........................................................................................................................... 37
2
List of Figure
3
Figure 34: LV System Cable Sizing .......................................................................................... 26
Figure 35: LV Busbar Sizing .................................................................................................... 27
Figure 36: LV System CB Sizing (Line A) ................................................................................ 27
Figure 37: LV System CB Sizing (Line B) ................................................................................ 28
Figure 38: LV System Voltage Drop ........................................................................................ 28
Figure 39: MV System .............................................................................................................. 29
Figure 40: MV System Cable Sizing ......................................................................................... 29
Figure 41: MV System Cable Sizing (Spec).............................................................................. 30
Figure 42: MV System Busbar Sizing ....................................................................................... 30
Figure 43: MV Impedance Calculation .................................................................................... 31
Figure 44: MV System CB Sizing ............................................................................................. 31
Figure 45: MV System Volage Drop ........................................................................................ 31
Figure 46: HV Single Line Diagram ........................................................................................ 32
Figure 47: HV Single Line Diagram with Notation ................................................................. 32
Figure 48: Power Flow Direction ............................................................................................ 33
Figure 49: Power Flow at Hospital ......................................................................................... 34
Figure 50: Power Flow at HV/MV ........................................................................................... 34
Figure 51: Power Flow at MV/LV............................................................................................ 35
List of Table
Table 1: Total Current in One Room ....................................................................................... 19
Table 2: Total Current in Administration Room ...................................................................... 19
Table 3: Total Current in Parking............................................................................................ 19
Table 4: Total Current in Line 1 .............................................................................................. 19
Table 5: Total Current in Line 2 .............................................................................................. 20
Table 6: Total Current in Hospital Line................................................................................... 20
Table 7: Cross-Sectional of Hospital Load .............................................................................. 21
Table 8: Discussion Table ........................................................................................................ 35
4
Power System Architecture
➢ Objective:
On the basic of the data provided and the information in Section B, we could
begin our laboratory as follows:
▪ Describe the entire power system from power plant to LV consumer also make
a simple schematic for it.
▪ Create a list of critical components for each voltage level (LV, MV, and HV)
and include a brief description of each component’s feature.
▪ Indeed, there are numerous layout options for power system. Create your own
layout for the system by following the layout provided in figure 1 and 2. To
begin, you’ll want to do the following:
• Utilize the distance specified in the layout above to locate the
transformer and each load.
• Construct your own system based on what you believe is the most
reliable and cost-effective design.
Part 2: for the following section below, use your knowledge from course work and the
reference provided to perform calculation aiding by excel (Section 1 and section 2):
▪ Section 1: LV System
▪ Section 2: MV System
5
- Perform power flow analysis
- Power quality analysis (Voltage drop, Power factor,
Harmonic,…etc).
▪ Section 3: HV System
• Draw single line diagram for 3 bus system, including the generators
and load power
• Perform power flow analysis between those 3 areas.
Part 3: Using software (Etap, Powerworld) to analyze the system and see how well the
designed system in part 2 perform.
6
Solution
▪ Describe the entire power system from power plant to LV consumer also make
a simple schematic for it.
7
▪ Create a list of critical components for each voltage level (LV, MV, and HV) and
include a brief description of each component’s feature
• LV (Low Voltage)
Critical component
Figure 2: LV Cable
They will automatically trip when the current through it exceeds a pre-
determined value.
8
3. RCCB
4. Switch
9
5. Fuse
The fuse breaks the circuit if a fault in an appliance causes too much
current to flow. It protects the wiring and the appliance if something goes
wrong. The fuse contains a piece of wire that melts easily.
6. Busbar
Busbars are metal bars used to carry large amounts of current. Often
made of copper or aluminum, every home electrical panel has busbars
to distribute ac power to the rows of circuit breakers. Moreover, busbars
have no insulation, they're protected by a separate enclosure.
10
• MV (Medium Voltage)
1. Vacuum Circuit Breaker
2. Switch
11
3. Contactor
4. Current-limiting fuse
5. Disconnecting Switch
When a circuit breaker is removed and racked out, the circuit can be
earthed by operating this earthing switch. Earthing switches are usually
used in conjunction with isolators. When the isolator isolates the
circuits, the earthing switches will ensure to discharge any residual
charges which may have accumulated.
12
Figure 12: Earthing Switch (MV)
6. Current transformer
• HV (High Voltage)
1. High Voltage Capacitor
From figure 17, we can see that the length had been defined by multiple
mathematically formula.
15
• Construct your own system based on what you believe is the most
reliable and cost-effective design.
From figure 18 and 19, we are able to see our own concept design based on
what we believe is the most reliable and cost-effective design.
16
Part 2: for the following section below, use your knowledge from course work and the
reference provided to perform calculation aiding by excel (Section 1 and section 2):
▪ Hospital Load:
- LV cable (Hospital)
17
Figure 21: Hospital Schematic
From figure 22, we are able to calculate the current Ib,correct in which room
needed.
Room
Equipment P(KW) V(KV) Cos(phi) Ib Ku Ks Ib,correct
Air Conditioner 1.2 0.22 0.9 6.06 1
TV 0.1 0.22 0.9 0.5 1
Fridge 0.1 0.22 0.9 0.5 1
18
Water Heater 3.6 0.22 0.9 18.18 1
Water Boiler 2.5 0.22 0.9 12.62 1
Lighting 0.05 0.22 0.9 0.25 1
TOTAL 7.55 0.22 0.9 38.13 1 0.8 30.5
Table 1: Total Current in One Room
Administration Room
Equipment P(KW) V(KV) Cos(phi) Ib Ku Ks Ib,correct
Air Conditioner 4.5 0.22 0.9 22.72 1
TV 0.2 0.22 0.9 1.01 1
Fridge 0.2 0.22 0.9 1.01 1
Lighting 0.2 0.22 0.9 1.01 1
TOTAL 5.1 0.22 0.9 25.75 1 1 25.75
Table 2: Total Current in Administration Room
Parking
Equipment P(KW) V(KV) Cos(phi) Ib Ku Ks Ib,correct
Lighting 0.2 0.22 0.9 1.01 1
TOTAL 0.2 0.22 0.9 1.01 1 0.8 1.01
Table 3: Total Current in Parking
19
Line 2: 10 Room
Ib (Per Room) 30.50
Ks 0.8
Safety factor 1.2
Total: (Ib, Line 1) 219.63
Table 5: Total Current in Line 2
From table 1 to table 6, we can see that we had obtained the current in each
room needs as well as the main line. After that we are able to proceed to the next
step which is cross-sectional sizing.
20
From figure 22, we are able to obtain the Cross-Sectional of the line that we had
calculated earlier in table 1 to table 6.
From table 7, we get the value of cross-sectional of each line by applying method
3 for single phase and method 3 for three phases. Moreover, cross-sectional of
line 3 and 4 are identical to line 2 since it is the same layout of 10 room combine
In order to choose the correct sizing for transformer, we first have to know the
total apparent power of our load before deciding transformer. For instance, in
this case through calculation, we obtain total apparent power of hospital load
is 144857.61VA (144KVA). After that, we decided to choose transformer with
the size of 150KVA.
From figure 21, we can see that in order to find size for busbar, we need to know
how much current is running on the busbar its self. As we know line 1 to line 4
are connected to busbar which means that the current flow in busbar is equal
the combination of current in line 1 to line 4 so we get Ibusbar is 663.38A (1
Phase).
21
Figure 24: Busbar Size
From figure 24, we can see that the busbar that we use has cross-sectional
of 150mm2 with the length of 20meter (Assumption).
22
Figure 26: Short Circuit Current Line 2 (Hospital)
23
Figure 28: Short Circuit Current Line 4 (Hospital)
From figure 25 to 28, we obtained the Isc or short circuit current which means
that we can also obtain what type and value of CB, we are going to use based
on Isc.
24
Figure 30: Voltage Drop Line 2 (Hospital)
25
From figure 29 to 32, we can obtain the value of voltage from each line of
hospital loads.
▪ Section 1: LV System
Before we proceed any further, here is the LV diagram with notation on it for
easy understanding the following steps.
- LV cable sizing
From figure 34, we are able to obtain cross-sectional of LV system. In this part,
we choosing method 3 of installation based on figure 23 and using multiple
26
cables when it is over 100mm2 to prevent overweight on the tray or transmission
plus cost efficiency.
- Busbar sizing
The same above method apply for finding busbar, we obtain the cross-sectional
of each busbar with the length of 20m each (Assumption).
In order to choose the correct sizing for transformer, we first have to know the
total apparent power of our load before deciding transformer. For instance, in
this case through calculation, we obtain total apparent power of Transformer 2
is 462KVA and Transformer 3 is 353.82 KVA. After that, we decided to choose
transformer with the size of 500 KVA for Transformer 2 and 400KVA for
Transformer 3
- LV Protection Sizing
27
Figure 37: LV System CB Sizing (Line B)
From figure 36 to 37, we obtained the Isc or short circuit current which means
that we can also obtain what type and value of CB, we are going to use as well
based on Isc.
From figure 38, we can obtain the value of voltage from each line of LV System.
28
▪ Section 2: MV System
Before we proceed any further, here is the MV diagram with notation on it for
easy understanding the following steps.
- MV Cable Sizing
29
Figure 41: MV System Cable Sizing (Spec)
- MV Busbar Sizing
The same above method apply for finding busbar, we obtain the cross-sectional
MV system busbar with the length of 20m each (Assumption).
In order to choose the correct sizing for transformer, we first have to know the
total apparent power of our load before deciding transformer. For instance, in
this case through calculation, we obtain total apparent power of Transformer 1
is 40.8MVA. After that, we decided to choose transformer with the size of 50
MVA for Transformer 1.
- MV Protection Sizing
Before we proceed to find the Isc for CB sizing, we first need to calculate
impedance load first since it is different from LV system.
30
Figure 43: MV Impedance Calculation
After obtaining the impedance result, we shall begin the process of finding Isc
From figure 44, we are able to obtain value of Isc and CB value for protection.
- MV Voltage Drop
31
From figure 45, we obtain the value of voltage drop of MV System.
▪ Section 3: HV System
- Draw single line diagram for 3 bus system, including the generator’s
power and load’s power.
From figure 47, we can identify which one is generator’s bus, load’s bus, and
slack bus by observing the given data.
• Slack Bus (swing bus) defined as a V𝜑 bus, is used to balance the active
power (P) and reactive power (Q) in a system when performing load
flow.
• Load bus defined as PQ bus, is a type of node that incorporates both
reactive power (Q) and active power (P).
• Generator bus is the bus that connects to generator to it’s generating
transformer.
32
- Perform power flow analysis between those 3 areas or buses
Generally, we don’t know how the power flows between these 3 areas or
buses unless we do calculation by given formula below:
𝑉1 − 𝑉2
𝐼𝑧 =
𝑍12
• If the current’s result is positive which means power flows from area
1 to area 2 or from bus 1 to bus 2.
• If the current’s result is negative which means power flows the
opposite way.
- What if fault occur at any of the area or bus?
When fault occur on either one of slack bus or generator, load bus can obtain
power from the bus that doesn’t have fault and when it obtains enough
power, it will transfer to the bus that fault took place.
When fault occur on both of generator and slack bus, load bus will have
some power from bus that don’t have fault.
33
• Fault on load bus
When fault occur on load bus, slack bus and generation should
complimented each other since there is no load. (Normally it doesn’t
happen).
Part 3: Using software (Etap, Powerworld) to analyze the system and see how well thr
designed system in part 2 perform.
34
Figure 51: Power Flow at MV/LV
- Discussion
35
Since full system is a board system with numerous types of loads, we
cannot make a discussion about all the loads. That is why we pick some
part of the system to make a discussion as shown in table 8.
We can see that there are slightly different in terms of result between
hand calculation in excel and ETAP software. First of all, it is
calculation tolerance. As we know that some of number, we left out
because we only take 2 digits when the rest is remained untouched and
some of value, we increase to its maximum for easy calculation. With
that being said, we will see the difference at the end result. Secondly,
we use difference type of cable. For instance, we wish to use Cu cable
for this install unfortunately, the manufacturing doesn’t have the cable
we need so we end up using difference type of cable. Thirdly, we use
difference c.s.a of cable. We know that using different c.s.a can result
in difference in current flow, and difference in voltage drop.
▪ Conclusion
After discussion, we can conclude that there are 3 factors that leads error happen such
as
✓ Tolerance in calculation.
✓ Differences type of cables are used.
✓ Difference C.S.A of cable are used.
36
▪ Reference
37