Minutes of Meeting
MINUTES OF MEETING HELD BETWEEN M/S GE T&D CHENNAI, M/s TSTRANSCO AT
220/132/33KV TSTRANSCO PEDDAGOPATTI SS DATED ON 13.03.2024.
Organization Represented by Signature
M/S TSTRANSCO
M/S TSTRANSCO
Work Accomplished:
Substation Circuit/product Work done Remarks
DATE: 13-03-2024
Page 3 of 8
Visit Document
Visit Details
Project : KXH5/KXW7
TVM 1- (J PADU 2,100 MVA 1 HV,LV,100 Changed the Modbus address and Scaling
4 MVA 1 HV and 2 HV 4 nos imp-MWH -?) same witnessed by M/s TSTRANSCO. Closed
DATE: 13-03-2024
Page 4 of 8
Visit Document
B301,302 & 303 CB not closing from SAS
& during fault :only 86 relay Checked and found ok Same witnessed by
9 showing ,not showing E/L,O/L M/s TSTRANSCO. Closed
132 kv SLD chilakallu name change as Modified in database same witnessed by
10 pammy M/s TSTRANSCO Closed
system architecture:- event Installed the Printer drivers in all PCS same
11 printer&colour printer to be arranged witnessed by M/s TSTRANSCO Closed
Completed the Testing same witnessed by
12 auto DR not generating M/s TSTRANSCO. Closed
Troubleshooted and reconfigured the
Archive crawler same witnessed by M/s
13 auto daily report not generating TSTRANSCO. Closed
alarams:-LBB initiation of PTRs
frequently pop up,start alarms changed the Profiles in database same
14 frequently pop up Witnessed by M/s TSTRANSCO Closed
ring formation and redundancy of N/W Checked and Verified same witnessed by
15 has to be checked M/s TSTRANSCO. Closed
Line VT- to be changed as Line CVT and Modified in database same witnessed by
16 Bus VT as PT M/s TSTRANSCO Closed
Same configured in database and loaded in
In Gateway need to configure three servers and gateway same witnessed by
17 control centers M/s TSTRANSCO. Closed
DATE: 13-03-2024
Page 5 of 8
Visit Document
COMMON POINTS:
M/s GE SAS Engineer started the SAVT (1000hrs Cumulative test) in PEDDAGOPATTI SS on
13.03.2024 at 12:00PM in the presence of M/s TSTRANSCO.
DATE: 13-03-2024
Page 6 of 8
Visit Document
RMA DETAILS
Project : KXH5/KXW7
Sl.
RMA Details REMARK
No
Raised the RMA for the same. As per
B205 BCU LHMI LCD Display
1 PO terms and conditions GE will
Found Faulty
Revert Back.
DATE: 13-03-2024
Page 7 of 8
Visit Document
Customer : M/S TSTRANSCO
Organization : M/S TSTRANSCO
Site : 220/132/33KV TSTRANSCO PEDDAGOPATTI SS
GE Engineer : N S NARESH
Did the Service engineer handover the catalogue for Retrofit / Training
GENERAL:
Excellent Average Poor
Response Time
Quality of Response
Customer Name :
Designation :
Seal of the Customer :
DATE: 13-03-2024