Name of the Site: 220/132/33KV TSTRANSCO PEDDAGOPATTI SS

Customer: M/s TSTRANSCO

Sub Station: 220/132/33KV TSTRANSCO PEDDAGOPATTI SS

Scope of Work: PUNCH POINTS

K Ref: KXH5/KXW7

Visit Document
For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 1 of 8
Visit Document

Contents

MINUTES OF MEETING 3

VISIT DETAILS 4

ADDITIONAL POINTS 7

CUSTOMER FEEDBACK FORM ON GE T&D SERVICES 8

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 2 of 8
Visit Document
Minutes of Meeting
MINUTES OF MEETING HELD BETWEEN M/S GE T&D CHENNAI, M/s TSTRANSCO AT
220/132/33KV TSTRANSCO PEDDAGOPATTI SS DATED ON 13.03.2024.
Organization Represented by Signature

M/s GE Mr. N S NARESH

M/S TSTRANSCO

M/S TSTRANSCO

Customer Service Call Objective:


Service Request (Please tick √ )
Substation & Applicatio
Commissi Trouble Relay Refurbish
Circuit n/
oning Shooting Testing ment
Settings
220/132/33KV
TSTRANSCO 
PEDDAGOPATTI
SS

Work Accomplished:
Substation Circuit/product Work done Remarks

Additional Work done:


Substation Circuit/product Work done Remarks

Attachments to this Document (Please tick)


 Comments by Customer
 Additional work Request
Request for Material against Damages / shortage
 Commissioning Completion Certificate

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 3 of 8
Visit Document
Visit Details

Project : KXH5/KXW7

Site : 220/132/33KV TSTRANSCO PEDDAGOPATTI SS

Customer : M/s TSTRANSCO

Panel / Relay Type : Control Relay Panel/Numerical protection relay

Drawing Reference No. : KXH5/KXW7

M/s GE Engineer Reported to 220/132/33KV TSTRANSCO PEDDAGOPATTI site on 07/02/24 for


attending the below mentioned SAS Punch points

SI SAS PROBLEMS AT 220 KV SS


Remark Status
NO PEDDAGOPATHI

33 KV KONIJERLA name change ,K Modified in database same witnessed by


1 should be capital M/s TSTRANSCO Closed
Modified in database same witnessed by
2 33 kv PT position change to left side M/s TSTRANSCO Closed
voltage difference in Sync check220KV
and 132KV To show the Voltage difference, Minimum
(bays:201,202,205,101,103,104,105,106, value should be >1V same explained to
3 107 & 108) M/s TSTANSCO. Closed

TVM 1- (J PADU 2,100 MVA 1 HV,LV,100 Changed the Modbus address and Scaling
4 MVA 1 HV and 2 HV 4 nos imp-MWH -?) same witnessed by M/s TSTRANSCO. Closed

Changed the Modbus address and Scaling


5 TVM all readings not matching exactly. same witnessed by M/s TSTRANSCO. Closed

TVM-2 (33KV name change 33 kv Modified in database same witnessed by


6 pangidi) M/s TSTRANSCO Closed
Minimum current of(6% rated current)
pf value not showing properly in 132KV required for showing the PF value same
7 (B101,B104)BAYS Explained to M/s TSTRANSCO. Closed
That will get updated/reseted when next
fault distance not reset in P442-distance fault comes same explained to M/s
8 relay TSTRANSCO. Closed
For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 4 of 8
Visit Document
B301,302 & 303 CB not closing from SAS
& during fault :only 86 relay Checked and found ok Same witnessed by
9 showing ,not showing E/L,O/L M/s TSTRANSCO. Closed
132 kv SLD chilakallu name change as Modified in database same witnessed by
10 pammy M/s TSTRANSCO Closed
system architecture:- event Installed the Printer drivers in all PCS same
11 printer&colour printer to be arranged witnessed by M/s TSTRANSCO Closed
Completed the Testing same witnessed by
12 auto DR not generating M/s TSTRANSCO. Closed
Troubleshooted and reconfigured the
Archive crawler same witnessed by M/s
13 auto daily report not generating TSTRANSCO. Closed
alarams:-LBB initiation of PTRs
frequently pop up,start alarms changed the Profiles in database same
14 frequently pop up Witnessed by M/s TSTRANSCO Closed
ring formation and redundancy of N/W Checked and Verified same witnessed by
15 has to be checked M/s TSTRANSCO. Closed
Line VT- to be changed as Line CVT and Modified in database same witnessed by
16 Bus VT as PT M/s TSTRANSCO Closed
Same configured in database and loaded in
In Gateway need to configure three servers and gateway same witnessed by
17 control centers M/s TSTRANSCO. Closed

Field Transducers are found faulty. M/s


Tap,wti,oti( B203,B204,109 & TSTRANSCO need to replace the same.
18 110)100MVA & 31.5PTR PTR-1 & 2 scope of work: M/s TSTRANSCO. Open
MFM meters are found faulty. TSTRANSCO
need to replace the same.
19 MFM readings not matching exactly. scope of work: M/s TSTRANSCO. Open
Scaling found ok. Field Transducers are
found faulty. TSTRANSCO need to replace
the same.
20 aux bay -total need to check. scope of work: M/s TSTRANSCO. Open

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 5 of 8
Visit Document

COMMON POINTS:

1. Main Server PC configuration is completed and checked working fine.


2. Standby Server PC configuration is completed and checked working fine.
3. DRPC configuration is completed and checked working fine.
4. Gateway- PC configuration is completed and checked working fine.
5. Final database version 5_15_42_0 _KXW7_TSTRANSCO_PEDDAGOPATTI_EN.2.3.3.MPC has
been loaded to all the servers.
6. Dsagile version-v5.1.26.4-base
7. Final backup of database is saved on DRPC on following path
“D:/FINAL BACKUPS 0N 13-03-24”.

M/s GE SAS Engineer started the SAVT (1000hrs Cumulative test) in PEDDAGOPATTI SS on
13.03.2024 at 12:00PM in the presence of M/s TSTRANSCO.

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 6 of 8
Visit Document

RMA DETAILS

Project : KXH5/KXW7

Site : 220/132/33KV TSTRANSCO PEDDAGOPATTI SS

Customer : M/s TSTRANSCO

Panel / Relay Type : Control Relay Panel/Numerical protection relay

Drawing Reference No. : KXH5/KXW7

Sl.
RMA Details REMARK
No
Raised the RMA for the same. As per
B205 BCU LHMI LCD Display
1 PO terms and conditions GE will
Found Faulty
Revert Back.

Customer Feedback Form on GE T&D Services

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 7 of 8
Visit Document
Customer : M/S TSTRANSCO
Organization : M/S TSTRANSCO
Site : 220/132/33KV TSTRANSCO PEDDAGOPATTI SS
GE Engineer : N S NARESH

PRESENT Service : (Please tick () the appropriate box)


Yes No
Do you feel that the job was handled time consciously?

Are you happy with services of this Engineer ?

Any suggestions for the engineer to improve

Did the service engineer briefed up on the Catalogue of Services


(Viz.Retrofit,Training )

Did the Service engineer handover the catalogue for Retrofit / Training

GENERAL:
Excellent Average Poor

Response Time

Quality of Response

Quality of Site Service

Quality of Relay repair

Any Comment on Service:

Customer Name :
Designation :
Seal of the Customer :

For M/s. GE (CHENNAI) For M/s. TSTRANSCO For M/s. TSTRANSCO

Mr. N S NARESH Mr. Mr.

DATE: 13-03-2024

Page 8 of 8