Site Plan

JT
JT
By
REVISED

3/2/22 Pool location has slightly shifted toward the west of the property
Josh Thompson

3/2/22 Pool will be raised 30", RBB will be 30" above pool
PROJECT DATA
*Existing Lot Size: 18,177 sq. ft.
*Proposed Lot Size: 18,177 sq. ft. Undeveloped Hillside
*Existing Floor Area: 3,993 sq. ft.
*Proposed Floor Area: 3,993 sq. ft.

Issue/Revision
*Existing Impervious Surface: 1,705 sq. ft.
*Proposed Impervious Surface: 120 sq. ft.
*Existing Pervious Surface: 12,359 sq. ft.
*Proposed Pervious Surface: 12,359 sq. ft.
*80 cubic yards of dirt to be removed/hauled
away in excavation of pool.
*No fill to be used in project. Undeveloped Hillside

(E)Steps

Date
Symbol
(E)Gate to open

1
2
3/2/2022
outward. Will be self- 2
closing and self-latching Undeveloped Hillside

Josh Thompson
PA
with hardware mounted 100 3/2/2022
no less than 60 above 1
grade. Raised Bond Beam
T.W. 105.3
PA B.W. 102.3

Contractors License

791298
76'-6" T.O.C.

License Class

C-53
102.3
PA 1
3/2/2022
PA Undeveloped Hillside
(E)Stone Patio

3413 Petaluma Blvd N. Petaluma, CA 94952


Golden Iris Terrace

(415)726-0001, (415) 479-4040


PA
Undeveloped Hillside
(E)Driveway (E)Block Wall
+99.25

106

105
PA

(E)Concrete
(E)Residence 104
(N)Equipment Pad
Golden Iris Terrace

101 103
102

New Swimming Pool/Spa for 6 Golden Iris Terrace


PROPERTY LINE

PA (E)Concrete

San Rafael, CA 94903


6 Golden Iris Terrace
PA PA

Friend Residence
PA

(E)Concrete (E)Concrete
PA PA

PROPERTY LINE/(E)FENCE

Scope of Work
1) Form and excavate for a new in-ground pool that is 15' x 31' with a raised bond
beam and an automatic safety cover vault. Mechanical, Plumbing Requirements
2) Install steel reinforcement per engineered plan. 1) An atmospheric or pressure backflow prevention device will be placed on *NOTE*
3) Install rough plumbing as follows: Pool- 2½” main drain suction line, 2½” the water supply to the pool. A New 2" Gas Line Will Be Run For Approximately 120' From The Existing
Owner: Matthew & Cari Friend skimmer suction line, 2" return line, 1½” cleaner line. Meter To The New Equipment Pad Where It Will Be Connected To The New
2) Anti-siphon devices will be placed on all hose bibs within the pool area
Parcel# 164-570-19 4) Apply gunite material to form new pool/spa/cover vault shell and 52' of 30" high Pool/Spa Heater.
3) A minimum of 36 inches is required between filter and heater for future
Mailing Address: 6 Golden Iris Terrace raised bond beam. installation of solar
San Rafael, CA 94903 5) Install a precast coping stone on top of pool bond beam and raised bond beam.
Jurisdiction: Unincorporated 6) Install a standard range waterline tile on pool.
Zoning: RMP-0.345 7) Install equipment as follows: Pentair Variable Speed Filter Pump, Pentair
Use Type: Residential Single Family Electrical Requirements
Variable Speed Water Feature Pump, Pentair 420 Clean and Clear Cartridge *NOTE*
Units: 1 @ 3,993 Sq. Ft. Filter, Pentair 400 MasterTemp Heater, Pentair Intellicenter.

164-570-19
1) All metal within 5 feet horizontally and 12 feet vertically of water will be Approximately 80 Cubic Yards Of Dirt Will Be Removed In The Excavation Of
Lot Square Footage: 18,177 8) Install approximately 120' of 2' gas line from meter to new equipment pad. bonded. The Pool. Approximately 8 Yards Of Rock Will Be Used For A 6" Gravel Bed

JT
Trenching route TBD. 2) All receptacles providing power to pool equipment will be GFCI protected. In The Pool, If Required By The Engineer. All Spoils From Excavation Will Be

Site Plan (REVISED)


9) Pressure wash gunite structures, clean up construction debris and prep for Off-Hauled, Dumping/Recycling Site TBD At Start Of Job.
plaster. 3) An equipotential bonding of a minimum 8AWG will be installed.

APN #

Drawn
10) Install a standard white plaster finish on pool and spa interior.
11) Install automatic safety cover.
*NOTE* 12) Start up system and balance chemicals.
Consultants And Designers
The new swimming pool will be equipped with at least 2 of the 7 *NOTE*
drowning prevention safety features per CBC sec. 3109.4.4.2 and State (N) Outdoor Weather Proof Convenience Plug, GFCI Protected Electrical 1) Structural Engineer - Paul Reilly, A.P.E. 2351 Sunset Blvd Suite 170
Applicable Codes

3/2/2022

1" = 10'
of California Building Standards Information Bulletin 17-08 effective Receptacle Will Be Installed No Closer Than 6’ And No Further Than 20’ Rocklin, CA 95765 (916) 768-4656

SHEET TITLE
January 1, 2018. 2019 California Building Code (CBC), 2019 California Residential Code (CRC), 2019 From Pool. Location TBD During Project.
1)The new swimming pool will be equipped with an automatic safety California Electrical Code (CEC), 2019 California Mechanical Code (CMC), 2019 California 2) Pool Designer - Josh Thompson, Herb’s Pool Service 3413 Petaluma Blvd N.

Scale
Date
cover that is manually controlled from a key switch. Plumbing Code (CPC), 2019 California Energy Code (CEC), 2019 California Fire Code (CFC),
Petaluma, CA 94952 (415) 726-0001
2019 California Green Code (CGC), International Swimming Pool, Spa Code, 2018 Edition. Sheet Index

1 of 6 SHEETS
2) Exit alarms on the private single-family home’s doors that
provide direct access to the swimming pool or spa. The exit alarm 3) Pool Project Manager - Mike White, Herb’s Pool Service 3413 Petaluma P-1 Site Plan (REVISED)
Type Of Construction

P-1
may cause either an alarm noise or a verbal warning, such as a P-2 New Pool Plan (REVISED)
Blvd N. Petaluma, CA 94952 (707) 849-6663
repeating notification that “the door to the pool is open.” New Pool P-3 Pool Flow Rates
P-4 Equipment Specs
P-5 General Notes

SHEET:
SP1 Engineering
New Pool Plan

By
Drain Covers

Legend

- Pool Returns
Plan View

Issue/Revision
- Skimmer
Raised Bond Beam 5'-0"
AWL
- Automatic Water Levelor

Bench Bench
P
- Pool Sweep Fitting

Automatic Safety Cover Vault


S

Date
- Pool Lights

Step
Step
Step

Step

Symbol
15'-0"
18'-0"

Josh Thompson
- Dual Pool Main Drains Spaced a
Minimum of 4' Apart and Hydraulically
Balanced. Will be Equipped with VGB/
Anti-Entrapment Approved Grates

Contractors License

791298
P
S

License Class

C-53
Pool Plumbing
AWL
Main Drain Suction Line – 2½” SCH40 PVC
Skimmer Suction Line – 2½” SCH40 PVC 2'-8" 31'-0" 12"

94952 (415)726-0001, (415) 479-4040


3413 Petaluma Blvd N. Petaluma, CA
Return Line - 2" SCH40 PVC 34'-8"
Pool Cleaner Line – 1½” SCH40 PVC
Automatic Refill Line – ¾”

Sectional View General Notes


Sectional View Of Shallow End
Automatic Safety Cover Precast Coping Stones FEDERAL AGENCY AND NATIONAL COMPLIANCE LISTINGS
Waterline Tiles
1) (N) Underwater lights will be in compliance with Cover-Pools is committed to producing the safest and highest quality pool and spa
CEC 680.23. The lights will be GFCI protected, covers in the world. We are your partners in providing a reliable additional layer of
2'-6"

mounted no less than 18" below water, and each safety for your pool.
light will have a lens guard.
4'-0"

UNDERWRITERS LABORATORIES INC. LISTING


5'-0"
6'-0"

2'-6"
The Cover-Pools Underwriters Laboratories listing number is 181T - File # E52841

4'-0"
(E)Grade
2) 2019 California Building Code (CBC), 2019 WBAH Covers for Swimming Pools and Spas
(E)Grade
California Residential Code (CRC), 2019 California Power Safety Cover, Model Save-T® 3, Classified in Accordance with ASTM F1346-91
Electrical Code (CEC), 2019 California Mechanical WDDJ Swimming Pool and Spa Cover Operators Electric
15'-0"
Code (CMC), 2019 California Plumbing Code (CPC), Pool cover operator, Model “Save-T”
6'-0" 10'-0" 15'-0"
2019 California Energy Code (CEC), 2019 California

New Pool and Spa for 6 Golden Iris Terrace


ASTM ( American Society for Testing and Materials)
Fire Code (CFC), 2019 California Green Code (CGC),

San Rafael, CA 94903


6 Golden Iris Terrace
International Swimming Pool, Spa Code, 2018 Designation: F 1346-91 (PSC, MSC, OC)

Friend Residence
Top Step - 2' Run/10½” Rise
Sectional View With Stairs/Raised Bond Beam 2nd Step - 12" Run/10½” Rise Sectional View Of Deep End Edition. Cover-Pools products Save-T cover and Step-Saver® have been manufactured and are
3rd Step - 12" Run/10½” Rise
4th Step - 12" Run/10½” Rise
in full compliance with ASTM F 1346-91 Standard Performance Specification for Safety
LedgeStone Facing Covers and Labeling Requirements for All Covers for Swimming Pools, Spas, and Hot
Or Similar Material Precast Coping Stones Tubs.
FCC ID: P8G–50306 Save-T Cover Wireless 50305

3'-0"
3) The swimming pool or spa shall either have at
3'-0"

least two circulation suction outlets per pump that Note: This equipment has been tested and found to comply with the limits for a Class B
shall be hydraulically balanced and symmetrically digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
2'-6"

plumbed through one or more “T” fittings, and that provide reasonable protection against harmful interference in a residential installation.
2'-6"

Sheer Descent Water Features are separated by a distance of at least three feet in This equipment generates, uses, and can radiate radio frequency energy and, if not
4'-0"

installed and used in accordance with the instructions, may cause harmful interference
5'-0"

6'-0"

any dimension between the suction outlets, or be


6'-0"

(E)Grade designed to use alternatives to suction outlets, to radio communications. However, there is no guarantee that interference will not
(E)Grade including, but not limited to, skimmers or perimeter occur in a particular installation. If this equipment does cause harmful interference to
5'-0" overflow systems to conduct water to the radio or television reception, which can be determined by turning the equipment off and
recirculation pump. on, the user is encouraged to try to correct the interference by one or more of the
15'-0"
following measures:
6'-0" 10'-0" 15'-0" Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receive

New Pool Plan (REVISED)


4) The circulation system shall have the capacity to

164-570-19
Vault Coping/Concrete Detail Cover Sectional provide a complete turnover of pool water, as is connected.

JT
NO SCALE NO SCALE specified in Section 3124B of Chapter 31B of the Consult the dealer or an experienced radio/TV technician for help.
Coping Stone Bracket California Building Standards Code (Title 24 of the

APN #
California Code of Regulations). Note: This equipment has been tested and found to comply with the limits for a Class 1,

Drawn
Concrete Coping Stone
0'-6" 1'-0" Class 2, and Class 3 Radio equipment and systems under Title: ETS EN 300 683 : 97
and ETS EN 300 200-1 (RES) (EMC) (SRD) operating on frequencies between 9 kHz
Automatic Safety Cover and 25 GHz. These limits are designed to provide reasonable protection against
5) Suction outlets shall be covered with harmful interference in a residential installation. This equipment generates, uses and
Outer Wall Of Pool
antientrapment grates, as specified in the ANSI/ can radiate radio frequency energy and, if not installed and used in accordance with the

3/2/2022

¼” = 1'
Cover Vault 1'-2"

SHEET TITLE
APSP-16 performance standard or successor instructions, may cause harmful interference to radio communications. However, there
Interior Pool Wall
standard designated by the federal Consumer is no guarantee that interference will not occur in a particular installation. If this

Scale
Product Safety Commission, that cannot be removed

Date
equipment does cause harmful interference to radio or television reception, which can
0'-7"

except with the use of tools. Slots or openings in the be determined by turning the equipment off and on, the user is encouraged to try to

2 of 6 SHEETS
grates or similar protective devices shall be of a correct the interference by one or more of the following measures:
shape, area, and arrangement that would prevent

P-2
Reorient or relocate the receiving antenna.
physical entrapment and would not pose any suction
hazard to bathers. Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the

SHEET:
receiver is connected.
Pool Flow Rates

By
Issue/Revision
Date
Symbol

Josh Thompson
Contractors License

791298
License Class

C-53

94952 (415)726-0001, (415) 479-4040


3413 Petaluma Blvd N. Petaluma, CA
Pool 31' LONG x 15' WIDE AND 4' x 6' DEEP

New Pool and Spa for 6 Golden Iris Terrace

San Rafael, CA 94903


6 Golden Iris Terrace
LENGTH X WIDTH X AVERAGE DEPTH X 7.48 = GALLONS

Friend Residence
(L) 31' x (W) 15' = 465 x (A.D.) 5 = 2,325 x 7.48 = 17,391 GALLONS

8 HOURS = 480 MINUTES

17,391 GALLONS / 480 MINUTES = 36 GALLONS PER MINUTE

• 36 GALLONS PER MINUTE THROUGH A 2 ½” SCH40 PVC SUCTION LINE WILL

164-570-19
TRAVEL AT 2.4 FEET PER SECOND WITH A MAXIMUM 100’ OF HEAD. BOTH THE

JT
MAIN DRAIN AND SKIMMER SUCTION LINES ARE 21/2” SCH40 PVC

APN #
• 36 GALLONS PER MINUTE THROUGH A 2” PVC PIPE WILL TRAVEL AT 3.4 FEET

Drawn
Pool Flow Rates
PER SECOND WITH A MAX 100’ HEAD. THE POOL RETURN LINE WILL BE 2” SCH 40
PVC.

3/3/2022

None
SHEET TITLE

Scale
Date

3 of 6 SHEETS
P-3
SHEET:
Equipment Specs

SHEET: SHEET TITLE License Class Symbol Date Issue/Revision By

Equipment Specs New Pool and Spa for 6 Golden Iris Terrace C-53
Date APN # Friend Residence Contractors License

3/3/2022 164-570-19
P-4 6 Golden Iris Terrace 791298
Scale Drawn 3413 Petaluma Blvd N. Petaluma, CA
None JT San Rafael, CA 94903
4 of 6 SHEETS 94952 (415)726-0001, (415) 479-4040 Josh Thompson
General Notes

By
GENERAL NOTES:
1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF TITLE 24 OF THE CALIFORNIA ADMINISTRATIVE CODE, THE UNIFORM BUILDING CODE, AND ALL STATE AND LOCAL CODES.
POOL COVER COMPLIANCE 1-800-447-2838
2. ALL GATES TO OPEN OUTWARD AND BE EQUIPPED WITH SELF CLOSING SPRINGS AND A SELF LATCHING LATCH TO BE MOUNTED A MINIMUM OF 60”.
COVER-POOLS IS COMMITTED TO PRODUCING THE SAFEST AND HIGHEST QUALITY POOL AND SPA COVERS IN THE WORLD. WE ARE YOUR PARTNERS IN PROVIDING A
RELIABLE ADDITIONAL LAYER OF SAFETY FOR YOU POOL. 3. INSTALLATION OF ONE (1) GFCI CONVIENCE RECEPTICAL ON A GENERAL PURPOSE BRANCH CIRCUIT LOCATED A MINIMUM OF 6’ AND MAXIMUM OF 20’ FROM WATER EDGE WILL BE
INSTALLED.
UNDERWRITERS LABORATORIES INC. LISTING

Issue/Revision
THCOVER-POOLS UNDERWRITERS LABORATORIES LISTING NUMBER IS 181T-FILE #E52841
WBAH COVERS FOR SWIMMING POOLS AND SPAS
POWER SAFETY COVERS, MODEL SAVE-T3® 3, CLASSIFIED IN ACCORDANCE WITH ASTM F1346-91
WDDJ SWIMMING POOL AND SPA COVER OPERATORS ELECTRIC
POOL COVER OPERATOR, MODEL “SAFE-T”
GAS LINE
ASTM (AMERICAN SOCIETY FOR TESTING MATERIALS)
PLASTIC GAS LINE SHALL HAVE 18” OF COVER AND SHALL HAVE AN ELECTRONICALLY CONTINUOUS CORROSION RESISTANT TRACER WIRE (MIN 14GA) BURIED WITH IT. ONE END OF THE TRACER
DESIGNATION: F 1346-91 (PSC, MSC, OC)
WIRE SHALL BE BROUGHT ABOVE GROUND AT A WALL OR A RISER.
COVER-POOLS PRODUCTS SAVE-T COVER AND STEP-SAVERS® HAVE BEEN MANUFACTURED AND ARE IN FULL COMPLIANCE WITH ASTM F 1346-91 STANDARD
PREFORMANCE SPECIFICATION FOR SAFETY COVERS AND LABELING REQUIREMENTS FOR ALL COVERS FOR SWIMMING POOLS, SPAS, AND HOT TUBS.

Date
FCC ID” P8G-50306 SAVE-T COVER WIRELESS 50305

Symbol
NOTE: THIS EQUIPMENT HAS BEEN TESTED AND FOUND TO COMPLY WITH THE LIMITS FOR A CLASS B DIGITAL DEVICE, PURSUANT TO PART 15 OF THE FCC RULES. THESE
LIMITS ARE DESIGNED TO PROVIDE REASONABLE PROTECTION AGAINST HARMUL INTERFERENCE IN A RESIDENTIAL INSTALLATION. THIS EQUIPMENT GENERATES, USES,

Josh Thompson
AND CAN RADIATE RADIO FREQUENCY ENERGY AND, IF NOT INSTALLED AND USED IN ACCORDANCE WITH THE INSTRUCTIONS, MAY CAUSE HARMFULL INTERFERENCE TO
RADIO COMMUNICATIONS. HOWEVER, THERE IS NO GUARENTEE THAT INTERFERENCE WILLNOT OCCUR IN A PARTICULAR INSTALLATION. IF THIS EQUIPMENT DOES CAUSE
HARMFUL INTERFERENCE TO RADIO OR TELEVISION RECEPTION, WHICH CAN BE DETERMINED BY TURNING THE EQUIPMENT OFF AND ON, THE USER IS ENCOURAGED TO
TRY TO CORRECT THE INTERFERENCE BY ONE OR MORE OF THE FOLLOWING MEASURES:
• REORIENT OR RELOCATE THE RECEIVING ANTENNA.

Contractors License

791298
INCREASE THE SEPARATION BETWEEN THE EQUIPMENT AND RECEIVER.

License Class
• 2019 BUILDING ENERGY EFFICIENCY STANDARDS

C-53
CONNECT THE EQUIPMENT INTO AN OUTLET ON A CIRCUIT DIFFERENT FROM THAT TO WHICH THE RECEIVE IS CONNECTED.
• CONSULT THE DEALER OR AN EXPERIENCED RADIO/TV TECHNICIAN FOR HELP. EFFICIENCY STANDARD EXCERPT FROM THE CALIF. CODE OF REGULATIONS- TITLE 24, PART 6
NOTE: THIS EQUIPMENT HAS BEEN TESTED AND FOUND TO COMPLY WITH THE LIMITS FOR A CLASS 1, CLASS 2, AND CLASS 3 RADIO EQUIPMENT AND SYSTEM UNDER
TITLE: ETS EN 300 683: 97 AND ETS EN 300 200-1(RES) (EMC) (SRD) OPERATING ON FREQUENCIES BETWEEN 9kHz AND 25GHz. THESE LIMITS ARE DESIGNED TO PROVIDE SUBCHAPTER 2- ALL OCCUPANCIES- MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING
REASONABLE PROTECTION AGAINST HARMFUL INTERFERENCE IN A RESIDENTIAL INSTALLATION. THIS EQUIPMENT GENERATES, USERS, AND CAN RADIATE RADIO COMPONENTS SECTION 110.4- MANDATORY REQUIREMENTS FOR POOL AND SPA SYSTEMS AND EQUIPMENT

94952 (415)726-0001, (415) 479-4040


(a) CERTIFICATION BY MANUFACTURERS. ANY POOL OR SPA HEATING SYSTEM OR EQUIPMENT MAY BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED THAT THE

3413 Petaluma Blvd N. Petaluma, CA


FREQUENCY ENERGY AND, IF NOT INSTALLED AND USED IN ACCORDANCE WITH THE INSTRUCTIONS, MAY CAUSE HARMFUL INSTERFERENCE TO RADIO COMMUNICATIONS.
HOWEVER, THERE IS NO GUARANTEE THA INTERFERENCE WILL NOT OCCUR IN A PARTICULAR INSTALLATION. IF THIS EQUIPMENT DOES CAUSE HARM INTERFERENECE TO SYSTEM OR EQUIPMENT HAS ALL OF THE FOLLOWING:
RADIO OR TELEVISION RECEPTION, WHICH CAN BE DETERMINED BY TURNING THE EQUIPMENT OFF AND ON, THE USER IS ENCOURAGED TO TRY TO CORRECT THE 1. EFFICIENCY. A THERMAL EFFICIENCY THAT COMPLIES WITH THE APPLIANCE EFFICIENCY REGULATIONS; AND
INTERFERENCE BY ONE OR MORE OF THE FOLLOWING MEASURES: 2. ON-OFF SWITCH. A READILY ACCCESSIBLE ON-OFF SWITCH, MOUNTED ON THE OUTSIDE OF THE HEATER THAT ALLOWS SHUTTING OFF THE HEATER WITHOUT ADJUSTING THE
REORIENT OR RELOCATE THE RECEIVING ANTENNA. THERMOSTAT SETTING; AND
INCREASE THE SEPARATION BETWEEN THE EQUIPMENT AND RECEIVER. 3. INSTRUCTIONS. A PERMANENT, EASILY READABLE AND WEATHERPROOF PLATE OR CARD THAT GIVES INSTRUCTION FOR THE ENERGY EFFICIENT OPERATION OF THE POOL OR
CONNECT THE EQUIPMENT INTO AN OUTLET ON A CIRCUIT DIFFERENT FROM THAT TO WHICH THE RECEIVER IS CONNECTED. SPA HEATER AND FOR THE PROPER CARE OF THE POOL OR SPA WATER WHEN A COVER IS USED; AND
4. ELECTIC RESISTANCE HEATING. NO ELECTRIC RESISTANCE HEATING; AND
EXCEPTION 1 TO SECTION 110.4(a)4: LISTED PACKAGE UNITS WITH FULLY INSULATED ENCLOSURES, AND WITH TIGHT-FITTING COVERS THAT ARE INSULATED TO AT LEAST R-6.
EXCEPTION 2 TO SECTION 110.4(a)4: POOLS OR SPAS DERIVING AT LEAST 60 PERCENT OF THE ANNUAL HEATING ENERGY FROM SITE SOLAR ENERGY OR RECOVERED ENERGY.
(b)INSTALLATION. ANY POOL OR SPA SYSTEM OR EQUIPMENT SHALL BE INSTALLED WITH ALL OF THE FOLLOWING:
1. PIPING. AT LEAST 36 INCHES OF PIPE SHALL BE INSTALLED BETWEEN THE FILTER AND THE HEATER OR DEDICATED SUCTION AND RETURN LINES, OR BUILT-IN OR BUILT UP
CONNECTIONS SHALL BE INSTALLED TO ALLOW FOR THE FUTURE ADDITION OF SOLAR HEATING EQUIPMENT; AND
2. COVERS. A COVER FOR OUTDOOR POOLS OR OUTDOOR SPAS THAT HAVE A HEAT PUMP OR GAS HEATER.
3. DIRECTIONAL INLET AND TIME SWITCHES FOR POOLS. IF THE SYSTEM OR EQUIPMENT IS FOR A POOL:
i. THE POOL SHALL HAVE DIRECTIONAL INLETS THAT ADEQUATELY MIX THE POOL WATER; AND
ii. A TIME SWITCH OR SIMILAR CONTROL MECHANISM SHALL BE INSTALLED AS PART OF THE POOL WATER CIRCULATION CONTROL SYSTEM THAT WILL ALLOW ALL PUMPS TO BE
SET OR PROGRAMMED TO RUN ONLY DURING THE OFF-PEAK ELECTRIC DEMAND PERIOD AND FOR THE MINIMUM TIME NECESSARY TO MAINTAIN THE WATER IN THE CONDITION
REQUIRED BY APPLICABLE PUBLIC HEALTH STANDARDS.
SECTION 110.5- NATURAL GAS POOL/SPA HEATERS (PILOT LIGHT PROHIBITED)
EQUIPOTENTIAL BONDING ANY NATURAL GAS SYSTEM OR EQUIPMENT LISTED BELOW MAY BE INSTALLED INLY IF IT DOES NOT HAVE A CONTINUOUSLY BURNING PILOT LIGHT.
(a) FAN-TYPE CENTRAL FURNACES.
NATIONAL ELECTRICAL CODE (NEC) 2019 (b) HOUSEHOLD COOKING APPLIANCES.
THE FOLLOWING ARE EXCERPTS FROM THE 2019 NEC PERTAINING TO THE ELECTRICAL COMPONTENTS WITHIN AND AROUND WATER ENVIROMENTS.

New Pool and Spa for 6 Golden Iris Terrace


Exception to 110.5(B): HOUSEHOLD COOKING APPLIANCES WITHOUT AN ELECTRICAL SUPPLY VOLTAGE CONNECTION AND IN WHICH EACH PILOT CONSUMES LESS THAN 150 BTU/
HR.

San Rafael, CA 94903


6 Golden Iris Terrace
680.26 EQUIPOTENTIAL BONDING (c) POOL HEATERS.
(A) PERFORMANCE. THE EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION SHALL BE INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE POOL AREA.

Friend Residence
(d) SPA HEATERS.
(B) BONDED PARTS. THE PARTS SPECIFIED IN 680.26(B)(1) THROUGH (B)(7) SHALL BE BONDED TOGETHER USING SOLID COPPER CONDUCTORS, INSULATED COVERED, OR SUBCHAPTER 7-LOW RISE RESIDENTIALBUILDINGS- MANDATORY FEATURES AND DEVICES
BARE, NOT SMALLER THAN 8 AWG OR WITH RIGID METAL CONDUIT OF BRASS OR OTHER IDENTIFIED CORROSION-RESISTANT METAL. CONNECTIONS TO BONDED PARTS SECTION 150.0- MANDATIRY FEATURES AND DEVICES
SHALL BE MADE IN ACCORDANCE WITH 250.8. AN 8AWG OR LARGER SOLID COPPER BONDING CONDUCTOR PROVIDED TO REDUCE VOLTAGE GRADIENTS IN THE POOL LOW-RISE RESIDENTIAL BUILDINGS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 150(a) THROUGH 150.0(r)
AREA SHALL NOT BE REQUIRED TO BE EXTENDED OR ATTACHED TO REMOTE PANELBOARDS, SERVICE EQUIPMENT, OR ELECTRODES. (p) POOL SYSTEM AND EQUIPMENT INSTALLATION. ANY RESIDENTIAL POOL SYSTEM OR EQUIPMENT INSTALLED SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
(1) CONDUCTIVE POOL SHELLS. BONDING TO CONDUCTIVE POOL SHELLS SHALL BE PROVIDED AS SPECIFIED IN 680.26(B)(1)(a) OR (B)(1)(b). POURED CONCRETE, SECTION 110.4, AS WELL AS THE REQUIREMENTS LISTED IN THIS SECTION.
PNEUMATICALLY APPLIED OR SPRAYED CONCRETE AND CONCRETE BLOCK WITH PAINTED OR PLASTERED COATINGS SHALL ALL BE CONSIDERED CONDUCTIVE MATERIALS 1. PUMP SIZING AND FLOW RATE.
DUE TO WATER PERMEABILITY AND POROSITY. VINYL LINERS AND FIBERGLASS COMPOSITE SHELLS SHALL BE CONSIDERED TO BE NONCONDUCTIVE MATERIALS. A. ALL PUMPS AND PUMP MOTORS INSTALLED SHALL BE LISTED IN THE COMMISSION’S DIRECTORY OF CERTIFIED EQUIPMENT AND SHALL COMPLY WITH THE APPLIANCE
(a) STRUCTURAL REINFORCING STEEL. UNENCAPSULATED STRUCTURE REINFORCING STEEL SHALL BE BONDED TOGETHER BY STEEL TIE WIRES OR THE EQUIVALENT. WHERE EFFICIENCY REGULATIONS.
STRUCTURAL REINFORCING STEEL IS ENCAPSULATED IN A NONCONDUCTIVE COMPOUND, A COPPER CONDUCTOR GRID SHALL BE INSTALLED IN ACCORDANCE WITH B. ALL PUMP FLOW RATES SHALL BE CALCULATED USING THE FOLLOWING SYSTEM EQUATION: H= C X F2 WHERE H IS THE TOTAL SYSTEM HEAD IN FEET OF WATER, F IS THE FLOW
680.26(B)(1)(b). RATE IN GALLONS PER MINUTE (GPM), C IS THE COEFFICIENT BASED ON THE VOLUME OF THE POOL: 0.0167 FOR POOLS LESS THAN OR EQUAL TO 17,000 GALLONS & 0.0082 FOR
(b) COPPER CONDUCTOR GRID. A COPPER CONDUCTOR GRID SHALL BE PROVIDED AND SHALL COMPLY WITH (b)(1) THROUGH (b)(4). POOLS GREATER THAT 17,000 GALLONS, AND ;
1. BE CONSTRUCTED OF MINIMUM 8AWG BARE SOLID COPPER CONDUCTORS BONDED TO EACH OTHER AT ALL POINTS OF CROSSING. THE BONDING SHALL BE IN C. FILTRATION PUMPS SHALL BE SIZED, OR IF PROGRAMMABLE, SHALL BE PROGRAMMED, SO THAT THE FILTRATION FLOW RATE IS NOT GREATER THAN THE RATE NEEDED TO
ACCORDANCE WITH 250.8 OR OTHER APPROVED MEANS. TURN OVER THE POOL WATER VOLUME IN 6 HOURS OR 36GPM, WHICHEVER IS GREATER; AND
2. CONFORM TO THE CONTOUR OF THE POOL. D. PUMP MOTORS USED FOR FILTRATION WITH A CAPACITY OF 1 HP OR MORE SHALL BE MULTI-SPEED; AND
3. BE ARRANGED IN A 300-MM (12-IN) BY 300-MM (12IN) NETWORK OF CONDUCTORS IN A UNIFORMLY SPACED PERPENDICULAR GRID PATTERN WITH TOLERANCE OF E. EACH AUXILIARY POOL LOAD SHALL BE SERVED BY EITHER SEPARATE PUMPS OR THE SYSTEM SHALL BE SERVICED BY A MULTI-SPEED PUMP; AND
100MM (4IN) EXCEPTION TO SECTION (p)1E: PUMPS IF LESS THAN 1 HP MAY BE A SINGLE SPEED.
4. BE SECURED WITHIN OR UNDER THE POOL NO MORE THAN 150 MM (6 IN) FROM THE OUTER CONTOUR OF THE POOL SHELL. F. MULTI-SPEED PUMPS SHALL HAVE CONTROLS WHICH DEFAULT TO THE FILTRATION FLOW RATE WHEN NO AUXILIARY POOL LOADS ARE OPERATING; AND
(a) PERIMETER SURFACES. THE PERIMETER SURFACE SHALL EXTEND FOR 1 M (3FT) HORIZONTALLY BEYOND THE INSIDE WALLS OF THE POOL AND SHALL INCLUDE G. FOR MULTI-SPEED PUMPS, THE CONTROLS SHALL DEFAULT TO THE FILTRATION FLOW RATE SETTING WITHIN 24 HOURS AND SHALL HAVE AN OVERRIDE CAPABILITY FOR
UNPAVED SURFACES, AS WELL AS POURED CONCRETE SURFACES AND OTHER TYPES OF PAVING. PERIMETER SURFACES LESS THAN 1 M (3 FT) SEPARATED BY A PERMANENT SERVICING.

164-570-19
WALL OR BUILDING 1.5 MM(5FT) IN HEIGHT OR MORE SHALL REQUIRE EQUIPOTENTIAL BONDING ON THE POOL SIDE OF THE PERMANENT WALL OR BUILDING. BONDING 2. SYSTEM PIPING.

JT
TO PERIMETER SURFACES SHALL BE PROVIDED AS SPECIFIED IN 680.26(B)(2)(a) OR (2)(b) AND SHALL BE ATTACHED TO THE POOL REINFORCING SHEEL OR COPPER A. A LENGTH OF STRAIGHT PIPE THAT IS GREATER THAN OR EQUAL TO AT LEAST 4 PIPE DIAMETERS SHALL BE INSTALLED BEFORE THE PUMP; AND
CONDUCTOR GRID AT A MINIMUM OF FOUR (4) POINTS UNIFORMLY SPACED AROUND THE PERIMETER OF THE POOL. FOR NONCONDUCTIVE POOL SHELLS, BONDING AT B. POOL PIPING SHALL BE SIZED SO THAT THE VELOCITY OF THE WATER AT MAXIMIM FLOW FOR AUXILIARY POOL LOADS DOES NOT EXCEED 8 FEET PER SECOND IN THE RETURN
FOUR POINTS SHALL NOT BE REQUIRED.

APN #

Drawn
LINE AND 6 FEET PER SECOND IN THE SUCTION LINE; AND
(a) STRUCTURAL REINFORCING STEEL. STRUCTURAL REINFORCING STEEL SHALL BE BINDED IN ACCORDANCE WITH 680.26(B)(1)(a). C. ALL ELBOWS SHALL BE SWEEP ELBOWS OR ELBOW-TYPE THAT HAVE A PRESSURE DROP OF LESS THAN THE PRESSURE DROP OF STRAIGHT PIPE WITH A LENGTH OF 30 PIPE

General Notes
(b) ALTERNATE MEANS. WHERE STRUCTURAL REINFORCEING STEEL IS NOT AVAILABLE OR IS ENCAPSULATED IN A NONCONDUCTIVE COMPOUND, A COPPER DIAMETERS.
CONDUCTOR(S) SHALL BE UTILIZED WHERE THE FOLLOWING REQUIREMENTS ARE MET: 3. FILTERS. FILTERS SHALL BE AT LEAST THE SIZE SPECIFIED IN NSF/ANSI 50 FOR PUBLIC POOL INTENDED APPLICATIONS.
1. AT LEAST ONE MINIMUM 8AWG BARE SOLID COPPER CONDUCTOR SHALL BE PROVIDED. 4. VALVES. MINIMUM DIAMETER OF BACK WASH VALVES SHALL BE 2 INCHES OR THE DIAMETER OF THE RETURN PIPE, WHICHEVER IS GREATER.
2. THE CONDUCTORS SHALL FOLLOW THE CONTOUR OF THE PERIMETER SURFACE.

3/2/2022
3. ONLY LISTED SPLICES SHALL BE PERMITTED.

None
SHEET TITLE
4. THE REQUIRED CONDUCTOR SHALL BE 450 MM TO 600 MM (18IN TO 24IN) FROM THE INSIDE WALLS OF THE POOL.
5. THE REQUIRED CONDUCTOR SHALL BE SECURED WITHIN OR UNDER THE PERIMETER SURFACE 100 MM TO 150 MM (4IN TO 6IN) BELOW THE SUBGRADE

Scale
Date

5 of 6 SHEETS
P-5
SHEET:
36" MAX
COPING ADD #3 TIES T10"
T8" T12" T6" SPECIAL INSPECTION (GEOTECHNICAL OBSERVATION)
EXISTING RETAINING WALL, AS OCCURS FG T6" T12" BB RBB RBB
RBB EXTERIOR FACE: EXTERIOR FACE:
2: 2 1. POOL WALLS HAVE BEEN FORTIFIED TO ACT
MA 1 NOTCH SOIL #3 6" CC MAX #3 6" CC MAX
X CAP AS FREE-STANDING CANTILEVER WALLS,
S EACH WAY S EACH WAY

8' MAX DESIGN "H"


OFFSET MAX H = 12 FEET 3 TYP AND DO NOT REQUIRE THE PASSIVE RESISTANCE

8' MAX DESIGN "H"


BB
( UON BY THE ENGINEER )
D (POOL) OF EXTERIOR SOILS FOR SUPPORT.
2
T7" WP STEM WP STEM 2. . GEOTECHNICAL ENGINEER SHALL DIRECT PLACEMENT

4' MAX
COVER D

RBB
VAULT D D BB D 2" CLR, TYP OF SUBDRAIN.
S ADD ONE 3. COMMAND & CONTROL:
S ALT BAR BASIN T7" MIN 2" CLR BASIN THE G.E., MAY AT THEIR SOLE DISCRETION,
POOL S TYPICAL DIRECT ANY SITE MITIGATION REQUIRED FOR
24 24 FG

8"

3'-0" MAX
H1 H2 H3 ELEVATION THIS PROJECT.
E NOTES
NOTE
1. NOTCH OPTION AT POOL INTERIOR
NOTES:
1. RBB TO SPAN ACROSS TOP OF COVER VAULT STONE/MASONRY RBB FEATURE OTHER STEMS FG
ADD ONE
ALT BAR
7 S 4. FOR COMPLETE SOILS INFORMATION, REFER TO
THE THE REPORT PROVIDED BY HERZOG
GEOTECHNICAL CONSULTING ENGINEERS

6' MAX
2. FOR ADDITIONAL REQUIREMENTS SEE STEM NOTCH ASSOCIATES DATED MAY 26, 2020.
P
1. FIND MAX "H" (POOL DEPTH + RBB), AS APPLIES. SEPARATION WALL: SEE POOL PLAN. or COVER TRACK WITH BACKFILL
2. SEE MANUF SPECIFICATIONS FOR OPTIONS (DETAIL 3). S 24 S
CASE 1 CASE 2 CASE 3
2. REFER TO "DETAIL B" FOR STRUCTURAL SECTION. 6' MIN CONTACT:
FOR OTHER REQUIREMENTS. 7 24 HERZOG GEOTECHNICAL CONSULTING ENGINEERS
3. THE "BUILD" SECTION MAY CHANGE WITH POOL DEPTH. NOTES
A

4. OFFSET TO RETAINING WALL ABOVE THE BB MAY VARY. A. POOL-COVER VAULT B. RBB AT COVER VAULT 1. THE UPPER STEM, NOTCH DIMS & FG MAY VARY.
T8" 70 WOODSIDE LANE
5. IF OFFSET RETAINING WALL IS BELOW THE BB: THEN 2. EMBEDDED FIXTURE: INSTALL PER MANUF SPECIFICATIONS. * CASE 1 * CASE 2 MILL VALLEY, CA
* NOTES: BASIN SIZE PHONE: (415) 388-8355
CONTACT THE ENGINEER FOR ADDITIONAL EVALUATION. 3. WHEN A RBB RETAINS EARTH, ADD A GEO-PANEL & MAY VARY
1. ELEMENT DIMENSIONS MAY VARY, SEE BUILDER PLAN FOR DETAILS. SUBGRADE DRAIN BEHIND THE BOND BEAM. SEE GENERAL NOTES 6' MIN
6. IF PORTIONS OF AN EXISTING RETAINING WALL ARE
REMOVED, THEN RECONSTRUCTED PORTIONS MUST 2. ELEMENTS MAY BE "WET" OR "DRY" FEATURES AND MAY HAVE NOTES 1. STEMWALL BASE MUST BE OFFSET FROM ANY DESCENDING SLOPE: 7' MIN TO SLOPE FACE.
MEET CURRENT CODES. CONTACT THE ENGINEER. EMBEDDED PIPING, ELEC CONDUITS & JUNCTIONS, OR VALVES. 2. SEE "GENERAL NOTES" AND "DETAIL B" FOR ALL OTHER REQUIREMENTS.

3. STEM NOTCH TYPICAL SECTIONS * DETAIL NOTES APPLY TO BOTH SECTIONS


1. SHEET KEY (BEGIN) 2. SUPPLEMENTAL ELEMENTS NTS 4. VANISHING EDGE PROJECT NOTES
CMU DESIGN CRITERIA CL STEM TYPE: CIP CONCRETE, SHOTCRETE, OR SOLID-GROUT CMU BLOCK. SEE BUILDER PLAN FOR ADDITIONAL INFORMATION.
PRIMARY BAR EXPOSED WALLS, PERFORMANCE RATED; VERT BAR OFFSET: (CMU) 2 3/4" PRIMARY REINFORCEMENT NOT SHOWN T12"
SPACING G1 THE BUILDER MUST EXERCISE DUE-DILIGENCE TO
85 MPH WIND SPEED, SEISMIC CONTROLS.

3"
TABLE 60 EFP VERIFY THAT ADVERSE SOIL DEFECTS EXIST.
LEVEL FG

6'-0" MAX
C1. MORTAR SHALL BE "TYPE S" MORTAR; SAND, CLAYS, #4 16" CC, CMU BLOCK OPTIONS: G2 IF THE SCOPE OF WORK IS REVISED OR DIFFERING SITE
**

MAY VARY
36'' MAX
#4 VERT. #4 VERT.
EACH WAY, CONDITIONS ARE DISCOVERED, THEN STOP-WORK AND

GRADE
PORTLAND CEMENT & LIME. 8 x 6 x16, SOIL H MAX TOE W REINF KEY

H = HEIGHT
REINF. BOND BEAM TYPE

RETAINED
TYPICAL S S CONTACT THE ENGINEER FOR GUIDANCE.

6-FT MAX
C2. CMU TYPE - MEDIUM WEIGHT BLOCKS, 8 x 8 x16, SEE CAP 3'-0" 2'-0" 3'-0" 16" CC 20"
TABLE & SHAPE MAY VARY G3 A GEOTECHNICAL EVALUATION IS RECOMMENDED FOR
(2) ALTERNATE BARS STRENGTH: f'm = 1500 PSI MIN. 8 x10 x16 4'-0" 2'-6' 3'-6" 8" CC 28" ALL BUILDING PROJECTS & EXCAVATIONS.
#4 DOWEL 5'-0" 3'-0" 4'-0" 8" CC 30" FG FG
PRIMARY BAR
C3. ASSEMBLY: RUNNING BOND w/ HORIZ OFFSET.
6'-0" 3'-6" 4'-6" 8" CC 38"
2:1 G4 SOIL COMPACTION (WITH GEOTECH OBSERVATION) IS
32" CC WITH FS ADD (1) REQUIRED ON ALL FILL SOIL: COMPACT ALL FILL TO 90%
MASONRY TO BE SET ON CONTINUOUS MORTAR BED. ADD (1)

IN NATIVE SOIL
SPACING AT MAX DRY DENSITY PER ASTM D1557.

IN NATIVE SOIL
24" MIN HORIZ REINF: #4 16" CC, TYPICAL FULL-HEIGHT

EMBEDMENT
24'' MINIMUM
D ALTERNATE BAR

EMBEDMENT
GROUT ALL CELLS WITH REBAR: 2000 PSI IN 28-DAYS. TOE G5 SATURATE EXPANSIVE SOILS PRIOR TO SHOTCRETE.
LAP SPLICE DESIGN CRITERIA: FRICTION 0.25, ALTERNATE BAR

24'' MIN
C4. GROUT: PROVIDE MECHANICAL VIBRATORY SOIL BRG 1,500 PSF MAX, EFP 60 PCF, G6 SHOTCRETE EXPOSURE CATEGORY: ACI TABLE 19.3.1.1,

KEY 12"
CONSOLIDATION. MAX LIFT HEIGHT: 48". FS PASSIVE RESISTANCE: 200 PSF/FT. CLASS WΦ: PROVIDE WATERPROOF FINISH COATING.
2' MIN RADIUS G7 SHOTCRETE APPLICATION: ACI CERTIFIED NOZZLEMAN
(1) ALTERNATE BAR SEE NOTE 1

1'- 10" MIN


C5. CONDUIT & PIPING, PANELS, FIXTURES, OR J J #4 U-DOWEL " " RADIUS = 24'' MIN (WITH CREDENTIAL) IS REQUIRED TO PERFORM WORK.
OTHER APPURTENANCE MAY BE PLACED AS-NOTED: 16" CC, TAILS DOWN APPLY SHOTCRETE TO UNDISTURBED FIRM NATIVE

12" MIN
A.1 ALTERNATE BARS ARE REQUIRED WHEN (H) > 6-FEET 12" 12" SOIL OR ENGINEERED SUBGRADE. KEEP SHOTCRETE
A. CONDUITS OR PIPES SHALL NOT INTERFERE THE U-DOWEL IS REQUIRED MOIST FOR 7-DAYS (MINIMUM) AFTER APPLICATION.

48" MAX
(UON) AND MUST BE PLACED BETWEEN THE PRIMARY WITH, OR DISPLACE THE REINFORCING STEEL. IN THE KEY ONLY WHEN H > 3.5' D
W G8 PREVENT EXTERNAL HYDROSTATIC-PRESSURE ON
VERTICAL REINFORCEMENT. B. CONDUITS OR PIPES SHALL NOT IMPAIR THE NOTES: DROP-STEM: ALL STRUCTURAL SECTIONS; IF A SEEP OR HIGH-WATER
A.2 ALTERNATE REBAR MUST BE THE SAME SIZE AND GRADE 1. NO PIPING OR CONDUITS PERMITTED IN STEMWALL. 18" MIN WIDTH IS DISCOVERED, THEN PRESSURE-RELIEF MITIGATION IS
PLACEMENT OR CONSOLIDATION OF GROUT. 2'- 0" MIN CASE 2
E

AS THE PRIMARY VERTICAL REINFORCEMENT, UON. NOTES 2. TOP OF ALT BAR MAY TERMINATE AT BENCH OR STEP. REQUIRED, INCLUDING A CLEAN GRAVEL BASE OVER FILTER
C6. MATERIAL AND PRACTICE SHALL CONFORM TO NOTES 1. GEOCOMPOSITE BACKING REQUIRED. SEE NOTE G12.
SEE NOTE 2 FABRIC (MIRAFI 140N OR EQUAL).
A.3 ALTERNATE REBAR NEED NOT CROSS OTHER 1. ALTERNATE THE DIRECTION OF THE DOWEL NOTES
TRADE SPECIFICATIONS TMS 602, ASTM C-90, * 2. KEY IS NOT REQ'D IF BASE IS FULLY RESTRAINED. G9 PROVIDE POSITIVE DRAINAGE BEHIND RAISED BOND-
ALTERNATE REBAR BELOW CORNERS OR CURVES. & PRIMARY REINFORCEMENT ALONG FOOTING. 1. THE STEMWALL BASE MUST BE OFFSET FROM ANY DESCENDING SLOPE: 7' MIN TO SLOPE FACE. BEAMS AND/OR RETAINING WALLS, AS-APPLIES.
* A COLD JOINT (PAPER OR PLASTIC) IS REQUIRED
3.
P

ACI 530.1, AND ASCE 7. BETWEEN THE POOL STRUCTURE AND ANY WALL.
A.4 LAP SPLICES ARE NOT PERMITTED IN ALTERNATE BARS. 2. FOOTING HORIZ BARS: 12" CC MAX. 2. OPTIONAL DROP-STEM MAY BE ADDED TO ACHIEVE THE 2-FOOT MIN EMBEDMENT ( "CASE 2" ONLY). G10 PROVIDE STORMWATER DRAINS AND/OR SWALES TO
C7. ALL MATERIALS & WORK MUST COMPLY WITH THE 4. WALLS THAT DO NOT RETAIN EARTH: CENTER THE STEM CAPTURE & CONVEY ALL SURFACE STORMWATER FROM
3. DESIGN: REFERENCE BULLETIN LADBS P/BC 2020-96 PLACE UNDERDRAIN AND/OR CRUSHED ROCK BEDDING TO COLLECT/CONVEY WATER, AS-NEEDED.
2019 CBC CH 21, MASONRY. ABOVE THE TOTAL WIDTH OF REQ'D FOOTING. ASCENDING SLOPES PRIOR TO CONTACT WITH WALLS.
B1. ALTERNATE BARS 6. FREE-STANDING STEM G11 COLLECTION DRAINS & UNDERDRAINS: 4"Φ RIGID PVC
A

CMU SPECIFICATIONS 5.1 CMU FENCE OR PARTITION 5.2 RETAINING WALLS & SEAT WALLS (SDR 35) WITH PERFORATED PIPE BOTTOM. ENCASE
WITH CALTRANS CLASS II PERMEABLE MATERIAL.
G12 GRAVEL BACKING MAY ALSO BE USED WITH COMPOSITE
TABLE B - REBAR & SECTION THICKNESS B1 REINFORCEMENT MUST CONFORM TO ASTM A615-40. NTS SINGLE-BEND, OR 24" MIN 6" THICK LAYER OF GEOPANELS (EG., MIRAFI G100NC, HYDRODUCT COIL 600,
A. REINF CLEARANCE TO EARTH OR GRAVEL: 3" MIN. BB CALTRANS CLASS 2 OR EQUAL). PROVIDE PIPING/UNDERDRAINS AS-NOTED.
(H) HEIGHT THICKNESS REINFORCEMENT ALT
B. REINF CLEARANCE TO CONDUIT OR PIPING: 1" MIN. 6" TYP PERMEABLE MATERIAL G13 SLOPE DRAIN PIPING AT 1% MIN TO APPROVED OUTLET.
MAX WALL & FLOOR TYPICAL SECTION BARS #3 REBAR TYPE A WHEN DIRECTED BY
C. REINF CLEARANCE AT TOP OF BB OR RBB: 2" MIN. CASE 1 THE ENGINEER. G14 STRUCTURAL SECTION REQUIREMENTS: SEE DETAIL 1
6 FT MAX 6.5 INCH S STANDARD na B2 LAP SPLICES: A BY-PASS LAP SPLICE RECOMMENDED. EACH SIDE HORIZONTAL: TO ESTABLISH THE HEIGHT OF RETAINED EARTH, "H".
FRONT-FACE
8 FT MAX (1) OF FIXTURE (3) #3 x 4' FILTER FABRIC
8.0 INCH S STANDARD WHERE CONTACT LAP-SPLICES ARE PERMITTED, REINF
MUST BE STACKED: INTERIOR-BAR OVER OUTER-BAR.
DOUBLE HOOP:
(2) #3 REBAR x 96"
UNDERDRAIN D
ALL COLLECTION SYSTEMS:
GENERAL NOTES
9 FT MAX 9.5 INCH #4 12" CC EW (1)
° LAP SPLICES (GRADE 40): 40 BAR-DIAMETERS MIN. ENCAPSULATE 6"x 6" SET PIPE PERFORATIONS DOWN.
12 FT MAX 10.0 INCH #4 12" CC EW (2) ° LAP SPLICES (GRADE 60): 60 BAR-DIAMETERS MIN.
COMPACT NICHE WITH 6" MIN FIRM SOIL or
SINGLE-LAYER WEATHERED BEDROCK 2
B3 ADJACENT REINF LAP SPLICES MAY BE STAGGERED. SKIMMER SECTION SHOTCRETE LIGHT
NICHE INTERSECTIONS
TOP OF SECTION: (2) STD HORIZ REBAR 3" APART.
BB or RBB TW 6 OR
B4 ADD (1) ALTERNATE BAR TO THE WALL SECTION: 3 #3 REBAR 12" CC MAX, EACH WAY, TYPICAL.
24"

AT THE EXCAVATION ACCESS RAMP (AS OCCURS). NOTES 4 #4 REBAR 12" CC MAX SPACING (16" CC FOR CMU).
" H " SEE DETAIL 1

WHERE THE WALL-FLOOR RADIUS IS LESS THAN (H)/2: STD STEM SHOWN AT BB STEM w/ HAUNCH SHOWN 90º 135º 180º
CL 1. UNDERDRAIN, SUBDRAINS & DRAIN TRANSIT PIPE: 4" Φ,

POOL / SPA
ADD (1) ALT BAR FOR EACH FOOT THAT THE CASE 2 6 6'' MIN THICKNESS CONCRETE/SHOTCRETE/GUNITE.
RIGID (SDR 35) SCH 40 PIPE.
WALL-FLOOR RADIUS HAS BEEN REDUCED.

4"
ALTERNATE BAR FRONT-FACE REBAR TIES 4" 2. PROVIDE 2% MIN SLOPE TO APPROVED OUTLET or
B5 REBAR SUBSTITUTION: DIAGONALS: 7 7'' MIN THICKNESS CONCRETE/SHOTCRETE/GUNITE.
(1) #4 REBAR → (2) #3 REBAR, SPACED 2 1/2" APART.
2" DIA, TYP MIN, TYP ENERGY DISIPATOR, SEE DETAIL.
TOP OF BB. (4) #3 REBAR x 48" 3. DRAIN TRANSIT PIPE(S) TO BE NON-PERFORATED. 24 EXTEND REBAR LEG 24" MIN EACH END, AS APPLIES.
ADDITIONAL REINFORCEMENT (TIES OR BRACING)
FOR (H) > 48" (H) MAY BE ADDED TO FACILITATE CONSTRUCTION. #3 REBAR 4. FILTER FABRIC: MIRAFI 140NP (or EQUAL), 6-INCH MIN LAP.
EXCAVATION RADIUS = (2) 5. WHEN FINISH GRADE IS ABOVE COLLECTION TRENCH: D DRAIN REQUIRED: 4" PERF SDR-35 PIPE SET IN
NOTES: 90º 135º
P1 PIPE WRAP IS NOT REQUIRED ON PIPE PENETRATIONS PROVIDE 12" MIN THICKNESS LOW-PERMEABILITY FILTER FABRIC WITH GRAVEL COVER. ADD
POOL FLOOR OR EMBEDDED NON-METALIC PIPE. 1. STANDARD REINFORCEMENT NOT SHOWN. 12" MIN DEPTH SOIL CAP AT FG. SEE NOTE G11.
MATERIAL.
S P2 A PIPE WATERSTOP IS RECOMMENDED FOR ALL PIPE 2. INSTALL NICHE PER MANUF SPECIFICATIONS. STIRRUP STIRRUP AT COVER-VAULT: SEE MANUF REQUIREMENTS.
DIU PENETRATIONS FOR WALLS OR FLOORS. 3. NO ADDITIONAL REINFORCEMENT IS REQUIRED
RA (STANDARD) (SPECIAL)
24" P3 FOUNTAIN HEADS, SHEAR-DESCENT OR OTHER FOR LED OR OTHER LIGHTS WHEN INSTALLED S STANDARD REBAR SIZE & SPACING: SEE SECTION A.
PRIMARY (STANDARD) REINFORCEMENT NOT SHOWN FEATURES MAY BE EMBEDDED IN BB OR RBB. BB WITHOUT A NICHE OR IN PIPE PENETRATIONS.

B. SECTION & ALTERNATE BARS B3. REINFORCEMENT & PIPE B4. SKIMMER B5. LIGHT NICHE B6. REINF BENDS & SHAPES 4. UNDERDRAIN & SUBDRAIN, TYPICAL KEYNOTES
E

PLAN VIEW

(W) WIDTH: MAY VARY ENGINEERING


RBB: IF NO SOIL IS RETAINED, ELEVATION
APE
P

BUILDING FOUNDATION OFFSET BUILDING


RBB: (2) #4 REBAR 6" CC 5' MINIMUM FOUNDATION
SERVICES, INC
MASONRY OR COPING AT BB: THEN H = POOL DEPTH. OTHER RAISED CURB(S) MAY BE
PROVIDE FULL-DEPTH MASTIC CASES, SEE DETAIL STEM-NOTCH. CL
WHERE EXPANSIVE SOILS PLACE IMPERVIOUS DECK, C ADDED TO ANY FEATURE
2351 SUNSET BLVD, SUITE 170, ROCKLIN, 95765
SSIONAL EN
O FE
SKIMMER * * POST OR COLUMN * *
24" MAX 4-FT MIN WIDTH AROUND PERIMETER OF POOL. G

HEIGHT PER BLDR PLAN


R
E I LLY, P.E IN
OR EXPANSION JOINT NO OFFSET RESTRICTION
MAY VARY PLACE CONTINUOUS BOND BREAKER BETWEEN PH: (916) 768-4656 P
A

ADD STIRRUP C R .

3" 3" 6" 3" 2" CLR

EE
6 POOL ENGINEER@GMAIL COM

D
6 CONCRETE DECKS AND THE BOND BEAM. FG C

R
REGISTERE
PAU
DECK DESIGN PROFESSIONAL IN
BB WATER LINE BB FG
S RESPONSIBLE CHARGE:
STIRRUP SKIMMER
REBAR SPACING S 3
B BOND 5358

IA
& LOCATION ADD (2) #3x4' .
1:1

SIGNATURE ATTACHED o
DECK TO N L

RN
C I V I I FO
MAY VARY ENTRY STEPS, CONVENTION: (3) #3 HORIZ REBAR ELECTRONICALLY
POOL REBAR HAUNCH 12" MAX RISERS, 12" MIN TREADS, TYP S TYP S 05-20-2021
BB OPTION STA
TE OF C AL
LAP SPLICE S SEE BUILDER PLAN FOR TYP
OPTION STEPS, BENCHES & SWIM-OUTS
OPTIONAL S STANDARD REBAR SIZE & SPACING: Be Safe !
COPING/BRICK BB HAUNCH REBAR IS A BUILDER OPTION
EQUALIZER #4 12" CC MAX, EACH WAY
IN STEPS & BENCHES: Dig
ALTERNATE BB SHAPES AND BB REBAR CONFIGURATIONS #3 12" CC, EW, UON. Alert
SKIMMER ELEVATION
MAY VARY WITH BUILDER REQUIREMENT OR TRADE PRACTICE. COLD-JOINT WHEN W > 3' 811
LIGHT
Be Safe ! LEGEND GROUND & BOND
ALL METAL & FIXTURES
REINFORCEMENT & SECTION GEOMETRY:
SEE "DETAIL B, STRUCTURAL SECTIONS"
DESIGN CRITERIA: EXPANSIVE SOILS
RISK CATEGORY 1, IMPORTANCE FACTOR 1, 8. ROCK BENCH or FEATURE Call Before
You Dig
BB BOND BEAM SOIL SITE CLASS D,
REF CEC ARTICLE 680
Dig CJ
RBB = RAISED BB
CONTROL JOINT (PAPER OR PLASTIC)
PIPING OR OTHER PENETRATIONS
6" MIN OF CALTRANS CLASS II
PERMEABLE MATERIAL
MIN SOIL BEARING CAPACITY: 1,500 PSF.
CBC TABLE 1610.1 - LATERAL SOIL LOAD,
COPYRIGHT LAWS APPLY TO THIS SHEET
Permit & Construction By:

Alert CIP CAST-IN-PLACE CONCRETE


CMU CONC MASONRY UNIT. SEE KEYNOTE 4
DIMS DIMENSIONS
THROUGH WALL OR FLOOR
SEE DETAIL B3, NOTES P1 & P2:
LATERAL PRESSURE, MODIFIED (ACTIVE):
85 EFP, TYPICAL, WITH INCLUSIVE LOADS:

811 EW
FG
EACH WAY
FINISH GRADE, VARIES
REMOVABLE CAP
4" MAX DIA (O.D.)
3:1 M
AX SLO
PE 2:1 MAX ASCENDING BACKSLOPE
ADJACENT LINE LOAD (SURCHARGE).
PSEUDOSTATIC SEISMIC LOAD: 10H2 .
FS FINISH SURFACE
H HEIGHT OF EARTH RETAINED
Call Before LEG BENT REBAR EXTENSION
R RADIUS
DESIGN CRITERIA, STRUCTURE: 2019 CBC, ASCE 7, ACI 318, LADBS P/BC 2017-014
( AGENCY USE ) CA LIC CLASS C53
You Dig REINF. REINFORCEMENT PLAN SYMBOLS HYDROSTATIC RELIEF DEVICE
1. SHOTCRETE / GUNITE: CONFORM TO CBC 1903.1 & ACI 506: 3,000 PSI IN 28 DAYS.
2. REINFORCEMENT: CONFORM TO CBC 1908.4 AND ASTM A615-40, GRADE 40 REINF. PERMITTED USE: SHEET TITLE: SITE: DESIGN: PFR
TW TOP OF WALL SUMP. (1) OF (2) SUMPS SHOWN CHECK: TMR
REINFORCEMENT PLACEMENT & OTHER REQUIREMENTS, SEE DETAIL B3 (NOTES). FRIEND RESIDENCE
SOG SLAB ON GRADE
VAR DIMENSION MAY VARY
PERMISSIBLE LOCATION OF
PIPE OR CONDUIT.
SITE BUILT: EMBED 2" DIAMETER PVC
PERFORATED PIPE, 18" DEPTH INTO
WALL DESIGN PER ACI 11.1.4, FLOOR DESIGN PER ACI 7.6.1.1. RESIDENTIAL STANDARD DETAILS 6 GOLDEN IRIS TERRACE
05-20-2021
SHEET NUMBER
PERVIOUS MATERIAL BELOW FLOOR. SECTION A, TYPICAL R3, GROUP U
FOR POOL & SPA
UON UNLESS OTHERWISE NOTED
WP WATER PROOF SEE "GENERAL NOTES" G.8 NO SCALE - THIS SHEET
POOL ENGINEERING METHODOLOGY, REFER TO LADBC CH 31B, DOCUMENT: P/BC 2017-014. SAN REFAEL, CA 94903
SP1