ACTION REQUIRED: Show all existing public and private on-site fire hydrants on the site plan. Include the location of all public fire hydrants within
300 feet of the lot frontage on both sides of the street. Specify size of fire hydrant(s) and dimension(s) to property lines. Additional fire hydrant
requirements may be necessary after this information is provided.
Correction: 017 - Building address numbers - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Approved building address numbers, building numbers or approved building identification shall be provided and maintained so as to be
plainly visible and legible from the street fronting the property. The numbers shall contrast with their background, be Arabic numerals or alphabet
letters, and be a minimum of 4 inches high with a minimum stroke width of 0.5 inch. Fire Code 505.1
ACTION REQUIRED: Complete and return the “Fire Flow Availability” Form 195, with fire flow information provided by the water purveyor from the
closest fire hydrant along the lot frontage.
Correction: 023 - Public fire flow requirement __________ - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: The required fire flow for fire hydrants at this location is 1,000 gpm, at 20 psi residual pressure, for a duration of 1 hours over and
above maximum daily domestic demand. Fire Code 507.3 and Appendix B105.2.
ACTION REQUIRED: Clearly identify firefighter walkway access routes on the site plan. Indicate the slope and walking surface material. Indicate
the slope and walking surface material. Clearly show the required width.
Correction: 001 - FD access road maintenance - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Fire Department vehicular access roads must be installed and maintained in a serviceable manner prior to and during the time of
construction. Fire Code 503.1
General Correction
Fire Engineer Building Review
REVIEW ITEM STATUS REVIEWER
Fire Engineering - FBU v.1 In Review Joel Gonzalez Sandoval Ph: (323) 890-4125 email: Joel.GonzalezSand
Fire - Fire Building Unit
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Provide an answer sheet, which includes responses to each plan review requirement along with resubmitted plans.
Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Dwelling units in two-family dwellings shall be separated from each other by wall and/or floor assemblies having not less than a
1-hour fire-resistance rating when tested in accordance with ASTM E 119 or UL 263. Fire-resistance-rated floor-ceiling and wall assemblies shall
extend to and be tight against the exterior wall, and wall assemblies shall extend from the foundation to the underside of the roof sheathing.
Residential Code R302.3.
** Detail A/A is reference but not found
ACTION REQUIRED: Indicate on interior elevations and provide construction details.
Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: The garage and/or carport shall be separated as required by Table R302.6. A separation is not required between the dwelling unit
and a carport, provided the carport is entirely open on two or more sides and there are not enclosed areas above. Residential Code R302.6.