PLAN CORRECTIONS REPORT FEPC2024-0393

FOR REPORT TEXT LIBRARY: MUNICIPALITY_NAME

PLAN ADDRESS: 11428 Fidel Avenue PARCEL: 8026012013


Whittier, CA 90605
APPLICATION DATE: 02/12/2024 SQUARE FEET: 0.00 DESCRIPTION: Two Story Unit
EXPIRATION DATE: 02/11/2025 VALUATION: $0.00 One Story ADU

CONTACTS Name Company Address


Applicant Siraj Aboulhosn NA 8409 Somerset Blvd
Paramount, CA 90723

FBU - Water & Access


Fire Engineer Building Review
REVIEW ITEM STATUS REVIEWER
Fire Engineering - FBU v.1 In Review Joel Gonzalez Sandoval Ph: (323) 890-4125 email: Joel.GonzalezSand
Fire - Fire Building Unit
Correction: 025 - Hydrant spacing requirements - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Spacing of fire hydrants shall not exceed the distances specified in Fire Code C105.2, 105.3 & C106.

ACTION REQUIRED: Show all existing public and private on-site fire hydrants on the site plan. Include the location of all public fire hydrants within
300 feet of the lot frontage on both sides of the street. Specify size of fire hydrant(s) and dimension(s) to property lines. Additional fire hydrant
requirements may be necessary after this information is provided.
Correction: 017 - Building address numbers - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Approved building address numbers, building numbers or approved building identification shall be provided and maintained so as to be
plainly visible and legible from the street fronting the property. The numbers shall contrast with their background, be Arabic numerals or alphabet
letters, and be a minimum of 4 inches high with a minimum stroke width of 0.5 inch. Fire Code 505.1

ACTION REQUIRED: Provide verbatim note on site plan


Correction: 021 - Fire flow form 195 / 196 - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Every application for a building permit shall be accompanied by evidence indicating that the proposed structure is provided with a
reliable water supply capable of supplying the required fire flow as required by Fire Code 507.1.1

ACTION REQUIRED: Complete and return the “Fire Flow Availability” Form 195, with fire flow information provided by the water purveyor from the
closest fire hydrant along the lot frontage.
Correction: 023 - Public fire flow requirement __________ - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: The required fire flow for fire hydrants at this location is 1,000 gpm, at 20 psi residual pressure, for a duration of 1 hours over and
above maximum daily domestic demand. Fire Code 507.3 and Appendix B105.2.

ACTION REQUIRED: Provide the following calculation on site plan.


The required fire flow is based on the following calculation:
Type of construction per the Building Code V-B
VHFHSZ: NO
Fire-flow calculation area 3,373 sq.ft.
Fire flow based on the fire-flow calculation area 1,000 gpm
Reduction for fire sprinklers (maximum 50%) 0 gpm
Total fire flow required 1,000 gpm
Correction: 002 - 20 feet single family dwelling FD access - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Provide a minimum unobstructed width of 15 feet, exclusive of shoulders, except for approved security gates in accordance with
Section 503.6, and an unobstructed vertical clearance “clear to sky” Fire Department vehicular access to within 150 feet of all portions of the
exterior walls of the first story of the building, as measured by an approved route around the exterior of the building. Fire Code 503.1.1, 503.2.1
ACTION REQUIRED: Cross-hatch the Fire Department vehicle access on the site plan, and clearly show the required width.
Correction: 015 - 5 foot walking FD access - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: A minimum 5 foot wide approved firefighter access walkway leading from the fire department access road to all required openings in
the building's exterior walls shall be provided for firefighting and rescue purposes. Fire Code 504.1

ACTION REQUIRED: Clearly identify firefighter walkway access routes on the site plan. Indicate the slope and walking surface material. Indicate
the slope and walking surface material. Clearly show the required width.
Correction: 001 - FD access road maintenance - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Fire Department vehicular access roads must be installed and maintained in a serviceable manner prior to and during the time of
construction. Fire Code 503.1

ACTION REQUIRED: Provide verbatim note on site plan.

February 29, 2024 Report Text Library: Municipality_Page_Footer Page 1 of 2


PLAN CORRECTIONS REPORT (FEPC2024-0393)
Correction: 029 - Public hydrants installed prior to const - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: All required PUBLIC fire hydrants shall be installed, tested and accepted prior to beginning construction. Fire Code 501.4

ACTION REQUIRED: Provide verbatim note on site plan.

General Correction
Fire Engineer Building Review
REVIEW ITEM STATUS REVIEWER
Fire Engineering - FBU v.1 In Review Joel Gonzalez Sandoval Ph: (323) 890-4125 email: Joel.GonzalezSand
Fire - Fire Building Unit
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Provide an answer sheet, which includes responses to each plan review requirement along with resubmitted plans.
Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Dwelling units in two-family dwellings shall be separated from each other by wall and/or floor assemblies having not less than a
1-hour fire-resistance rating when tested in accordance with ASTM E 119 or UL 263. Fire-resistance-rated floor-ceiling and wall assemblies shall
extend to and be tight against the exterior wall, and wall assemblies shall extend from the foundation to the underside of the roof sheathing.
Residential Code R302.3.
** Detail A/A is reference but not found
ACTION REQUIRED: Indicate on interior elevations and provide construction details.
Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: The garage and/or carport shall be separated as required by Table R302.6. A separation is not required between the dwelling unit
and a carport, provided the carport is entirely open on two or more sides and there are not enclosed areas above. Residential Code R302.6.

ACTION REQUIRED: Indicate on floor plan, elevations, and construction details.


Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Enclosed accessible space under stairs shall have walls, under-stair surface and any soffits protected on the enclosed side with
1/2-inch gypsum board. Residential Code R302.7.
ACTION REQUIRED: Indicate on floor plan.
Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from a commercial
source and shall be equipped with a battery backup. Where more than one smoke alarm is required to be installed within an individual dwelling or
sleeping unit, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the
individual unit. Residential Code R314.4 and R314.6.

ACTION REQUIRED: Provide note on floor plan.


Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Required carbon monoxide alarms shall receive their primary power from the building wiring where such wiring is served from a
commercial source and shall be equipped with a battery back-up. Where more than one carbon monoxide alarm is required to be installed within
the dwelling unit or within a sleeping unit the alarm shall be interconnected in a manner that activation of one alarm shall activate all of the alarms
in the individual unit. Residential Code R315 & Building Code 915.

ACTION REQUIRED: Provide note on floor plan.


Corrective Action: <User Entry>
Correction: Correction - Joel Gonzalez Sandoval (2/29/24) - Not Resolved
Comments: Additional requirements might be provided pending requested information.
Corrective Action: <User Entry>

February 29, 2024 Report Text Library: Municipality_Page_Footer Page 2 of 2