ABBREVIATIONS ERB Emergency Rescue Bus OCR Operations Control Room NOTES

1 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE RELEVANT ARCHITECTURAL, CIVIL, E&M AND LANDSCAPING DRAWINGS
E&M Electrical and Mechanical OHL Overhead Line
2 USE ONLY FIGURED DIMENSIONS. NO DIMENSIONS SHALL BE OBTAINED BY SCALING FROM THE DRAWINGS
ABWF Architectural Builders Works and Finishes EVA Emergency Vehicular Access OHVD Overhead Ventilation Duct
3 ALL WORKS BY CONTRACTOR 810A UNLESS NOTED OTHERWISE
OPD Over Pressure Relief Duct 4 ALL LEVELS IN mPD
ACABAS Advisory Committee on the Appearance of EVS Exhaust Vent Shaft
OTE Over Track Exhaust Duct 5 ALL LEVELS INDICATED ON SECTIONAL DWGS. ARE FFL. UNLESS NOTED OTHERWISE
Bridges and Associated Structures EWS External Wall Systems
P/D Pipe Duct 6 STRUCTURAL LEVELS ON ALL PLANS SHALL REFER TO STRUCTURAL DRAWINGS
AC Access Cover FA Fresh Air 7 FOR CONTRACT DEMARCATION BOUNDARY SETTING OUT AND SITE ACCESS, REFER TO PS AND CIVIL / STRUCTURAL ENGINEERING DWGS.
PEP Platform Emergency Plunger
ACU Auxiliary Communications Unit FAG Fresh Air Grille 8 FOR SETTING OUT AND DETAILS OF STRUCTURAL ELEMENTS REFER TO STRUCTURAL DWGS
PER Power Equipment Room
9 SETTING OUT OF NON-STRUCTURAL WALLS AND RELEVANT WALL OPENINGS ARE SHOWN ON THE ARCHITECTURAL DRAWINGS.
ACS Access Control System FAD Fresh Air Duct PFA Principle Firemen's Access 10 SETTING OUT OF RC STRUCTURAL WALLS AND RELEVANT WALL OPENINGS ARE SHOWN ON THE STRUCTURAL DRAWINGS.
ADB Automatic Drop Barrier F&B Food & Beverages PID Passenger Information Display 11 SETTING OUT AND DIMENSIONS OF RC PLINTHS ARE SHOWN ON THE ARCHITECTURAL
AFC Automatic Fare Collection FB Footbridges PRC People's Republic of China DRAWINGS. TYPICAL PLINTH DETAILS ARE SHOWN ON THE STRUCTURAL DRAWINGS

AFCD Agriculture, Fisheries and Conservation Department 12 SETTING AND DIMENSIONS OF E&M FLOOR OPENINGS AND LIFTTING HOOKS/ BEAMS ARE SHOWN ON THE STRUCTURAL DRAWINGS.
FCL Finished Ceiling Level PS Particular Specification
13 FOR INTERFACE DETAILS OF ABWF AND E&M BUILDING SERVICES REFER TO THE E&M INTERFACE DETAILS
AFFL Above Finished Floor Level FCR Fire Control Room PSB Platform Supervisor's Booth
14 FOR TRANSFORMER ROOM TRENCH REQUIREMENT, REFER TO PARTICULAR SPECIFICATIONS, APPENDIX AX-CLP TRANSFORMER ROOM REQUIREMENTS AND CIVIL
AHU Air Handling Unit FD Floor Drain PSD Platform Screen Door DRAWING C01/123.

AMB Ambulance Bay FE Fire Extinguisher PSV Pre-action Sprinkler Valve Chamber 15 FOR GENERAL NOTES, ABBREVIATIONS & SYMBOLS ON INTERNAL GYPSUM BLOCKWORK, REFER TO DWG NO. A51/001
PTI Public Transport Interchange 16 FOR GENERAL NOTES ON LIFTS, REFER TO DWG NO. A31/001
ARD Air Relief Duct FEHD Food and Environment Hygiene Department
17 FOR GENERAL NOTES ON ESCALATORS AND MOVING WALKWAYS, REFER TO DWG NO. A32/001 & A33/001
RC Reinforced Concrete
APG Automatic Platform Gate FFL Finished Floor Level 18 FOR GENERAL NOTES ON DOORS, REFER TO DWG NO. A42/001
RCP Reflected Ceiling Plan
APPROX Approximately FH Fire Hydrant 19 FOR CLP TRANSFORMER ROOM'S DOOR DETAILS, LOUVRE DETAILS, IRONMONGERY, SIGNAGE AND FINISHES, REFER TO PARTICULAR SPECIFICATION, APPENDIX
REF Reference AX-CLP TRANSFORMER ROOM REQUIREMENTS.
ATM Automatic Teller Machine FHR Fire Hydrant & Hose Reel
RHS Rectangular Hollow Section 20 ALL ABUTTING/ ADJOINTING METAL FABRICATIONS OR ASSEMBLIES SHALL BE WELDED UNLESS NOTED OTHERWISE. ALL WELDS SHALL BE IN ACCORDANCE
AUS Austin Station FMO Facility Management Office WITH THE MATERIALS AND WORKMANSHIP SPECIFICATION FOR CIVIL ENGINEERING WORKS
RM Room
AVM Add Value Machine FOH Front of House RWO Rain Water Outlet 21 FOR HYDROSEEDING DETAILS REFER TO CIVIL LANDSCAPE OVERALL LAYOUT PLANS

BCF Boundary Control Facilities 22 RC FIRE TANKS AND SUMP PITS SHALL BE INTERNALLY FINISHED WITH 15MM THICK WP03 AND PR02 ALL ROUND
FRP Fire Rated Protection RWP Rain Water Pipe
23 FOR RC KERBS TO VOIDS, DIMENSIONS OF RC KERB ARE SHOWN ON THE ARCHITECTURAL DRAWINGS.
BGL Base Geometry Line FS Fire Service SED Smoke Extract Duct 24 REFER TO STRUCTURAL DRAWINGS FOR TYPICAL KERB DETAILS
BOH Back of House FSI Fire Service Inlet SEM Structural, Electrical & Mechanical 25 800mm RECESS TYPICAL FOR BOH FIRE HYDRANT AND HOSE REEL UNLESS SHOWN OTHERWISE.
BEVS Back of House Exhaust Vent Shaft GA General Arrangement SER Signalling Equipment Room 26 WHERE TYPICAL ELEMENTS ON THE SAME DRAWING ARE INDICATED THE DIMENSIONS, SETTING-OUT AND OTHER

SEVS Station Exhaust Vent Shaft INFORMATION SHALL BE CONTINUOUS WITH THE TYPICAL ELEMENTS SHOWN WHEN OTHERWISE IDENTIFIED
BSVS Back of House Supply Vent Shaft G.L./GL Grid Line
27 SAFETY HOOP IS REQUIRED FOR CAT LADDERS OVER 2000mm FROM FINISHED FLOOR LEVEL.
BS Bumper Strip SFL Structural Floor Level
GMS Galvanised Mild Steel 28 FOR MATERIAL REFER TO CAT LADDER SCHEDULE
SH Short Haul
C/C Centre to Centre H Height 29 ALL GMS TO BE PAINTED WITH UNLESS NOTED OTHERWISE.
SHS Square Hollow Section
CCR Central Control Room HKPF Hong Kong Police Force
SIM Similar 30 FOR THE GATEWAY INFORMATION TO EWS DRAWINGS, REFER TO DWG. No. A65/010.
CCTV Closed Circuit Television H/L High Level 31 FOR THE MATERIAL SCHEDULE RELATED TO ABWF DRAWINGS AND ADDITIONAL INTERNAL FINISHES ON FOOTBRIDGE DRAWINGS, REFER TO DWG. Nos. A00/101-
S.MCR Station Motor Control Room
C&ED Custom and Excise Department HR Hose Reel 105.
SOP Setting out Point
CEM Card Enquiry Machines 32 ADDITIONAL INTERNAL FINISHES ON FOOTBRIDGE DRAWINGS ARE THOSE THAT ARE NOT INCLUDED AS PART OF THE EWS INTERNAL FINISHES.
HWU Head Wall Unit S.O. Structural Opening
33 FOR THE MATERIAL SCHEDULE RELATED TO EWS DRAWINGS AND EXTERNAL/ INTERNAL FINISHES ON FOOTBRIDGE DRAWINGS, REFER TO DWG. Nos. : A00/111-
CER Communication Equipment Room IC Immigration Counter SPD Staircase Pressurisation Duct 112.
CF Compressible Filler IG Immigration Gate SPS Staircase Pressurisation Supply 34 FOR ROLLER SHUTTER, FIRE CURTAINS, SMOKE CURTAINS CONTRACT DEMARCATION, REFER TO DWG. No. A53/512 : DETAIL 03.

CH Column Head ImmD Immigration Department SPR Staircase Pressurisation Relief 35 FOR FIRE AND SECURITY SHUTTER REFERENCE NO. REFER TO GA DWGS.
36 REFER TO DRAWINGS C27 SERIES FOR LOCATIONS OF FLOOR DRAIN ASSOCIATED WITH FIRE HYDRANT AND HOSE REEL.
CHS Circular Hollow Section KOW Kowloon Station SS Stainless Steel
37 ALL BUND WALL, KERB, UP STANDS IN PLANT ROOM SHALL BE PAINTED WITH
CIQ Customs Immigration and Quarantines KR Kick Rail SSB Stainless Steel Balustrade
38 150mm HIGH KERB REQUIRED FOR PIPES AND CABLE PASSING THROUGH A FLOOR TO A LEVEL BELOW, REFER TO 810A/W/WKT/A59/101 FOR DETAILS.
CIS Customer Information Stand L/UL Loading and Unloading SSCC Safety & Security Coordinating Committee 39 WHERE APPLICABLE, WALL PAINT NOMINALLY TERMINATES AT 200mm ABOVE FALSE CEILING LEVEL UNLESS OTHERWISE SPECIFIED.

LH Long Haul SSVS Station Supply Vent Shaft 40 FOR SUMP PIT FLOOR DRAIN LOCATIONS, REFER TO DWG. NO. C27/017.
CJ Control Joint
STC Sound Transmission Class 41 THE EXTENT OF GOVERNMENT ABWF WORKS IS SHOWN IN DRAWINGS A38/011 & 012
CL Centreline LO Louvre
42 REFER TO DRAWING A38/701-753 FOR FURNITURE CODES.
STIC Station and Transport Integration Committee
CLP China Light & Power LPD Lobby Pressurisation Duct 43 REFER TO DRAWING A38/655 AND 660-665 FOR SANITARYWARE SCHEDULE.
TBE Telecommunications & Broadcasting Equipment
CONC Concrete LV Low Voltage 44 REFER TO DRAWING A38/800 & 801 FOR TYPICAL SETTING OUT OF WALL-MOUNTED FURNITURE AND EQUIPMENT, SANITARY FITMENT AND E&M FITTINGS.
TEF Trackside Exhaust Fan
C/S Cement / Sand LWP Lower Working Point TER Telecom Equipment Room 45 REFER TO ELEVATIONS FOR FURNITURE CODES OF WALL MOUNTED CABINETS.
CSP Channel Supervisor's Podium MAG Makeup Air Grille TFA Track Fan Area 46 ALL EAG / FAG / MAG ARE 1000mm HIGH WITH BOTTOM LEVEL AT 100mm AFFL UNLESS OTHERWISE SPECIFIED.
CTR Cable Termination Room MAD Makeup Air Duct THK Thick 47 REFER TO A38/801 FOR SETTING-OUT OF SOCKETS / SWITCHES / OUTLETS UNLESS OTHERWISE SPECIFIED ON ELEVATIONS.
48 THE SETTING-OUTS OF E&M FITMENTS ARE MEASURED FROM CENTRE TO CENTRE ON ALL DRAWINGS AND ARE LOCATED AT CENTRE OF CEILING PANEL ON RCP,
CTER Common Telecom Equipment Room MAX Maximum TIM Ticket Issuing Machine UNLESS OTHERWISE SPECIFIED.
CuC Customer Service Centre MCC Motor Control Cubicle TOR Top of Rail 49 HORIZONTAL SETTING-OUT OF WALL TILE JOINTS SHALL FOLLOW FLOOR TILE JOINTS. VERTICAL SETTING-OUT OF WALL TILES TO START AT TOP OF SKIRTING.

TOW Top of Wall 50 TO PROVIDE FREE AREA FOR SMOKE EXTRACTION, THE EDGE OF FALSE CEILING IS 300mm TYPICAL AWAY FROM THE PERIPHERY OF THE ROOM / CORRIDOR
DCO Duty Collection Office MCR Motor Control Room UNLESS OTHERWISE STATED ON RCP. REFER TO A38 SERIES. FOR THE CORRESPONDING DETAIL OF FALSE CEILING DESIGN AND ELEVATIONS FOR ROOMS THAT
MCS Main Control System TSF Trackside Supply Fan HAVE SUCH ARRANGEMENT.
DOH Department of Health
TSSC Trackside Safety and Security Committee
DEE Designated Emergency Entrance MIN. Minimum 51 REFER TO DRAWING 810A/W/WKT/A38/861 DETAIL 06 FOR EXPOSED FLOOR DRAIN DETAIL UNLESS TO OTHERWISE SPECIFIED ON PLANS.
TVF Tunnel Ventilation Fan 52 REFER TO DRAWING A38/861 DETAIL 06 FOR EXPOSED FLOOR DRAIN DETAIL AND A38/851 DETAIL 08 FOR GRATING DETAIL UNLESS SPECIFIED ON PLAN.
D Depth MIRR Mirrored
TVS Tunnel Ventilation System
DIA Diameter MIV Motorized Isolation Valve ENCLOSURE WALLS TO BUILD UP THE EAD/FAD/MAD THAT ARE NOT PART OF THE PERIPHERY OF THE ROOM / CORRIDOR ITSELF SHALL BE NON-FULL HEIGHT
TYP Typical 53
MJ Movement Joint WALLS OF HEIGHT 400mm ABOVE FCL OR 2900mm AFFL IF THERE IS NO FALSE CEILING.
DN Down UPS Uninterrupted Power Supply 54 IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PREPARE, SUBMIT TO AND OBTAIN APPROVAL FROM CLP FOR ALL DRAWINGS
DR Door m Metre(s) (or m) VG Vertical Grating FOR WORKS ASSOCIATED WITH THE CLP ROOMS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM CLP FOR THE CONSTRUCTION
DWG Drawing mm Millimetre(s) (or mm) W Width OF THE CLP OCCUPIED AREAS TO THE SATISFACTION OF CLP AND IT SHALL BE THE CONTRACTOR'S OBLIGATION TO HAND OVER THE

MOA Means of Access ROOMS TO CLP TO MEET THEIR REQUIREMENT.


EAA Emergency Assembly Area W/ With
55 BASEMENT 4 TRACK SLAB PLANS (810B) A12/B46-B91 ARE INCLUDED TO IDENTIFY LOCATIONS OF ACCESS COVERS ONLY.
EAD Exhaust Air Duct MOE Means of Escape
REFER TO STRUCTURAL DRAWINGS (810B) C10/B30-B92 FOR CONSTRUCTION RELATED INFORMATION.
EAG Exhaust Air Grille mPD Level in metres relative to Hong Kong principal datum 56 ALL PLINTHS TO BE 100mm(H) AFFL UNLESS NOTED OTHERWISE.

EAP Emergency Access Point MPR Multi-Processor Enquiry Machines 57 ALL E&M FITTINGS AND SETTING OUT ARE SUBJECT TO COORDINATION WITH E&M CONTRACTOR.
58 MASS CONCRETE-FILL STAIR IN PLENUM TYPICALLY FAIRFACE WITHOUT SKIRTING, NOSING AND TACTILE TILE UNLESS SPECIFIED OTHERWISE. WHERE VERTICAL
EC E-Channel MTR Mass Transit Railway CLEARANCE LESS THAN HEIGHT OF HANDRAIL / GUARD RAIL, HANDRAIL/GUARD RAIL SETS OUT 150mm FROM STRUCTURAL SOFFIT. NO INTERMEDIATE RAIL
REQUIRED FOR GUARD RAIL EQUAL OR LOWER THAN 650mm IN HEIGHT. HANDRAIL MOUNTED ON WALL SIDE. HANDRAIL FLOOR-MOUNTED AND SETS OUT
ECS Environmental Control System M&W Material & Workmanship
TYPICAL 100mm FROM STAIR EDGE ON OPPOSITE SIDE. NO BRAILLE PLATE REQUIRED FOR HANDRAIL. REFER TO A55/501,505 FOR WALL-MOUNTED AND FLOOR-
EED Emergency Escape Doors NOM Nominal MOUNTED HANDRAIL DETAILS RESPECTIVELY
59 VFD (VERTICAL FLOOR DRAIN) IN 815F TOILET AREA TO BE SUPPLIED AND INSTALLED BY 815F.
EEP Emergency Evacuation Point NO. Number
60 FOR ACCESS COVERS WHERE THERE IS A LEVEL DIFFERENCE GREATER THAN 600mm IMMEDIATELY BEHIND THE OPENING (TYPICALLY, BUT NOT LIMITED TO TYPE
ELEC Electrical Riser NTS Not to Scale 11, TYPE 14 AND TYPE 17); THE CONTRACTOR SHALL PROVIDE 2 NOS. GMS SAFETY CHAINS MOUNTED AT 900mm & 450mm AFFL / TOP OF KERB. CHAINS SHALL
BE FIXED SECURELY TO THE ADJACENT STRUCTURE USING PROPRIETARY RING / EYE BOLT(S) TO PREVENT FALL FROM HEIGHT. ADDITIONALLY, WHERE SUCH
EQ Equal OCC Operational Control Centre SAFETY CHAINS ARE PROVIDED, THE CONTRACTOR SHALL ADHESIVELY FIX 1 NOS. WARNING SIGN TO THE OUTSIDE FACE OF THE ACCESS COVER AS PER 02-
A68/238.