SC - SA2S - Complete
SC - SA2S - Complete
Contract: SN:
Short-Circuit Analysis
ANSI Standard
Number of Buses: 1 0 5 6
Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total
Number of Branches: 2 0 0 3 0 0 5
Number of Machines: 0 1 0 2 2 5
Contract: SN:
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Apply Individual
Temperature Correction Adjustments /Global Degree C
Contract: SN:
6 Buses Total
Contract: SN:
ohms or siemens per 1000 ft per Conductor (Cable) or per Phase (Line/Busway)
Line/Cable/Busway Length
Contract: SN:
Grounding
Transformer Rating Conn. Primary Secondary
ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm
Contract: SN:
Branch Connections
Contract: SN:
U2 Bus1 1000.000 110.000 10.00 0.99504 9.95037 Wye - Solid 10.00 0.995037 9.95037
Contract: SN:
Induction Machine Rating (Base) Positive Seq. Imp. Grounding Zero Seq. Imp.
ID Type Qty kVA kV RPM X"/R %R % X" % X' Conn. Type Amp X/R % R0 % X0
Mtr1 Motor 1 11.15 34.500 1800 3.70 6.301 23.31 9999.00 Wye Open 4.08 6.30 25.69
Mtr3 Motor 1 1.11 13.200 1800 3.70 6.944 25.69 9999.00 Wye Open 3.70 6.94 25.69
Contract: SN:
Impedance
Lumped Load Rating % Load Loading X/R Ratio (Machine Base) Grounding
ID kVA kV MTR STAT kW kvar X"/R X'/R %R % X" % X' Conn. Type Amp.
Lump1 4000.0 34.500 44 56 1496.0 927.1 10.00 10.00 1.538 15.38 23.08 Delta
Lump3 200.0 13.800 47 53 79.9 49.5 6.67 6.67 2.307 15.38 23.08 Delta
Contract: SN:
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus3 Total 0.00 8.119 0.00 108.62 96.27 7.773 7.773 5.99E+000 1.97E+001 2.00E+000 2.38E+001
Bus2 Bus3 0.87 7.988 21.57 95.28 90.59 7.669 7.773 6.16E+000 2.00E+001 2.00E+000 2.38E+001
Bus14 Bus3 0.00 0.007 0.00 108.62 96.27 0.005 0.000 2.46E+003 2.46E+004
Mtr1 Bus3 100.00 0.000 100.00 100.00 100.00 0.000 0.000 5.65E+004 8.96E+007
Lump1 Bus3 100.00 0.127 100.00 100.00 100.00 0.101 0.000 8.74E+001 1.31E+003
Contract: SN:
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus14 Total 0.00 8.026 0.00 109.75 96.90 7.558 7.558 6.32E+000 1.99E+001 2.26E+000 2.52E+001
Bus3 Bus14 1.75 8.019 2.88 108.39 96.29 7.553 7.558 6.33E+000 1.99E+001 2.26E+000 2.52E+001
Bus9 Bus14 0.05 0.007 55.97 63.36 99.74 0.005 0.000 2.46E+003 2.46E+004
Contract: SN:
Bus3 34.500 2.359 -7.768 8.119 1.674 -7.590 7.773 6.756 2.048 7.060 6.206 5.687 8.418
Bus14 34.500 2.434 -7.648 8.026 1.689 -7.367 7.558 6.651 2.114 6.979 6.104 5.596 8.281
All fault currents are symmetrical (1.5-4 Cycle network) values in rms kA.
* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 13
Contract: SN:
Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Bus3 34.500 0.71287 2.34761 2.45345 0.70467 2.32912 2.43338 0.23821 2.83067 2.84067 0.00000 0.00000 0.00000
Bus14 34.500 0.75276 2.36498 2.48189 0.74452 2.34648 2.46176 0.26950 2.99471 3.00681 0.00000 0.00000 0.00000