DATE 04-Jan-23 Fine Agg Grading

Mix Description C150/250 OPC 100

Consultant EHAF
Contractor Orascom Co. 90

Project Magdi Yacoub Hospital 80

Mix Description: Plain Concrete 70


Required Characteristic Strength 150 Kg/cm²

% PASSING
60
Workability required : Slump 20 ±20 mm
Raw Material Description Weights per m³
50

Cement OPC Content 250 kg 40

Micro Silica 0 kg
30
Dolomite Size (12.5-19) mm 563 kg
Dolomite Size (4.75-12.5) mm 563 kg 20
Natural Sand 823 kg
Crushed Sand 0 kg 10

Free Water 150 kg


0
Total Water 191 kg 0.1 1 10
Egyptian Code 203.2018
MasterRehbuild 880 EG or Weber 101U or Ncc X4 4.8 Kg
Using at site if required RH1110 .5 : 1.0 Lit
Combined Coarse Aggregate Grading Curve
100
Density 2395 kg
Material Breakdown 90

Dolomite Size (12.5-19) mm 29%


80
Dolomite Size (4.75-12.5) mm 29%
Natural Sand 42% 70
Crushed Sand 0.0%
Water / Cement Ratio 0.60
% PASSING

60

Aggregate / Cement Ratio 7.80


50
Sources and Alternative of Raw Material
Cement Wadi El Nile /Arabia / Army 40
Fly Ash GEOS
Aggregates Attaka 30

Natural Sand SAF or Mostakabl Masr Quarriers


20
Crushed Sand N.A
Water Government
10
Micro silica Master Builder
Water Proof Master Builder 0
1 10 100
Polypropylene Fiber GEOS
Egyptian Code 203.2018
Admixture Master Builder or Weber or NCC
AGGREGATES Combined Egyptian Code FINES
Combined
Coarse
SIEVE SIZES 20mm 14mm Sand1 Sand2 Aggregate
Fine LOWER HIGHER LOWER HIGHER
37.50 mm 100% 100% 100% 100% 100% 100% 100% 100%
25.00 mm 100% 100% 100% 100% 100% 100%
20.00 mm 96% 100% 100% 100% 98% 100% 90% 100%
14.00 mm 27% 98% 100% 100% 67% 100%
10.00 mm 4% 65% 100% 100% 40% 100% 30% 60% 100% 100% 0%
5.00 mm 0% 2% 100% 84% 1% 100% 0% 10% 89% 100% 0%
2.36 mm 0% 1% 97% 71% 1% 97% 65% 100% 3%
1.18 mm 81% 48% 81% 45% 100% 19%
0.60 mm 40% 33% 40% 25% 80% 60%
0.30 mm 19% 20% 19% 5% 48% 81%
0.15 mm 4% 10% 2% 0% 10% 98%
Fine Agg. Breakdown 100.0% 0.0%
FINENESS MODULUS 2.6
Agg. Breakdown 28.9% 28.9% 42.2% 0.0%
* The Admixture has been used as per Manufacturer certificate and advises and the dosage can be vary based on the winter to summer seasons, according to
the technical data sheet; the admixture can be vary from the min dosage 2.5 Kg/M³ to Max dosage 7.5 Kg/M³ to achieve the required performance.
*All the alternative material submitted in the mix design can be used without prior notification.
* The above Mix design based on S.S.D for Aggregates. . . .
* Admixture may be added at site in order to maintain workability critical for placing.
*Coarse and Fine aggregates quantities could be changed based on material properties " FM variation by 0.1%" from mix design FM 2.6%.

Fm=Fcu+1.64*S = 197 Kg/cm²


*As per ECP the Miniumm Accepted margin for C 150 is 55 Kg/Cm² So Fm will be = 205 Kg/cm²
Compressive Strength Test Result

* 7 Day Result is 164 Kg/Cm²


* 28 Days Result is 221 Kg/Cm²

We trust that the above meets your requirements.