SPECIFICATION
CFE K0000-05
MEXICO
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
CONTENTS
1 OBJECTIVE 1
2 FIELD OF APP 1
3 RULES THAT APPLY 1
4.7 Disconnector 6
4.8 Protection 8
4.10 Bushings 11
4.11 Dimensions Highs 12
4.12 Accessories 12
4.14 Drawings 13
4.15 Useful life Expected 13
5 CONDITIONS OF OPERATION 13
8.1 Tests 14
9 MARKED 15
9.1 Plate Data 15
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
9.4 ID of Bushings 16
9.5 Disconnectors 16
9.8 ID Internal 16
12 CHARACTERISTICS INDIVIDUALS 17
TABLE1 Three-phase transformers Type submersibles of 300 kVA and 500 kVA for
Distribution underground 2
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
1 de 20
1 PURPOSE
Establish the characteristics that they must achieve the transformers of distribution triphasic Type submersible that HE
install in the distribution networks underground of the Commission Federal Electricity (CFE).
2 FIELD OF APPLICATION
Apply to transformers with cooling natural in liquid insulating, triphasic of 300 kVA and 500 kVA, for operate insystems
with nominal voltages until 34.5 kV, designed for settle in vault.
ISO ISO 261-1998 General Purpose Metric Screw Threads- General Plan
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
2 de 20
NOTE: In case of that the documents previous be reviewed either modified, has to be used the edition current in the date of
publication of the announcement to the tender, except that the CFE indicate other stuff
The transformers to the that HE refers this specification he indicate in the TABLE1, and they must achieve with it
indicated herein and what is applicable to standards NOM-002-SEDE and NMX-J-287-ANCE. They must be of the dead
front type for operation in ring.
TABLE1 - Transformers triphasic Type submersible of 300 kVA and 500 kVA for
underground distribution
Lightning
impulse
Rated Rated voltage sand withstand
capacity connections voltage Short Description
(kVA) (V effective) normalized
(kV Crest
Transformer submersible
300 13 200YT/7 620-220Y/127
D3SS-300-13 200YT/7 620-220Y/127
95
Transformer submersible
500 13 200YT/7 620-220Y/127
D3SS-500-13 200YT/7 620-220Y/127
Transformer submersible
300 22 860YT/13 200-220Y/127
D3SS-300-22 860YT/13 200-220Y/127
125
Transformer submersible
500 22 860YT/13 200-220Y/127
D3SS-500-22 860YT/13 200-220Y/127
Transformer submersible
300 33 000YT/19 050-220Y/127
D3SS-300-33 000YT/19 050-220Y/127
150
Transformer submersible
500 33 000YT/19 050-220Y/127
D3SS-500-33 000YT/19 050-220Y/127
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
3 de 20
d Distribution
3 Three-phase
H.H Underground-Submersible
300 and 500 Rated capacity in kVA
13 200/7 620
22 860/13 200 Rated voltage in medium voltage in volts
33 000/19 050
YT, AND Type of Connection
220Y/127 Rated voltage in low voltage in volts
4.1.1 Altitude
The transformers triphasic to that he refers to this specification they must be built for operate to 2 300 masl.
The transformers to that he refers this specification they must be designed for operate to a temperature atmosphere
maximum inside of the vault of 50°C and a temperature half in a period of 24 h of 40 °C.
The primary nominal voltages are: (13 200YT/7 620) V, (22 860YT/13 200) V and (33 000YT/19 050) V. The voltage
nominal secondary is: (220Y/127) V.
4.2.3 Connections
For the transformers of this specification the Connection in Average and low Voltage has to be star landed.
4.2.4 Impedance
The impedance voltage must be measured at current and nominal frequency. The impedance expressed in percent of
the Voltage of impedance and with regard to the Voltage nominal he correct to the temperature of reference of 75
°C for warm type transformers and 85 °C for normal transformers and must comply with the values indicated in the rule
NMX-J-287-ANCE.
He bidder has to inform he worth of the impedance together with the proposal. This worth that has to consider for
The test of acceptance.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
4 de 20
The excitation current, extent to r ated Voltage, No has to be elderly of the 1.0 %. He bidder has to inform he worth
of the current of excitement together with the proposal.
The values of losses maxims in empty Pv and totals Pt they must achieve with the rule NMX-J-287-ANCE.
4.2.7 Efficiency
The efficiency of the covered transformers by this specification, to load nominal and considering factor of unitary power,
must comply with what is indicated in the NOM-002-SEDE standard. The bidder must indicate the value of the efficiency
together with his proposal.
They must be provided Guarantee nominal values of: losses of excitement and losses charging, which must comply
with the provisions of this specification and are subject to bidding and penalties according to the specification CFE
K0000-03.
The transformers object of this specification they must achieve with it indicated to continuation.
a) These transformers are installed in vaults below the surface of the ground, which ones will be
exposed to flooding, so they must be completely submersible in water, including the connections for
cables, equipment disconnector, fuses internal and the accessories external.
b) He transformer has to have a covering anticorrosive and color according to indicated in the
subsection 4.13.
c) The top of the transformer has to be to 2 waters with inclination of 1st to 2nd for avoid the
accumulation of water (see figure 2).
d) He tank of the transformer has to have a base adequate for avoid that he background of the
samethis in contact with the floor of the vault.
f) The medium and low voltage bushings, the sectionalization equipment, the internal fuses and the
Lead changer operating handle must be accessible from the top of the transformer, in order to operate
or detect them from the surface, without having to enter the vault.
g) The bridges of half Voltage they must be facts with cables of copper flexible of the Type electrode
holder, which have a section cross of the ampacity appropriate.
h) The nuts used in the connections electrical they must be of the Type security and count with locknut
either any medium That prevents that he loosen
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
5 de 20
i) In the connections internal of the transformer, when the windings of low Voltage be connected by
means of rigid copper bars, one of its ends must be attached to the bolt of the low voltage shoe, by
means of a flexible copper conductor, soldering one of their extremes to the bar copper made rigid
and the other extreme HE will weld to one Solera of copper that will be screwed to the low tension
nozzle bolt, to avoid failures due to false contact. Both the copper conductor flexible as the Solera of
copper, they must have the ampacity necessary.
j) The coolers should be placed on the rear side of the side where the relief valve is located. drainage
and sampling, coolers should not be placed on the sides where hooks are installed for lift the unit
complete.
k) Screws in contact with the environment must be made of grade 304 or 316 stainless steel, their
corresponding nuts, sheaves must be of steel stainless degree 304.
l) The tightening screws of the flanges of the medium and low voltage bushings must have a
perpendicularity with respect to the tank cover, they must also have a locknut or any half that prevent
that he loosen
These devices do not have a tap changer unless CFE requires it. If CFE require in whose case has to indicate in the
Characteristics Individuals.
When required, the tap changer must be external operation and fulfill with what is indicated in the rule NMX-J-287-
ANCE.
All permanent connections that carry current, except for those threaded, they must be joined with welding or with type
connectors compression.
4.5.3 Core
The core must be electrically connected to the tank at a single point by means of a copper conductor. The connection
must be visible from he record of hand.
He driver of the windings in half and low Voltage has to be of copper I aluminum, with the endurance mechanics
necessary for bear the efforts of short circuit of agreement with the rules NMX-J-287 and NMX-J-169-ANCE.
He insulation has to be compatible with he liquid insulating of the transformer, his class thermal has to be as minimum
120, of agreement to the rule NMX-J-153, besides of their characteristics dielectric, chemicals, mechanical, thermal,
between others, they must be selected for The right one functioning of the transformers here specified.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
6 de 20
Has to count with a base that medium he weight of the transformer and that allow move it to it long of their axles
longitudinal and cross by half of rollers.
All the zones of the tank in contact with he background of the vault they must be designed for reduce to the maximum
hiscorrosion and achieve with he paragraph 4.13.
He tank has to be manufactured of a material whose characteristics comply with any of the following steels:AISI-
1018, AISI-1025 and ASTM A-36.
In zones coastal either of high pollution HE has to use steel stainless degree 304 either 316 and indicate in the
Characteristics Individuals.
The ropes of nuts, screws and plugs they must correspond to the of the system international of units(NOM-008-SCFI)
and agree with the rule ISO 261-1998.
He inside of the tank has to be free of trash, burr either any other element strange that HE deposit in he backgroundof
the tank, in the reels either be suspended in he liquid insulating.
He tank of the transformer has to be built for bear, completely assembly, a pressure internal of 69 kPa during 2 h,
either a pressure internal minimum of fifty kPa during 3 h, without introduce a deformation final elderlyof the 2 %.
4.7 Disconnector
HE they must supply two disconnectors internal triphasic of operation with burden of the following characteristics:
a) Positions: 2.
b) Handle of operation: 1.
All the connections and items internal of the transformer that form part of the ring, they must be designed forbear the
direct currents and of failure of the ability of the ring.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
7 de 20
The endurance maximum extent between the bushingsof a same phase, of the side A to the side B, has to be equal either
minor to:
The disconnectors they must be of 200 TO, to less that in the Characteristics Individuals he indicate that he requireof
400 A either 600 A.
He has to supply a disconnector triphasic radial of operation with burden, whose function is disconnect hetransformer of
the ring without interrupting his continuity and has to be of the following characteristics:
a) Positions: 2.
4.8 Protection
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
8 de 20
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
9 de 20
Accessory Description
No.
1 Adjuncts for leverage
2 Adjuncts for glide
3 Adjuncts for get up
4 Connection of the tank to land type B
5 Connection of the low Voltage to land
6 Bridge of low voltage to land
9 Bushing of low Voltage
10 Bushing of high Voltage
eleven Medium for connectors Type elbow
12 Disconnectors
23 Plate of data
25 Record of hand
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
10 de 20
The fuses they must be of the Type limiter of current of sand-silver of interval complete, removable from
outside without the need to uncover the transformer and have a suitable accessory to prevent them from being
removed Yeah No this open he disconnector radial, when it I carried (see subsection 4.7.2), the characteristics
electrical that they must fulfill the fuses are indicated in the TABLE 5.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
11 de 20
He supplier has to supply the transformers with he liquid insulating necessary owing be of the Type specified in the
rule NMX-J-123-ANCE.
4.10 Bushings
The bushings of medium and low voltage must be detachable to be removable from he abroad. No they must
weld to the top of the tank so they must be installed through system screwable.
Has to have 6 well-type bushings installed in a vertical position so that the oil from the equipment does not cover
completely the internal part of the terminal and if required by the CFE, they can be 6 of the bolt type according to the
CFE-55000-99 with the same provision. It former has to be in base to the characteristics of the ring, as HE indicates:
The bushings they must protect yourself with covers to proof of outdoor during he transport either storage.
Has to count with 4 bushings provided of a cap screw threaded of dimensions of agreement to the ability of the
adequate transformer, driving capacity and rope so that straight connectors can be installed insulated, hermetic and
submersible, spring type in 2 groups of 4 for 8 circuits, compatible with various brands and located as he indicates in
the Figure 2. The supplier has to provide these connectors.
The neutral on average and low voltage they must connect each other and count a disconnection forecast through
of the record of hand for ends of proof.
He neutral of low Voltage has to go out by half of a nozzle isolated and HE has to connect externally to the tank by
half of a removable bridge of copper flexible, proportionate by the supplier.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
12 de 20
The transformers to that HE refers the present specification No must exceed the dimensions maxims indicated
in the rule NMX-J-287-ANCE.
4.12 Accessories
The joints (packaging) they must be of a material elastomeric that fulfill with the characteristics indicated in the
NMX-J-287-ANCE standard, compatible with the insulating liquid, according to the method and limits indicated in the
Appendix B of the rule NMX-J-287-ANCE.
The valve of relief, manual and automatic, has to achieve with it indicated in the rule NMX-J-287-ANCE.
a) Hooks for get up he transformer complete, the which they must be removable.
b) Valve of sewer system Type balloon with thread conical for tube of 25.4 mm of diameter.
c) Two hand registers located on the lid, with a minimum area of 700 cm 2 each and in case of
records rectangular dimension minimum has to be from twenty cm.
d) The surfaces on which the gasket is placed must be smooth, flat and have sufficient rigidity to
ensure compression of the gaskets. There must be means to maintain in position the packaging,
the which not they must stand out from the registers.
i) 25.4 mm diameter nipple with a weatherproof material plug on the wall of the tank and of the side
of low Voltage for fill and proof of air tightness.
He tank of the transformer has to have a covering that it protect against the corrosion, he which to his time,
has to achieve with the values indicated in the TABLE of the Appendix D of the rule NMX-J-287-ANCE.
The supports of the set core-coil, they must of be free of oxidation and No necessarily they mustcarry
covering.
In any case the supplier must deliver warranty by written corresponding to the surface treated, forNo require
maintenance during 10 years.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
13 de 20
4.14 Drawings
Before proceeding to manufacture the prototype, the supplier must deliver to the Standardization Management of
Distribution, a game of the following drawings, for his revision and approval:
a) Of the core.
b) Of the coils.
d) Of the disconnector.
- Name plates.
- tightening torque.
- Fuses Characteristics.
g) Of dimensions general.
He made of approve the drawings No exempt to the supplier of the responsibility and obligation of correct any
defect or deficiency that represents danger or malfunction and that had not been noticed in the review of drawings.
Subsequently, he supplier has to introduce to the Management of LAPEM either the person physical either moral
that HE designatewith each prototype a game of approved drawings.
The transformers must be designed and manufactured for reach a life expected useful of when less twenty years,
low the conditions of operation and defined environment in the present specification.
For each delivery site, the supplier must deliver an operation and maintenance manual with its equipment. writings in
language Spanish of agreement to it indicated in the rule of reference NRF-002-CFE.
Overload recommendations and tightening torques must be included in the manuals. The bidder must provide to the
CFE the data that HE request in he Appendix B.
5 CONDITIONS OF OPERATION
No applies.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
14 de 20
No applies.
No applies.
8 CONTROL OF QUALITY
The CFE represented by the Management of the LAPEM either the person physical either moral that this
designate, has to verify thatthe transformers comply with the evidence of prototype and acceptance contained in this
chapter.
8.1 Evidence
The transformer supplier is responsible for carrying out the evaluation and monitoring of the quality of its subsuppliers,
as well as is responsible of the quality and the derived consequences of the defects that they could introduce oneself
in any of the components supplied by third parties.
HE they must make the following evidence by sampling according to the rule NMX-Z-012 Part 1, 2 and 3, to
the transformers in presence of the staff of LAPEM of Control of Quality or his representative.
a) Physical characteristics.
g) Voltage induced.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
15 de 20
l) Measurement of the losses due to the burden.
p) Measurement of the endurance of contacts of the disconnector, the which No has to be elderly
to the values indicated in the present specification.
a) Short circuit.
c) Temperature r is e of the windings. This has to be realized inside of a vault of concrete built
of agreement with the rules of Distribution Construction of Lines Underground.
Besides of achieve with these essays, has to of satisfy the evidence of acceptance.
Any changes made by the supplier in the materials or design of the transformer invalidate the tests. of prototype.
The values of acceptance for the evidence of the isolations of the set are:
9 MARKED
Each transformer must have a plate that permanently shows the equipment data which must contain as minimum the
information that HE indicates in the rule NMX-J-287-ANCE, so as he number of the contract.
An additional plate must be provided to the data plate that permanently indicates the tightening torques of the screws
used to fasten the medium and low voltage bushings and in general where there are joints (packaging).
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
16 de 20
In addition to the marking that requests the NMX-J-287-ANCE standard for the data plate, must be marked
characteristics of the fuses. These data can be indicated in a plate for separate.
9.4 ID of bushings
Nozzle identification must be permanent with a height of no less than 15 mm. and placed in shape that No be
covered by cables either accessories of Connection, the letters they must be of a color that contrast with he of the
transformer.
9.5 Disconnectors
The positions of the disconnector and the direction of rotation must be permanently indicated on the tank cover, with
signs, whose height No be minor to 8 mm, placed in shape that No be covered by cables either accessories of
Connection.
Additionally to the marked that asks the rule NMX-J-287-ANCE for the plate of data, HE they must indicate
the following features of the disconnectors:
a) Brand.
b) Number of Catalogue.
c) current and Voltage nominal. These data they can indicate in a plate by separate.
On the tank, the cover and the upper internal frame that fixes the core-coil assembly must be marked, with the
number of strike, at least 10 mm high, the serial number of the transformer, in addition to indicating it on the plate of
data.
9.7 ID Internal
Internal points and terminals that are connected must be marked with matching numbers or letters. with those marked
on the plate. These identifications must be made by means of tapes or plastic labels, cardTABLEcompressed either
material similar, engraved to low relief either about reliefs, No minors to 5 mm, clamped to each terminal or
recorded directly on it so that they can be easily viewed. They can also be used recorded tapes, but never painted
numbers neither labels stuck.
9.8 ID External
Has to appear in the cover of transformer tank fence of the bushings low tension, the data of the nominal capacity,
with letters and numbers no less than 65 mm in height and painted in a color that contrasts with the transformer.
He supplier has to send the transformers duly protected, of agreement with the rule of reference NRF-001-
CFE, with a full perimeter wooden base with dimensions of 25 mm per side and with a minimum clearance between
the base and the floor of 25 mm to avoid collisions and friction between the equipment during installation.
transportation, handling and storage.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
17 de 20
11 BIBLIOGRAPHY
No applies.
12 CHARACTERISTICS INDIVIDUALS
According to what set out in this specification and the conditions of use imposed by the user, It is necessary to
indicate in the attached format, CPE-328, in the Particular Characteristics that complement the requirements of
specification.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
18 de 20
APPENDIX A
Is requirement indispensable that he supplier present blueprints for the authorization by part of CFE, the which
should include as minimum the following information:
a) Drawings, sizing the parts main of the product, in their views of "plant", "frontal(elevation)"
and a "side", with notes on mm and No necessarily to scale.
c) All the information has to be in language Spanish, with units of extent of the SystemInternational
of Units.
d) The blueprints they must Have on the box of references at least the name of the product with the
characteristics nominal main, brand, model, Type, number of Catalogue of the supplier and when
it is a prototype, indicate it, the CFE specification number, as well as the signatures of the officials
corresponding of the supplier; dates of authorization and of validity. Immediately above this box, a
vertical blank space of 100 mm x 125mm for satisfactory stamps and signatures. By folding the
plan to letter size, the references and he space for seal, they must stay at forehead.
e) The drawings that complement the information of "Dimensions General” and "SetInside", must
be submitted by separate or in a only flat and are the following:
- Disconnector in ring.
- Disconnector radial.
f) Plates of data: They must achieve with it that establishes the rule NMX-J-287-ANCE.
g) The blueprints of "Dimensions General” and "Set Inside" they must be of a sizemanageable,
multiple of the size letter and maximum to double letter.
h) The sheet of coordination of protections has to be in size double letter, being able be also in size
letter.
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
TRANSFORMADORES TRIFÁSICOS TIPO ESPECIFICACIÓN
SUMERGIBLE DE 300 kVA y 500 kVA PARA
DISTRIBUCIÓN CFE K0000-05
19 de 20
APPENDIX B TECHNICAL
INFORMATION
REQUIRED
TENDER: REQUISITION NUMBER:
Characteristics Number of
Concept
offered batch
Ability nominal (kVA)
Voltage primary (kV)
Voltage secondary (V)
Voltage of endurance to the impulse by ray normalized (kV crest)
Altitude of operation (masl)
Impedance in (%)
Current of excitement (%)
Losses empty (W)
Losses due to the load (W)
Losses total maximums (W)
Efficiency (%)
Compliant with “Frame for base"
Access to cables on average and low Voltage
Transformer complete with liquid
Addition for get up (hook and ears) insulating (removable)
Core and coil of the transformer
Height (mm)
Dimensions of the transformer Front (mm)
Background (mm)
Number of bushings removable by phase in half Voltage
Number of bushings of half Voltage in each Type well (CFE 55000-99)
transformer Type bolt (CFE 55000-99)
Number of supports for bushings stationary
Number of bushings low voltage in each transformer with connector straight isolated,
airtight and submersible Type dock of low tension
Fuse limiter of current of interval complete
Brand of the level of insulating liquid
Nipple for test air tightness
Valve of overpressure and relief
Valve for sewer system and sampling
Connection top for filling and filtered out
Forecast for manovacuometer indicator
Compliant with the gaskets
Compliant with covering anticorrosive and color
Brand of the transformers
Number of Catalogue of the supplier
Brand of the bushings in half tension and low Voltage
Number of Catalogue of the supplier
Brand of the switches of the disconnector radial
Number of Catalogue of the supplier
Brand of the switches of the disconnectors in ring
Number of Catalogue of the supplier
Brand of the fuses limiters of current of interval complete
Number of Catalogue of the supplier
Bidder Representative
CHARACTERISTICS
Description short:
Others accessories:
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508
Others modifications:
810919 Rev 881221 900125 940114 960915 980306 991008 041015 050812 071221 150508