SAMPLE COMPUTATION FOR BEAMS:

Both End Continuous


Considering beam designation of B-1: L = 4143 mm

Minimum h,
4143
h=
21
h = 197.286
h = 250 mm

Minimum b,
b = 0.3 (250)
b = 75 mm
bw = 300

SAMPLE COMPUTATION FOR SLAB:


Considering S-1: L= 4143 mm, S=4200 mm
4200
=1.014 ≥ 0.5 ; Two-Way Slab
4143
Both End Continuous
Minimum h,

h=
4143
28 (
0.4 +
420
700 )
h = 147.964 mm say 160 mm
Preliminary Thickness t,
2(4200+ 4143)
t=
180
t = 92.700 mm say 100 mm
SAMPLE COMPUTATION FOR COLUMN:
A) Superimposed Dead Loads
Add. Pressure Loads = 1.3 kpa + 0.18 kpa + 0.5 kpa + 0.1436 kpa
Add. Pressure Loads = 2.1236 kpa

Pressure Load on Slab


PLS = 24 kn/m^3 (0.10 m)
PLS = 2.4 kpa

Total SDL = 2.1236 kpa + 2.4 kpa


Total SDL = 4.5236 kpa

B) Self-Weight (Columns, Beams, Interior Walls)


Considering B-1 and B-2
For Beam, B-1
Self-Weight B-1 = 24 kn/m^3 (0.3m) (0.3m) (4.143m)
Self-Weight B-1 = 8.95 kN
For Beam, B-3
Self-Weight B-3 = 24 kn/m^3 (0.25 m) (0.3m) (4.2m)
Self-Weight B-3 = 7.56 kN
Total Self-Weight of Beam = 8.95 kN + 7.56 kN
Total Self-Weight of Beam = 16.51 kN

For Column, C-1 (1st floor)


Self-Weight of C-1 = 24 kn/m^3 (0.6m) (0.45m) (1m)
Self-Weight of C-2 = 6.48 kN
For Exterior Walls,
Load on Exterior Walls = (3.97 kpa + 0.1436 + 2(0.24 kpa)) (4m) (4.143m)
Load on Exterior Walls = 76.1251 kN
Load on Exterior Walls = (3.97 kpa + 0.1436 + 2(0.24 kpa)) (4m) (4.145m)
Load on Exterior Walls = 76.1619 kN

Total Self-Weight = 16.51 kN + 6.48 kN + 76.1251 kN


Total Self-Weight = 99.114 kN

C) Compute for Dead Load


Tributary Area for C-1 = 3m^2
SDL = 4.5236 kpa (3 m^2)
SDL = 13.5708 kN

Total DL = 13.5708 kN + 99.114 kN


Total Dead Load = 112.6848 kN

D) Compute for Live Load


Tributary Area for C-1 = 3m^2
LL = 2.9 kPa
Total LL = 2.9 kpa (3m^2)
Total Live Load = 8.7 kN

Factored Load, C-1 (Ground Floor)


Pu = 1.2 (112.6468) + 1.6 (8.7)
Pu = 149.142 kN
Area Gross, C-1 (Ground Floor)
fc' = 28 Mpa
fy = 420 Mpa
Steel Ratio, p = 0.02
Reduction Factor, = 0.65
Tributary Area = 12 m
α = 0.80

0.02 = As/Ag
As = 0.02Ag
Putotal = (149.142) (2) + 149.142
Putotal = 447.425 kN

447.425 x 10^3 = (0.65) (0.80) [0.85(28) (Ag-0.02Ag) + 0.02Ag (420)]


Ag = 27122.45279 mm^2

b = √ 27122.45279
b = 164.689 mm, 200 < 300; say 300 mm
SAMPLE COMPUTATION FOR FOOTING:
Considering C-1 for FT-C1
Size of Column (C-1) = 300 x 300 mm
Size of Footing = 1800 x 1200 x 450 mm
Total Dead Load = [(112.685 + 119.165 + 125.645 + 132.125) + (6.8 x 48)] kN + [(24)
kN/m^3 (1.8+0.3) (1.2+0.3) (0.45)] m
Total Dead Load = 854.576 kN

Total Live Load = [(8.7 x 48) kN + (4.7 + 4.80 + 2.4 kPa) (0.3) (0.3)
Total Live Load = 418.671 kN

Unfactored Load = 854.576 kN + 418.671 kN


Unfactored Load = 1273.247 kN

B=
√ 1273.247
230
B = 2.3528 say 3; Footing dimension is 3 x 3 m

Pu = 1.2(854.576) + 1.6(418.671)
Pu = 1695.3648 kN

qu = 1695.3648 / 3x3
qu = 188.374 kPa

One Way Shear


x = 1800/2 – 450/2 – d
x = 675 – d

Demand
Vu = 188.374/1000 (675 – d) (1800)
Capacity

Vn = (0.75) (0.17)√ 28 (1800)d

Demand = Capacity

188.374/1000 (675 – d) (1800) = (0.75) (0.17)√ 28 (1800) d

D1 = 147.331 mm

Punching Shear

Demand
Vu = (1695.3648 x 1000) – (188.374/1000) (450+d)^2

Capacity

Vn = (0.75) (0.33) √ 28(4(450+d))

Demand=Capacity

(1695.3648 x 1000) – (188.374/1000) (450+d)^2 = (0.75) (0.33) √ 28(4(450+d))d

D2 = 366.830 mm

One way Shear


H = 147.331 + 75 + 20/2

H = 232.331 say 250 mm

Punching Shear

H = 366.830 + 75 + 20/2

H = 451.83 say 500 mm


Therefore, FT-C1 footing size is 3m x 3m x 0.5 m