4
Hopkinson’s Test – Merits & Demerits
Merits
• Power required for the test is small as compared to the full-load powers of the two
machines.
• As machines are being tested under full-load conditions, the temperature rise and
the commutation qualities of the machines can be observed.
• Because of full-load conditions, any change in iron loss due to flux distortion at
full-load, is being taken into account.
Demerit
• The only disadvantage is with regard to the availability of two identical
machines.
Hopkinson’s Test – Problem 1
• The Hopkinson’s test on two similar shunt machines gave the following fullload data :
• Line voltage = 110 V Field currents are 3 A and 3.5 A
• Line current = 48 A Arm. resistance of each is 0.035 ohms
• Motor arm. current = 230 A
• Calculate the efficiency of each machine assuming a brush contact drop of 1 volt per
brush.
Hopkinson’s Test – Problem:2
Two shunt machines loaded for the Hopkinson’s test take 15 A at 200 V from the supply.
The motor current is 100 A and the shunt currents are 3 A and 2.5 A. If the armature
resistance of each machine is 0.05 ohm, calculate the efficiency of each machine for this
particular load-condition.
Hopkinson’s Test – Problem:2
Two shunt machines loaded for the Hopkinson’s test take 15 A at 200 V from the supply.
The motor current is 100 A and the shunt currents are 3 A and 2.5 A. If the armature
resistance of each machine is 0.05 ohm, calculate the efficiency of each machine for this
particular load-condition.