WSP Canada Inc.

252 Galaxy Boulevard


Page 1 of 1
Etobicoke, M9W 5R8
416-679-9410

Compressive Strength of Cylindrical Concrete Specimens


Test Standard: CSA A23.2:19-9C
Client: ONTrack Alliance
Project: CA-WSP-201-11216-02 / 21488014 - Union Station
Element: Area C Pile Cap Foundation PC15, SPC40, MPC 4A, MPC3C, SPC41
External ID: USEP-CON-230927-04 Report Number: GAL01761-23

Minimum Strength 35 MPa at 56 Days


Batching Date: 09/27/2023 Time: 07:40 Air Temp. During Pour (°C): 17.0
Sampling Date: 09/27/2023 Time: 09:10 Concrete Temp. During Pour (°C): 23.0
Supplier: CRHCA Concrete Specified Slump (mm): 120 To 180
Concrete Mix ID: WC12U510 Measured Slump (mm): 150
Delivery Ticket No.: 24918914 Specified Air Content (%): 5.0 To 8.0
Truck No.: 1869 Measured Air Content (%): 6.5
Load No.: 4 Water Added on Site: NA
Contractor: NA Type of Admixtures: Plastol 341
Departure From Site: 09/28/2023 Time: 17:00 Nominal Aggregate Size (mm): 20
Received in Lab: 09/28/2023 Time: 18:00 Plastic Density (kg/m³): NA

Test Specimen
Cast by: Arjun Cast Time: 9:25 Lab Number: GAL23-02005
Total Number: 8 Mold Type: Plastic 102mm x 201mm Curing Location: On site in WSP curing box with max/min.
Initial Curing Temp. (°C): Min 19 Max 23 Self Consolidating Concrete (SCC Only) Spec.Slump Flow NA to NA
Non-Standard Curing VSI Value NA Slump Flow NA
NA
Conditions VSI Values (As per CSA A23.2-19C) T50 cm Time NA

Results
Curing
Age of test Avg. Hardened Cylinder
Condition Avg. Length Type of
Cylinder ID Date Tested Tested By (days) 'x' if Diameter Mass (g) Density Compressive
(Standard or (mm) Fracture
Hold (mm) (kg/m³) Strength (MPa)
Field)
A 10/04/2023 Saleh, Abu 7 Standard 101.5 200.0 3814 2360 1 28.8
B 10/04/2023 Saleh, Abu 7 Standard 101.5 200.0 3820 2360 1 28.9
C 10/25/2023 Saleh, Abu 28 Standard 101.5 200.0 3770 2330 1 41.0
D 10/25/2023 Saleh, Abu 28 Standard 101.5 200.0 3732 2310 1 40.8
E 11/22/2023 Bourne, Shane 56 Standard 101.5 200.0 3775 2330 1 47.5
F 11/22/2023 Bourne, Shane 56 Standard 101.5 200.0 3793 2340 1 47.0
G 10/02/2023 Saleh, Abu 5 Field 101.5 200.0 3816 2360 1 26.5
H 10/02/2023 Saleh, Abu 5 Field 101.5 200.0 3826 2360 1 26.0

Average Strength at: 56 Days: 47.2

Type of fracture (As per CSA A23.2-9C)


1. 2. 3. 4. 5. 6.
Cones Cone Columnar Diagonal Side Similar to
on both on one vertical fracture with fracture type 5 with
ends end cracking no cracking at top / pointed
through ends bottom end(s)

Lab Reporting Comments / Deviations


RFT# 00186-0-CON-20230926-20230927-177.02-BLD-USP-GLD
General Comments

Reviewed By: Harun Rashid Title: Laboratory Supervisor

Signature:

Notice: The test data given herein pertain to the sample provided and may not be applicable to other samples or to material from earlier or subsequent production.
Reporting of these results constitutes a testing service only. Engineering interpretation and advice may be provided upon written request.