Hoval TopVent ®
TH | TC | THC | MH | MC | MHC
Design handbook
Recirculation units and supply air units with efficient air distribution
for heating and cooling with central heat and cold generation
TopVent ® TH 7
B
Recirculation units for heating spaces up to 25 m in height
with central heat supply
TopVent ® TC 19
C
Recirculation units for heating and cooling spaces up to 25 m in height
with central heat and cold supply (2-pipe-system)
TopVent ® THC 33
D
Recirculation units for heating and cooling spaces up to 25 m in height
with central heat and cold supply (4-pipe-system)
TopVent ® MH 45
E
Supply air units for ventilating and heating spaces up to 25 m in height
with central heat supply
TopVent ® MC 57
F
Supply air units for ventilating, heating and cooling spaces up to 25 m in
height with central heat and cold supply (2-pipe-system)
TopVent ® MHC 71
G
Supply air units for ventilating, heating and cooling spaces up to 25 m in
height with central heat and cold supply (4-pipe-system)
Options 85
H
Control systems
Hoval TopTronic ® C
→ see 'Control Systems for Hoval Indoor Climate Systems' manual
1
2
Hoval Indoor Climate Systems
Content
3
Hoval Indoor Climate Systems
Efficient. Flexible. Reliable.
Hoval indoor climate systems are decentralised systems for Draught-free air distribution
heating, cooling and ventilating halls for industrial, commer- A key feature of Hoval indoor climate units is the patented
cial and leisure applications. The systems have a modular vortex air distributor, known as the Air-Injector. It is controlled
structure. One system comprises several ventilation units automatically and changes the blowing angle of the air
which are spread around the room. These units are equipped continuously between vertical and horizontal. The highly
with reversible heat pumps and gas-fired appliances for efficient air supply system has many advantages:
decentralised heat and cold generation, or they heat and ■ It provides a high level of comfort during heating and
cool with a connection to a central energy supply. cooling. No draughts develop in the hall.
Tailored control systems complete the system and ensure ■ The efficient and even air distribution ensures that the
the effective combination and optimal use of all resources. indoor climate units cover a large area.
■ The Air-Injector keeps the temperature stratification in the
Diverse range of units ensures flexibility room low, thus minimising heat loss through the roof.
Different types of ventilation units can be combined to create
the perfect system for the project in question: Control with specialist expertise
■ RoofVent ® supply and extract air handling units The TopTronic ® C control system, which was specifically
■ TopVent ® supply air units developed for Hoval indoor climate systems, regulates the
■ TopVent ® recirculation units separate units individually and controls them based on
The number of supply and extract air handling units zones. This enables optimal adjustment to the local require-
depends on how much fresh air is required in order to ments of the different usage areas in the building. The
create a comfortable atmosphere for people in the building. patented control algorithm optimises energy use and ensures
Recirculation units cover additional heat or cool demand as maximum comfort and hygiene levels. Clear interfaces make
required. A broad range of unit types and sizes with heating it easy to connect the system to the building management
and cooling coils in various output levels means that the system.
overall output of the system can be scaled to whatever level Simpler control systems are also available for units that are
is required. only used for supply air or air recirculation.
Specially designed unit versions are also available for halls
with particularly humid or oily extract air. Competent and reliable
Furthermore, there is a range of units available which Hoval will support you and provide expert knowledge
have been expressly developed for very specific purposes. throughout all project phases. You can rely on comprehen-
ProcessVent units, for example, are coupled with extract air sive technical advice when it comes to planning Hoval indoor
purification systems in industrial halls and recover heat from climate systems and on the skills of the Hoval technicians
process air. during the installation, commissioning and maintenance of
the system.
4
Hoval Indoor Climate Systems
System overview
A
System with decentralised heat and cold generation with heat pump
5
6
TopVent ® TH
Content
TopVent ® TH
B
Recirculation units for heating spaces up to 25 m in height
with central heat supply
1 Use . . . . . . . . . . . . . . . . . . . . . . . 8
3 Technical data . . . . . . . . . . . . . . . . . . 11
4 Specification texts . . . . . . . . . . . . . . . . 14
7
TopVent ® TH
Use
TopVent ® TH units are recirculation units for heating spaces The TopVent ® TH unit consists of the following components:
up to 25 m in height with central heat supply. They have the ■ Fan unit:
following functions: Axial fan with energy-saving EC motor, maintenance-free
■ Heating (with connection to a hot water supply) and infinitely variable
■ Recirculation operation ■ Heating section:
■ Air distribution and destratification with adjustable Contains the heating coil for heating the supply air with
Air-Injector hot water
■ Air filtration (option) ■ Air-Injector:
The Air-Injector is a patented, infinitely variable vortex air
TopVent ® TH units comply with all the requirements of the distributor for the draught-free introduction of air into the
Ecodesign Directive 2009/125/EC relating to environmentally hall under changing operating conditions.
friendly design of energy-related products. It is a system of As part of the TopTronic ® C control system, the unit control
the 'fan coil unit' type. box is an integral component.
8
TopVent ® TH
Construction and operation
■ Suspension set
1
■ Fan
2
■ Heating coil
3
■ Air-Injector
4
■ Actuator Air-Injector
5
B
■ Extract air
1
■ Heating coil
4
■ Supply air
7
5
6
9
TopVent ® TH
Construction and operation
The same as REC, but the unit operates only at speed 1 Heating............................. on
(low air flow rate) 1) Depending on heat demand
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Heating............................. on
heats up the room in recirculation operation.
L_OFF Off (local operating mode) Fan................................... off
The unit is switched off. Heating............................. off
10
TopVent ® TH
Technical data
Unit type
TopVent ® TH 3.5 Sound level
Unit size Unit type TH-6C TH-9C
6 or 9 Sound pressure level (at a distance of 5 m) 1) dB(A) 55 58
Total sound power level dB(A) 77 80
Heating section
Octave sound power level 63 Hz dB 55 61
A with coil type A
125 Hz dB 60 65
B with coil type B
250 Hz dB 65 69
C with coil type C
500 Hz dB 70 73
Further options 1000 Hz dB 74 75
2000 Hz dB 70 75
Table B2: TopVent ® TH type code
4000 Hz dB 64 70
8000 Hz dB 56 63
1) with a hemispherical radiation pattern in a low-reflection room
11
TopVent ® TH
Technical data
TopVent ® TH
Model Unit
6A 6B 6C 9A 9B 9C
Total electric power input (Pelec) 0.46 0.53 0.74 0.84 0.96 1.26 kW
Hoval Aktiengesellschaft
Contact details Austrasse 70, 9490 Vaduz, Liechtenstein
www.hoval.com
Table B8: Product information according to Commission Regulation (EU) 2016/2281, Table 13
12
TopVent ® TH
Technical data
1
2
■ Return heating
1
■ Flow heating
2
13
TopVent ® TH
Specification texts
TopVent ® TH units comply with all the requirements of the Outlet nozzle (variant)
Ecodesign Directive 2009/125/EC relating to environmentally
friendly design of energy-related products. They are systems Housing made of magnesium zinc sheet, air-tight, flame
of the 'fan coil unit' type, provided for in Commission Regula- retardant, hygienic and easy to maintain because of
tion (EU) 2016/2281. ageing-resistant, silicone-free sealing materials. Concentric
outlet nozzle with a supply air sensor.
Fan unit
Unit control box
Consisting of maintenance-free, direct-drive axial fan with
high-efficiency EC motor and balanced rotating wheel with Control box fitted at the side of the unit for connection of the
aerodynamically shaped blades and serrated trailing edge power supply and housing the control components that facil-
(integrated in the heating section). itate energy-optimised operation, controlled by the control
system TopTronic ® C. Plastic casing, protection rating IP 56.
The following components are installed:
Heating section ■ Isolation switch
■ Circuit board with all required electrical components, unit
Housing made of magnesium zinc sheet, air-tight, flame controller (clipped on) as well as connection terminals for
retardant, hygienic and easy to maintain because of the following external connections:
ageing-resistant, silicone-free sealing materials. – Heating valve
The heating section contains: – Heating pump
■ The highly efficient heating coil consisting of seamless – Return temperature sensor
copper pipes with pressed-on, optimised and profiled – Door contact
aluminium fins and manifolds made of copper; for connec- The circuit board is fitted with push-in terminals facilitating
tion to the hot water supply easy installation of the connection cables. All components in
the unit control box as well as sensors and actuators in the
unit are fully factory-wired.
Power supply and bus connection to be installed on site.
14
TopVent ® TH
Specification texts
Suspension set
For ceiling installation of the unit consisting of 4 pairs
U-profiles made of magnesium zinc sheet, height-adjustable
to 1300 mm.
Filter box
Housing made of magnesium zinc sheet with 2 ISO coarse
60% bag filters (G4), with differential pressure switch for filter
monitoring, factory-wired to the circuit board in the unit control
box.
Recirculation silencer
As an attachment to the unit, made of magnesium zinc sheet,
lined with sound insulation matting, insertion attenuation
3 dB.
15
TopVent ® TH
Specification texts
4.2 TopTronic ® C – System control ■ Main operating modes of supply and extract air handling
units:
Zone-based control system for the energy-optimised VE..... Ventilation, infinitely variably adjustment
operation of decentralised Hoval indoor climate systems. AQ ���� Air quality, automatic control with Hoval combina-
Maximum system size per system bus: 64 control zones with tion sensor (option), optional reference variable:
up to 10 supply and extract air handling units or supply air – CO2 or VOC
handling units and 10 recirculation air handling units each. – Air humidity (optimised dehumidification mode)
REC.. Recirculation, infinitely variably adjustment
Zone allocation DES... Destratification
Configured in advance for the customer at the factory: EA..... Exhaust air, infinitely variably adjustment
SA..... Supply air, infinitely variably adjustment
Room designation Unit type ST..... Standby
Zone 1: ______________ ______________
Zone 2: ______________ ______________ ■ Main operating modes of supply air units:
… REC.. Recirculation, infinitely variably adjustment
DES... Destratification
System structure SA ���� Supply air, infinitely variably adjustment
■ Zone control panel made of coated sheet steel With Hoval combination sensor (option) also
(light grey RAL 7035), … x … x … mm, with: demand-driven control of the fresh air ratio, optional
– System operator terminal reference variable CO2 or VOC
– Fresh air temperature sensor ST..... Standby
– 1 zone controller and 1 room temperature sensor per
zone (expandable to up to 4 room temperature sensors ■ Main operating modes of recirculated air units:
per zone) REC.. Recirculation, infinitely variably adjustment
– Safety relay DES... Destratification
– Electrical cabinet internally pre-wired, all components ST..... Standby
routed to terminals
■ Zone bus: as serial bus for communication with all control- ■ Forced heating (construction site heating) can be acti-
lers in one control zone, with robust bus protocol via vated on each device before completion of the overall
shielded, twisted bus cable (provided by the client) system (activation by Hoval service technician)
■ Unit controller: installed in the particular indoor climate ■ Control of draught-free air distribution with the Hoval
unit, works autonomously according to the specifications Air-Injector: the discharge direction is adjusted infinitely
of the zone controller variably and automatically according to the respec-
■ Heating/cooling demand per zone with feedback tive operating condition and the existing temperatures
monitoring (heating/cooling).
16
TopVent ® TH
Specification texts
Functions, standard
■ Room temperature control via sequential control of the
coils
■ Intelligent automatic heating to reach the desired room
temperature at the switching time
■ 4 adjustable room temperature set values per zone:
– Cooling protection (lower setpoint in standby)
– Overheating protection (upper setpoint in standby)
– Room set value winter
– Room set value summer
17
TopVent ® TH
Specification texts
Alarms, protection
■ Central alarm management with registration of all alarms
(timestamp, priority, status) in an alarm list and alarm
memory of the last 50 alarms; forwarding via e-mail can
be set in the parameters.
■ If there is a failure of communication, bus stations, sensor
systems or supply media, each part of the system transi-
tions to a protection mode which safeguards operation.
■ A maintenance mode implemented in the control algorithm
for testing all physical data points and alarms guarantees
high reliability.
■ Pre-programmed data points retrievable via logger func-
tion for 1 year
18
TopVent ® TC
Content
TopVent ® TC
C
Recirculation units for heating and cooling spaces up to 25 m in height
with central heat and cold supply (2-pipe-system)
1 Use . . . . . . . . . . . . . . . . . . . . . . . 20
3 Technical data . . . . . . . . . . . . . . . . . . 23
4 Specification texts . . . . . . . . . . . . . . . . 27
19
TopVent ® TC
Use
TopVent ® TC units are recirculation units for heating and The TopVent ® TC unit consists of the following components:
cooling spaces up to 25 m in height with central heat and ■ Fan unit:
cold supply. They have the following functions: Diagonal fan with energy-saving EC motor, mainte-
■ Heating (with connection to a hot water supply) nance-free and infinitely variable
■ Cooling (with connection to a water chiller) ■ Heating/cooling section:
■ Recirculation operation Contains the heating/cooling coil for heating and cooling
■ Air distribution and destratification with adjustable the supply air with hot water or cold water and the
Air-Injector condensate separator for the condensate generated
■ Air filtration (option) ■ Air-Injector:
The Air-Injector is a patented, infinitely variable vortex air
TopVent ® TC units comply with all the requirements of the distributor for the draught-free introduction of air into the
Ecodesign Directive 2009/125/EC relating to environmentally hall under changing operating conditions.
friendly design of energy-related products. It is a system of As part of the TopTronic ® C control system, the unit control
the 'fan coil unit' type. box is an integral component.
possible dangers.
Fig. C1: TopVent ® TC components
20
TopVent ® TC
Construction and operation
■ Actuator Air-Injector
1
■ Condensate connection
2
■ Heating/cooling coil
3
■ Suspension set
4
■ Condensate separator
5
■ Fan
6
4 ■ Air-Injector
7
2
6
■ Extract air
1
■ Condensate separator
4
■ Fan
5
■ Supply air
8
6
7
21
TopVent ® TC
Construction and operation
The same as REC, but the unit operates only at speed 1 Heating/cooling................. on
(low air flow rate) 1) Depending on heat or cool demand
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Heating............................. on
heats up the room in recirculation operation.
OPR ■ Overheating protection: Fan................................... speed 2
If the room temperature rises above the set value for overheating protection, the Cooling.............................. on
unit cools down the room in recirculation operation.
L_OFF Off (local operating mode) Fan................................... off
The unit is switched off. Heating/cooling................. off
22
TopVent ® TC
Technical data
23
TopVent ® TC
Technical data
24
TopVent ® TC
Technical data
TopVent ® TC
Model Unit
6-C 9-C 9-D
Hoval Aktiengesellschaft
Contact details Austrasse 70, 9490 Vaduz, Liechtenstein
www.hoval.com
Table C9: Product information according to Commission Regulation (EU) 2016/2281, Table 13
25
TopVent ® TC
Technical data
1
2
■ Return heating/cooling
1 ■ Condensate connection
3
■ Flow heating/cooling
2 ■ Access panel
4
26
TopVent ® TC
Specification texts
TopVent ® TC units comply with all the requirements of the Unit control box
Ecodesign Directive 2009/125/EC relating to environmentally
friendly design of energy-related products. They are systems Control box fitted at the side of the unit for connection of the
of the 'fan coil unit' type, provided for in Commission Regula- power supply and housing the control components that facil-
tion (EU) 2016/2281. itate energy-optimised operation, controlled by the control
system TopTronic ® C. Plastic casing, protection rating IP 56.
The following components are installed:
Fan unit ■ Isolation switch
■ Circuit board with all required electrical components, unit
Consisting of radial fan with high-efficiency EC motor, back- controller (clipped on) as well as connection terminals for
wards-curved, three-dimensional contoured blades and the following external connections:
free-running rotor made of a high-performance composite – Heating/cooling valve
material, aerodynamically optimised inflow nozzle, low-noise, – Heating/cooling pump
with integrated overload protection (integrated in the heating/ – Return temperature sensor
cooling section). – Condensate pump
– Door contact
The circuit board is fitted with push-in terminals facilitating
Heating/cooling section easy installation of the connection cables. All components in
the unit control box as well as sensors and actuators in the
Housing made of magnesium zinc sheet, air-tight, flame unit are fully factory-wired.
retardant, hygienic and easy to maintain because of Power supply and bus connection to be installed on site.
ageing-resistant, silicone-free sealing materials, internally
insulated with close-pored polyurethane.
The heating/cooling section contains:
■ The highly efficient heating/cooling coil consisting of
seamless copper pipes with pressed-on, optimised and
profiled aluminium fins and manifolds made of copper; for
connection to the hot water and cold water supply
■ The pull-out condensate separator with collecting channel,
made of high-quality corrosion-resistant material, with a
downslope in all directions for rapid draining
■ The condensate trap for connecting to a condensate drain
(supplied)
27
TopVent ® TC
Specification texts
Suspension set
For ceiling installation of the unit consisting of 4 pairs
U-profiles made of magnesium zinc sheet, height-adjustable
to 1300 mm.
Filter box
Housing made of magnesium zinc sheet with 2 ISO coarse
60% bag filters (G4), with differential pressure switch for
filter monitoring, factory-wired to the circuit board in the unit
control box.
Recirculation silencer
As an attachment to the unit, made of magnesium zinc sheet,
lined with sound insulation matting, insertion attenuation
3 dB.
28
TopVent ® TC
Specification texts
4.2 TopTronic ® C – System control ■ Main operating modes of supply and extract air handling
units:
Zone-based control system for the energy-optimised VE..... Ventilation, infinitely variably adjustment
operation of decentralised Hoval indoor climate systems. AQ ���� Air quality, automatic control with Hoval combina-
Maximum system size per system bus: 64 control zones with tion sensor (option), optional reference variable:
up to 10 supply and extract air handling units or supply air – CO2 or VOC
handling units and 10 recirculation air handling units each. – Air humidity (optimised dehumidification mode)
REC.. Recirculation, infinitely variably adjustment
Zone allocation DES... Destratification
Configured in advance for the customer at the factory: EA..... Exhaust air, infinitely variably adjustment
SA..... Supply air, infinitely variably adjustment
Room designation Unit type ST..... Standby C
Zone 1: ______________ ______________
Zone 2: ______________ ______________ ■ Main operating modes of supply air units:
… REC.. Recirculation, infinitely variably adjustment
DES... Destratification
System structure SA ���� Supply air, infinitely variably adjustment
■ Zone control panel made of coated sheet steel With Hoval combination sensor (option) also
(light grey RAL 7035), … x … x … mm, with: demand-driven control of the fresh air ratio, optional
– System operator terminal reference variable CO2 or VOC
– Fresh air temperature sensor ST..... Standby
– 1 zone controller and 1 room temperature sensor per
zone (expandable to up to 4 room temperature sensors ■ Main operating modes of recirculated air units:
per zone) REC.. Recirculation, infinitely variably adjustment
– Safety relay DES... Destratification
– Electrical cabinet internally pre-wired, all components ST..... Standby
routed to terminals
■ Zone bus: as serial bus for communication with all control- ■ Forced heating (construction site heating) can be acti-
lers in one control zone, with robust bus protocol via vated on each device before completion of the overall
shielded, twisted bus cable (provided by the client) system (activation by Hoval service technician)
■ Unit controller: installed in the particular indoor climate ■ Control of draught-free air distribution with the Hoval
unit, works autonomously according to the specifications Air-Injector: the discharge direction is adjusted infinitely
of the zone controller variably and automatically according to the respec-
■ Heating/cooling demand per zone with feedback tive operating condition and the existing temperatures
monitoring (heating/cooling).
29
TopVent ® TC
Specification texts
Functions, standard
■ Room temperature control via sequential control of the
coils
■ Intelligent automatic heating to reach the desired room
temperature at the switching time
■ 4 adjustable room temperature set values per zone:
– Cooling protection (lower setpoint in standby)
– Overheating protection (upper setpoint in standby)
– Room set value winter
– Room set value summer
30
TopVent ® TC
Specification texts
Alarms, protection
■ Central alarm management with registration of all alarms
(timestamp, priority, status) in an alarm list and alarm
memory of the last 50 alarms; forwarding via e-mail can
be set in the parameters.
■ If there is a failure of communication, bus stations, sensor
systems or supply media, each part of the system transi-
tions to a protection mode which safeguards operation.
■ A maintenance mode implemented in the control algorithm
for testing all physical data points and alarms guarantees
high reliability.
■ Pre-programmed data points retrievable via logger func-
tion for 1 year
31
32
TopVent ® THC
Content
TopVent ® THC
D
Recirculation units for heating and cooling spaces up to 25 m in height
with central heat and cold supply (4-pipe-system)
1 Use . . . . . . . . . . . . . . . . . . . . . . . 34
3 Technical data . . . . . . . . . . . . . . . . . . 37
4 Specification texts . . . . . . . . . . . . . . . . 41
33
TopVent ® THC
Use
TopVent ® THC units are recirculation units for heating and The TopVent ® THC unit consists of the following
cooling spaces up to 25 m in height with central heat and components:
cold supply. They have the following functions: ■ Fan unit:
■ Heating (with connection to a hot water supply) Diagonal fan with energy-saving EC motor,
■ Cooling (with connection to a water chiller) maintenance-free and infinitely variable
■ Recirculation operation ■ Heating section:
■ Air distribution and destratification with adjustable Contains the heating coil for heating the supply air with
Air-Injector hot water
■ Air filtration (option) ■ Cooling section:
Contains the cooling coil for cooling the supply air
TopVent ® THC units comply with all the requirements of the with cold water and the condensate separator for the
Ecodesign Directive 2009/125/EC relating to environmentally condensate generated
friendly design of energy-related products. It is a system of ■ Air-Injector:
the 'fan coil unit' type. The Air-Injector is a patented, infinitely variable vortex air
distributor for the draught-free introduction of air into the
The Hoval TopTronic ® C integrated control system ensures hall under changing operating conditions.
energy-efficient, demand-based operation of Hoval indoor As part of the TopTronic ® C control system, the unit control
climate systems. box is an integral component.
■ Fan unit
4
1.2 User group ■ Air-Injector
5
34
TopVent ® THC
Construction and operation
■ Actuator Air-Injector
1
■ Condensate connection
2
■ Heating coil
3
■ Suspension set
4
■ Cooling coil
5
■ Condensate separator
6
■ Fan
7
■ Air-Injector
4
8
6
D
2
7
■ Extract air
1
■ Cooling coil
4
■ Condensate separator
5
■ Fan
2
6
■ Supply air
9
7
8
35
TopVent ® THC
Construction and operation
The same as REC, but the unit operates only at speed 1 Heating/cooling................. on
(low air flow rate) 1) Depending on heat or cool demand
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Heating............................. on
heats up the room in recirculation operation.
OPR ■ Overheating protection: Fan................................... speed 2
If the room temperature rises above the set value for overheating protection, the Cooling.............................. on
unit cools down the room in recirculation operation.
L_OFF Off (local operating mode) Fan................................... off
The unit is switched off. Heating/cooling................. off
36
TopVent ® THC
Technical data
Heating section
A with coil type A
B with coil type B 3.4 Air flow rate D
C with coil type C
Unit type THC-6 THC-9
Nominal air flow rate m³/h 6000 9000
Cooling section
Floor area covered m² 537 946
C with coil type C
D with coil type D Table D5: TopVent ® THC air flow rate
Further options
3.5 Sound level
Table D2: TopVent ® THC type code
Unit type THC-6CC THC-9CC
Sound pressure level (at a distance of dB(A) 59 60
5 m) 1)
3.2 Application limits Total sound power level dB(A) 81 82
Octave sound power level 63 Hz dB 42 47
Extract air temperature max. °C 50
125 Hz dB 56 66
Moisture content of extract air max. g/kg 15
250 Hz dB 65 69
Supply air temperature max. °C 60
500 Hz dB 70 74
Temperature of the heating medium 1) max. °C 90
1000 Hz dB 76 77
Pressure of the heating medium max. kPa 800
2000 Hz dB 76 76
Air flow rate Size 6: min. m³/h 3100
4000 Hz dB 74 74
Size 9: min. m³/h 5000
8000 Hz dB 68 67
Condensate quantity Size 6: max. kg/h 90 1) with a hemispherical radiation pattern in a low-reflection room
Size 9: max. kg/h 150
The units cannot be used in: Table D6: TopVent ® THC sound level
■ Damp locations
■ Places with a corrosive or aggressive environment
■ Spaces with a large amount of dust
■ Areas where there is danger of explosion
1) Design for higher temperatures on request
37
TopVent ® THC
Technical data
38
TopVent ® THC
Technical data
TopVent ® THC
Model Unit
6-AC 6-BC 6-CC 9-AC 9-BC 9-CC 9-AD 9-BD 9-CD
Cooling capacity (sensible) (Prated,c) 26.5 26.5 26.5 41.0 41.0 41.0 48.6 48.6 48.6 kW
Cooling capacity (latent) (Prated,c) 5.6 5.6 5.6 7.3 7.3 7.3 15.2 15.2 15.2 kW
Heating capacity (Prated,h) 13.2 18.9 29.8 22.6 28.5 46.2 22.6 28.5 46.2 kW
Total electric power input (Pelec) 1.38 1.41 1.5 1.37 1.49 1.42 1.54 1.56 1.68 kW
39
TopVent ® THC
Technical data
1
2
3
4
■ Return heating
1 ■ Return cooling
3 ■ Condensate connection
5
■ Flow heating
2 ■ Flow cooling
4 ■ Access panel
6
40
TopVent ® THC
Specification texts
4 Specification texts aluminium fins and manifolds made of copper; for connec-
tion to the cold water supply
■ The pull-out condensate separator with collecting channel,
4.1 TopVent ® THC made of high-quality corrosion-resistant material, with a
downslope in all directions for rapid draining
Recirculation unit for heating and cooling rooms up to 25 m ■ The condensate trap for connecting to a condensate drain
in height with central heat and cold supply (4-pipe system); (supplied)
equipped with highly efficient air distributor; maximum floor
area reached per unit 537 m² (size 6) and 946 m² respec-
tively (size 9). Air-Injector
The unit consists of the following components: Housing made of magnesium zinc sheet, air-tight, flame
■ Fan unit retardant, hygienic and easy to maintain because of
■ Heating section ageing-resistant, silicone-free sealing materials, internally
■ Cooling section insulated with close-pored polyurethane, with:
■ Air-Injector ■ Vortex air distributor with concentric outlet nozzle,
■ Unit control box adjustable vanes and integrated absorber hood D
■ Optional components ■ Actuator for infinitely variable adjustment of the air
distribution from vertical to horizontal
TopVent ® THC units comply with all the requirements of the – for draught-free air distribution in the hall under
Ecodesign Directive 2009/125/EC relating to environmentally changing operating conditions
friendly design of energy-related products. They are systems – for the rapid and large-area reduction of temperature
of the 'fan coil unit' type, provided for in Commission Regula- stratification in the room through induction of secondary
tion (EU) 2016/2281. air and strong mixing of the room air with supply air
■ Supply air temperature sensor
Fan unit
Unit control box
Consisting of radial fan with high-efficiency EC motor, back-
wards-curved, three-dimensional contoured blades and Control box fitted at the side of the unit for connection of the
free-running rotor made of a high-performance composite power supply and housing the control components that facil-
material, aerodynamically optimised inflow nozzle, low-noise, itate energy-optimised operation, controlled by the control
with integrated overload protection (integrated in the cooling system TopTronic ® C. Plastic casing, protection rating IP 56.
section). The following components are installed:
■ Isolation switch
■ Circuit board with all required electrical components, unit
Heating section controller (clipped on) as well as connection terminals for
the following external connections:
Housing made of magnesium zinc sheet, air-tight, flame – Heating/cooling valve
retardant, hygienic and easy to maintain because of – Heating/cooling pump
ageing-resistant, silicone-free sealing materials. – Return temperature sensor
The heating section contains: – Condensate pump
■ The highly efficient heating coil consisting of seamless The circuit board is fitted with push-in terminals facilitating
copper pipes with pressed-on, optimised and profiled easy installation of the connection cables. All components in
aluminium fins and manifolds made of copper; for connec- the unit control box as well as sensors and actuators in the
tion to the hot water supply unit are fully factory-wired.
Power supply and bus connection to be installed on site.
Cooling section
41
TopVent ® THC
Specification texts
42
TopVent ® THC
Specification texts
■ Main operating modes of supply and extract air handling Alarms, protection
units: ■ Central alarm management with registration of all alarms
VE..... Ventilation, infinitely variably adjustment (timestamp, priority, status) in an alarm list and alarm
AQ ���� Air quality, automatic control with Hoval combina- memory of the last 50 alarms; forwarding via e-mail can
tion sensor (option), optional reference variable: be set in the parameters.
– CO2 or VOC ■ If there is a failure of communication, bus stations, sensor
– Air humidity (optimised dehumidification mode) systems or supply media, each part of the system transi-
REC.. Recirculation, infinitely variably adjustment tions to a protection mode which safeguards operation.
DES... Destratification ■ A maintenance mode implemented in the control algorithm
EA..... Exhaust air, infinitely variably adjustment for testing all physical data points and alarms guarantees
SA..... Supply air, infinitely variably adjustment high reliability.
ST..... Standby ■ Pre-programmed data points retrievable via logger func-
tion for 1 year
■ Main operating modes of supply air units:
REC.. Recirculation, infinitely variably adjustment Options for the zone control panel
DES... Destratification ■ Alarm lamp
SA ���� Supply air, infinitely variably adjustment ■ Socket D
With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional Per zone:
reference variable CO2 or VOC ■ The change-over between heating and cooling can be
ST..... Standby either automatic or manual
– Cooling lock switch for automatic changeover
■ Main operating modes of recirculated air units: – Heating/cooling switch for manual changeover
REC.. Recirculation, infinitely variably adjustment ■ Additional room temperature sensors (max. 3)
DES... Destratification ■ Combination sensor room air quality, temperature and
ST..... Standby humidity
■ Combination sensor fresh air temperature and humidity
■ Forced heating (construction site heating) can be acti- ■ Transfer of actual values and setpoints from external
vated on each device before completion of the overall systems (0…10 V; 4 - 20 mA)
system (activation by Hoval service technician) ■ Load shedding input
■ Control of draught-free air distribution with the Hoval ■ Signal for external extract air fan
Air-Injector: the discharge direction is adjusted infinitely ■ Operating selector switches on terminal
variably and automatically according to the respec- ■ Operating selector button on terminal
tive operating condition and the existing temperatures ■ Control of distributor pump, incl. power supply
(heating/cooling).
Power distribution:
Operation ■ Circuit breakers and output terminals for Hoval indoor
■ TopTronic ® C-ST system operator terminal: touch panel climate units
for visualisation and control of all Hoval indoor climate ■ Safety relay (4-pin)
units registered on the bus
43
TopVent ® THC
Specification texts
4.3 TopTronic ® C – System control for TopVent ® C-SYS ■ Destratification mode for even temperature distribution
■ Main operating modes of supply air units:
Control system for the energy-optimised operation of decen- REC.. Recirculation, infinitely variably adjustment
tralised Hoval indoor climate systems. Maximum system DES... Destratification
size per system bus: 1 control zone with up to 6 supply air SA ���� Supply air, infinitely variably adjustment
handling units and 10 recirculation air handling units. With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional
System structure reference variable CO2 or VOC
■ Zone control panel, designed as compact cabinet for wall ST..... Standby
installation, made of coated sheet steel (light grey RAL
7035), 380 × 300 × 210 mm, with: ■ Main operating modes of recirculated air units:
– Operating panel REC.. Recirculation, infinitely variably adjustment
– Zone controller DES... Destratification
– Fresh air temperature sensor ST..... Standby
– 1 Room temperature sensor (expandable to up to
4 room temperature sensors) ■ Forced heating (construction site heating) can be acti-
– Safety relay vated on each device before completion of the overall
– Electrical cabinet internally pre-wired system (activation by Hoval service technician)
■ Zone bus: as serial bus for communication with all control- ■ Control of draught-free air distribution with the Hoval
lers in the control zone, with robust bus protocol via Air-Injector: the discharge direction is adjusted infinitely
shielded, twisted bus cable (provided by the client) variably and automatically according to the respec-
■ Unit controller: installed in the particular indoor climate tive operating condition and the existing temperatures
unit, works autonomously according to the specifications (heating/cooling).
of the zone controller
■ Circuit board with external connections for: Operation
– Power supply ■ Operating panel with LCD display, installed in the door of
– Zone bus the zone control panel for visualisation and control of all
– Room temperature sensors (max. 4) Hoval indoor climate units registered on the bus
– Fresh air temperature sensor
– Combination sensor room air quality, temperature and Options for operation
humidity ■ Operating of the units via building management system
– Collective alarm via standardised interfaces:
– Forced off – BACnet
– Heating demand – Modbus IP
– Setpoint heating demand – Modbus RTU
– Fault heat supply
– Cooling demand Alarms, protection
– Fault cold supply ■ Central alarm management with registration of all alarms
– External enabling heating/cooling (for automatic (timestamp, priority, status) in an alarm list and alarm
changeover) memory of the last 50 alarms; forwarding via e-mail can
– External setting heating/cooling (for manual be set in the parameters.
changeover) ■ If there is a failure of communication, bus stations, sensor
– Changeover valves heating/cooling systems or supply media, each part of the system transi-
– External setpoint fresh air ratio tions to a protection mode which safeguards operation.
– Operating selector switch on terminal (digital) ■ A maintenance mode implemented in the control algorithm
– Operating selector button on terminal for testing all physical data points and alarms guarantees
high reliability.
Functions, standard ■ Pre-programmed data points retrievable via logger func-
■ Room temperature control via sequential control of the tion for 1 year
coils
■ Intelligent automatic heating to reach the desired room Options for the zone control panel
temperature at the switching time ■ Additional room temperature sensors (max. 3)
■ 4 adjustable room temperature set values per zone: ■ Combination sensor room air quality, temperature and
– Cooling protection (lower setpoint in standby) humidity
– Overheating protection (upper setpoint in standby) ■ Signal for external extract air fan
– Room set value winter
– Room set value summer
44
TopVent ® MH
Content
TopVent ® MH
E
Supply air units for ventilating and heating spaces up to 25 m in height
with central heat supply
1 Use . . . . . . . . . . . . . . . . . . . . . . . 46
3 Technical data . . . . . . . . . . . . . . . . . . 50
4 Specification texts . . . . . . . . . . . . . . . . 53
45
TopVent ® MH
Use
TopVent ® MH units are supply air units for ventilating and The TopVent ® MH unit consists of the following components:
heating spaces up to 25 m in height with central heat supply. ■ Fan unit:
They have the following functions: Diagonal fan with energy-saving EC motor, mainte-
■ Heating (with connection to a hot water supply) nance-free and infinitely variable
■ Fresh air supply ■ Heating section:
■ Mixed air operation Contains the heating coil for heating the supply air with
■ Recirculation operation hot water
■ Air distribution and destratification with adjustable ■ Air-Injector:
Air-Injector The Air-Injector is a patented, infinitely variable vortex air
■ Air filtration distributor for the draught-free introduction of air into the
hall under changing operating conditions.
TopVent ® MH units comply with all the requirements of the ■ Filter box:
Ecodesign Directive 2009/125/EC relating to environmentally Contains 2 ISO Coarse 60 % bag filters (G4), easily
friendly design of energy-related products. It is a system of accessible behind the sliding door
the 'fan coil unit' type. ■ Mixed air box:
Contains fresh air damper and recirculation damper linked
The Hoval TopTronic ® C integrated control system ensures to move in opposite directions and actuator with spring
energy-efficient, demand-based operation of Hoval indoor return
climate systems. As part of the TopTronic ® C control system, the unit control
box is an integral component.
Intended use also includes compliance with the operating
instructions. Any usage over and above this use is consid-
ered to be not as intended. The manufacturer can accept no
liability for damage resulting from improper use. ■ Mixed air box
1
■ Filter box
2
■ Fan unit
3
1.2 User group ■ Unit control box
4
■ Heating section
5
The units are only allowed to be installed, operated and
maintained by authorised and instructed personnel who
1
■ Air-Injector
6
2
are well acquainted with the units and are informed about 3
possible dangers. 4
46
TopVent ® MH
Construction and operation
■ Actuator Air-Injector
1
■ Frost controller
2
■ Filter box
3
5
■ Mixed air box
4
■ Suspension set
6
■ Fan
8
■ Heating coil
9
6 ■ Air-Injector
10
4
7
2 9
10
E
1
■ Fresh air
1
1
■ Fresh air damper with actuator
2
2
■ Recirculation damper (opposed to the
3
fresh air damper)
3
■ Extract air
4
5
4
■ Mixed air temperature sensor
5
■ Heating coil
8
■ Frost controller
9
■ Supply air
12
8
10
11
12
Fig. E3: TopVent ® MH function diagram
47
TopVent ® MH
Construction and operation
1) Percentage is adjustable
2) Depending on heat demand
48
TopVent ® MH
Construction and operation
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
E
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Fresh air damper............... closed
heats up the room in recirculation operation. Heating............................. on
49
TopVent ® MH
Technical data
Unit type
TopVent ® MH 3.5 Sound level
Unit size Unit type MH-6C MH-9C
6 or 9 Sound pressure level (at a distance of 5 m) 1) dB(A) 58 60
Total sound power level dB(A) 80 82
Heating section
Octave sound power level 63 Hz dB 57 62
A with coil type A
125 Hz dB 61 66
B with coil type B
250 Hz dB 67 71
C with coil type C
500 Hz dB 72 74
Further options 1000 Hz dB 76 77
2000 Hz dB 73 76
Table E2: TopVent ® MH type code
4000 Hz dB 67 71
8000 Hz dB 59 64
1) with a hemispherical radiation pattern in a low-reflection room
50
TopVent ® MH
Technical data
TopVent ® MH
Model Unit
6A 6B 6C 9A 9B 9C
Total electric power input (Pelec) 0.9 1.05 1.29 1.37 1.49 1.91 kW
Hoval Aktiengesellschaft
Contact details Austrasse 70, 9490 Vaduz, Liechtenstein
www.hoval.com
Table E8: Product information according to Commission Regulation (EU) 2016/2281, Table 13
51
TopVent ® MH
Technical data
■ Return heating
1
■ Flow heating
2
52
TopVent ® MH
Specification texts
TopVent ® MH units comply with all the requirements of the Housing made of magnesium zinc sheet, internally insulated
Ecodesign Directive 2009/125/EC relating to environmentally with EPDM, with 2 ISO coarse 60% bag filters (G4), with
friendly design of energy-related products. They are systems differential pressure switch for filter monitoring, factory-wired E
of the 'fan coil unit' type, provided for in Commission Regula- to the circuit board in the unit control box.
tion (EU) 2016/2281.
Housing made of magnesium zinc sheet, air-tight, flame Control box fitted at the side of the unit for connection of the
retardant, hygienic and easy to maintain because of power supply and housing the control components that facil-
ageing-resistant, silicone-free sealing materials. itate energy-optimised operation, controlled by the control
The heating section contains: system TopTronic ® C. Housing made of coated sheet steel
■ The highly efficient heating coil consisting of seamless (light grey RAL 7035), protection rating IP 54. The following
copper pipes with pressed-on, optimised and profiled components are installed:
aluminium fins and manifolds made of copper; for connec- ■ Isolation switch
tion to the hot water supply ■ Circuit board with all required electrical components, unit
controller (clipped on) as well as connection terminals for
the following external connections:
– Heating valve
– Heating pump
– Return temperature sensor
– Forced off
The circuit board is fitted with push-in terminals facilitating
easy installation of the connection cables. All components in
the unit control box as well as sensors and actuators in the
unit are fully factory-wired.
Power supply and bus connection to be installed on site.
53
TopVent ® MH
Specification texts
54
TopVent ® MH
Specification texts
■ Main operating modes of supply and extract air handling Alarms, protection
units: ■ Central alarm management with registration of all alarms
VE..... Ventilation, infinitely variably adjustment (timestamp, priority, status) in an alarm list and alarm
AQ ���� Air quality, automatic control with Hoval combina- memory of the last 50 alarms; forwarding via e-mail can
tion sensor (option), optional reference variable: be set in the parameters.
– CO2 or VOC ■ If there is a failure of communication, bus stations, sensor
– Air humidity (optimised dehumidification mode) systems or supply media, each part of the system transi-
REC.. Recirculation, infinitely variably adjustment tions to a protection mode which safeguards operation.
DES... Destratification ■ A maintenance mode implemented in the control algorithm
EA..... Exhaust air, infinitely variably adjustment for testing all physical data points and alarms guarantees
SA..... Supply air, infinitely variably adjustment high reliability.
ST..... Standby ■ Pre-programmed data points retrievable via logger func-
tion for 1 year
■ Main operating modes of supply air units:
REC.. Recirculation, infinitely variably adjustment Options for the zone control panel
DES... Destratification ■ Alarm lamp
SA ���� Supply air, infinitely variably adjustment ■ Socket
With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional Per zone:
reference variable CO2 or VOC ■ The change-over between heating and cooling can be
ST..... Standby either automatic or manual
– Cooling lock switch for automatic changeover E
■ Main operating modes of recirculated air units: – Heating/cooling switch for manual changeover
REC.. Recirculation, infinitely variably adjustment ■ Additional room temperature sensors (max. 3)
DES... Destratification ■ Combination sensor room air quality, temperature and
ST..... Standby humidity
■ Combination sensor fresh air temperature and humidity
■ Forced heating (construction site heating) can be acti- ■ Transfer of actual values and setpoints from external
vated on each device before completion of the overall systems (0…10 V; 4 - 20 mA)
system (activation by Hoval service technician) ■ Load shedding input
■ Control of draught-free air distribution with the Hoval ■ Signal for external extract air fan
Air-Injector: the discharge direction is adjusted infinitely ■ Operating selector switches on terminal
variably and automatically according to the respec- ■ Operating selector button on terminal
tive operating condition and the existing temperatures ■ Control of distributor pump, incl. power supply
(heating/cooling).
Power distribution:
Operation ■ Circuit breakers and output terminals for Hoval indoor
■ TopTronic ® C-ST system operator terminal: touch panel climate units
for visualisation and control of all Hoval indoor climate ■ Safety relay (4-pin)
units registered on the bus
55
TopVent ® MH
Specification texts
4.3 TopTronic ® C – System control for TopVent ® C-SYS ■ Destratification mode for even temperature distribution
■ Main operating modes of supply air units:
Control system for the energy-optimised operation of decen- REC.. Recirculation, infinitely variably adjustment
tralised Hoval indoor climate systems. Maximum system DES... Destratification
size per system bus: 1 control zone with up to 6 supply air SA ���� Supply air, infinitely variably adjustment
handling units and 10 recirculation air handling units. With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional
System structure reference variable CO2 or VOC
■ Zone control panel, designed as compact cabinet for wall ST..... Standby
installation, made of coated sheet steel (light grey RAL
7035), 380 × 300 × 210 mm, with: ■ Main operating modes of recirculated air units:
– Operating panel REC.. Recirculation, infinitely variably adjustment
– Zone controller DES... Destratification
– Fresh air temperature sensor ST..... Standby
– 1 Room temperature sensor (expandable to up to
4 room temperature sensors) ■ Forced heating (construction site heating) can be acti-
– Safety relay vated on each device before completion of the overall
– Electrical cabinet internally pre-wired system (activation by Hoval service technician)
■ Zone bus: as serial bus for communication with all control- ■ Control of draught-free air distribution with the Hoval
lers in the control zone, with robust bus protocol via Air-Injector: the discharge direction is adjusted infinitely
shielded, twisted bus cable (provided by the client) variably and automatically according to the respec-
■ Unit controller: installed in the particular indoor climate tive operating condition and the existing temperatures
unit, works autonomously according to the specifications (heating/cooling).
of the zone controller
■ Circuit board with external connections for: Operation
– Power supply ■ Operating panel with LCD display, installed in the door of
– Zone bus the zone control panel for visualisation and control of all
– Room temperature sensors (max. 4) Hoval indoor climate units registered on the bus
– Fresh air temperature sensor
– Combination sensor room air quality, temperature and Options for operation
humidity ■ Operating of the units via building management system
– Collective alarm via standardised interfaces:
– Forced off – BACnet
– Heating demand – Modbus IP
– Setpoint heating demand – Modbus RTU
– Fault heat supply
– Cooling demand Alarms, protection
– Fault cold supply ■ Central alarm management with registration of all alarms
– External enabling heating/cooling (for automatic (timestamp, priority, status) in an alarm list and alarm
changeover) memory of the last 50 alarms; forwarding via e-mail can
– External setting heating/cooling (for manual be set in the parameters.
changeover) ■ If there is a failure of communication, bus stations, sensor
– Changeover valves heating/cooling systems or supply media, each part of the system transi-
– External setpoint fresh air ratio tions to a protection mode which safeguards operation.
– Operating selector switch on terminal (digital) ■ A maintenance mode implemented in the control algorithm
– Operating selector button on terminal for testing all physical data points and alarms guarantees
high reliability.
Functions, standard ■ Pre-programmed data points retrievable via logger func-
■ Room temperature control via sequential control of the tion for 1 year
coils
■ Intelligent automatic heating to reach the desired room Options for the zone control panel
temperature at the switching time ■ Additional room temperature sensors (max. 3)
■ 4 adjustable room temperature set values per zone: ■ Combination sensor room air quality, temperature and
– Cooling protection (lower setpoint in standby) humidity
– Overheating protection (upper setpoint in standby) ■ Signal for external extract air fan
– Room set value winter
– Room set value summer
56
TopVent ® MC
Content
TopVent ® MC
F
Supply air units for ventilating, heating and cooling spaces up to 25 m in
height with central heat and cold supply (2-pipe-system)
1 Use . . . . . . . . . . . . . . . . . . . . . . . 58
3 Technical data . . . . . . . . . . . . . . . . . . 62
4 Specification texts . . . . . . . . . . . . . . . . 66
57
TopVent ® MC
Use
TopVent ® MC units are supply air units for ventilating, The TopVent ® MC unit consists of the following components:
heating and cooling spaces up to 25 m in height with central ■ Fan unit:
heat and cold supply. They have the following functions: Diagonal fan with energy-saving EC motor, mainte-
■ Heating (with connection to a hot water supply) nance-free and infinitely variable
■ Cooling (with connection to a water chiller) ■ Heating/cooling section:
■ Fresh air supply Contains the heating/cooling coil for heating and cooling
■ Mixed air operation the supply air with hot water or cold water and the
■ Recirculation operation condensate separator for the condensate generated
■ Air distribution and destratification with adjustable ■ Air-Injector:
Air-Injector The Air-Injector is a patented, infinitely variable vortex air
■ Air filtration distributor for the draught-free introduction of air into the
hall under changing operating conditions.
TopVent ® MC units comply with all the requirements of the ■ Filter box:
Ecodesign Directive 2009/125/EC relating to environmentally Contains 2 ISO Coarse 60 % bag filters (G4), easily
friendly design of energy-related products. It is a system of accessible behind the sliding door
the 'fan coil unit' type. ■ Mixed air box:
Contains fresh air damper and recirculation damper linked
The Hoval TopTronic ® C integrated control system ensures to move in opposite directions and actuator with spring
energy-efficient, demand-based operation of Hoval indoor return
climate systems. As part of the TopTronic ® C control system, the unit control
box is an integral component.
Intended use also includes compliance with the operating
instructions. Any usage over and above this use is consid-
ered to be not as intended. The manufacturer can accept no
liability for damage resulting from improper use. ■ Mixed air box
1
■ Filter box
2
■ Heating/cooling section
3
1.2 User group ■ Unit control box
4
■ Fan unit
5
The units are only allowed to be installed, operated and
maintained by authorised and instructed personnel who
1 ■ Air-Injector
6
are well acquainted with the units and are informed about 2
possible dangers. 3
58
TopVent ® MC
Construction and operation
■ Actuator Air-Injector
1
■ Condensate connection
2
■ Frost controller
3
5
■ Filter box
4
■ Suspension set
7
■ Heating/cooling coil
9
6 ■ Condensate separator
10
4 ■ Fan
11
7
■ Air-Injector
12
2 9
10
F
Fig. F2: TopVent ® MC construction
■ Fresh air
1
1
■ Fresh air damper with actuator
2
2
■ Recirculation damper (opposed to the
3
fresh air damper)
3
■ Extract air
4
5
4
■ Mixed air temperature sensor
5
■ Heating/cooling coil
8
■ Condensate separator
9
■ Fan
10
7
■ Air-Injector with actuator
11
8
■ Supply air temperature sensor
12
9 ■ Supply air
13
10
11
12
13
Fig. F3: TopVent ® MC function diagram
59
TopVent ® MC
Construction and operation
1) Percentage is adjustable
2) Depending on heat or cool demand
60
TopVent ® MC
Construction and operation
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Fresh air damper............... closed
heats up the room in recirculation operation. Heating............................. on
61
TopVent ® MC
Technical data
Heating/cooling section
C with coil type C 3.4 Air flow rate
D with coil type D
Unit type MC-6 MC-9
Further options Nominal air flow rate m³/h 6000 9000
Floor area covered m² 537 946
Table F2: TopVent ® MC type code Table F5: TopVent ® MC air flow rate
62
TopVent ® MC
Technical data
28
40 21.0 21.0 14.0 16 3000 0.0 18.5 18.5 15.2 13 2649 0.0 F
60 20.7 20.7 14.2 16 2961 0.0 18.2 18.2 15.4 12 2609 0.0
MC-6 C
40 25.7 32.3 15.7 39 4630 9.7 23.3 26.1 16.9 25 3734 4.1
32
60 25.4 34.1 15.8 43 4884 12.7 23.0 27.8 17.0 29 3988 7.1
40 32.2 32.2 13.8 16 4614 0.0 28.4 28.4 15.0 12 4064 0.0
28
60 31.8 31.8 13.9 16 4554 0.0 28.0 28.0 15.2 12 4004 0.0
C
40 39.7 51.9 15.3 41 7432 18.0 35.8 35.8 16.6 20 5131 0.0
32
60 39.3 54.7 15.4 46 7829 22.7 35.4 38.1 16.7 22 5459 4.0
MC-9 40 38.1 38.1 11.8 13 5451 0.0 33.2 33.2 13.4 10 4756 0.0
28
60 37.7 37.8 12.0 13 5409 0.1 32.9 32.9 13.6 10 4706 0.0
D
40 47.4 64.8 12.7 39 9285 25.6 42.6 53.3 14.3 26 7626 15.7
32
60 47.1 68.3 12.9 43 9785 31.2 42.2 56.7 14.5 30 8126 21.3
Legend: Type = Type of coil tS = Supply air temperature
tF = Fresh air temperature ∆pW = Water pressure drop
RHF = Relative humidity of the fresh air mW = Water quantity
Qsen = Sensible cooling capacity mC = Condensate quantity
Qtot = Total cooling capacity
Reference: ■ At fresh air temperature 28°C: room air 22°C / 50% RH, extract air 24°C
■ At fresh air temperature 32°C: room air 26°C / 50% RH, extract air 28°C
Fresh air ratio 10%
63
TopVent ® MC
Technical data
TopVent ® MC
Model Unit
6-C 9-C 9-D
Hoval Aktiengesellschaft
Contact details Austrasse 70, 9490 Vaduz, Liechtenstein
www.hoval.com
Table F9: Product information according to Commission Regulation (EU) 2016/2281, Table 13
64
TopVent ® MC
Technical data
1 2
4
3
■ Return heating/cooling
1 ■ Condensate connection
3
■ Flow heating/cooling
2 ■ Access panel
4
65
TopVent ® MC
Specification texts
TopVent ® MC units comply with all the requirements of the Housing made of magnesium zinc sheet, internally insulated
Ecodesign Directive 2009/125/EC relating to environmentally with EPDM, with 2 ISO coarse 60% bag filters (G4), with
friendly design of energy-related products. They are systems differential pressure switch for filter monitoring, factory-wired
of the 'fan coil unit' type, provided for in Commission Regula- to the circuit board in the unit control box.
tion (EU) 2016/2281.
Heating/cooling section Control box fitted at the side of the unit for connection of the
power supply and housing the control components that facil-
Housing made of magnesium zinc sheet, air-tight, flame itate energy-optimised operation, controlled by the control
retardant, hygienic and easy to maintain because of system TopTronic ® C. Housing made of coated sheet steel
ageing-resistant, silicone-free sealing materials, internally (light grey RAL 7035), protection rating IP 54. The following
insulated with close-pored polyurethane. components are installed:
The heating/cooling section contains: ■ Isolation switch
■ The highly efficient heating/cooling coil consisting of ■ Circuit board with all required electrical components, unit
seamless copper pipes with pressed-on, optimised and controller (clipped on) as well as connection terminals for
profiled aluminium fins and manifolds made of copper; for the following external connections:
connection to the hot water and cold water supply – Heating/cooling valve
■ The pull-out condensate separator with collecting channel, – Heating/cooling pump
made of high-quality corrosion-resistant material, with a – Return temperature sensor
downslope in all directions for rapid draining – Condensate pump
■ The condensate trap for connecting to a condensate drain – Forced off
(supplied) The circuit board is fitted with push-in terminals facilitating
easy installation of the connection cables. All components in
the unit control box as well as sensors and actuators in the
unit are fully factory-wired.
Power supply and bus connection to be installed on site.
66
TopVent ® MC
Specification texts
67
TopVent ® MC
Specification texts
■ Main operating modes of supply and extract air handling Alarms, protection
units: ■ Central alarm management with registration of all alarms
VE..... Ventilation, infinitely variably adjustment (timestamp, priority, status) in an alarm list and alarm
AQ ���� Air quality, automatic control with Hoval combina- memory of the last 50 alarms; forwarding via e-mail can
tion sensor (option), optional reference variable: be set in the parameters.
– CO2 or VOC ■ If there is a failure of communication, bus stations, sensor
– Air humidity (optimised dehumidification mode) systems or supply media, each part of the system transi-
REC.. Recirculation, infinitely variably adjustment tions to a protection mode which safeguards operation.
DES... Destratification ■ A maintenance mode implemented in the control algorithm
EA..... Exhaust air, infinitely variably adjustment for testing all physical data points and alarms guarantees
SA..... Supply air, infinitely variably adjustment high reliability.
ST..... Standby ■ Pre-programmed data points retrievable via logger func-
tion for 1 year
■ Main operating modes of supply air units:
REC.. Recirculation, infinitely variably adjustment Options for the zone control panel
DES... Destratification ■ Alarm lamp
SA ���� Supply air, infinitely variably adjustment ■ Socket
With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional Per zone:
reference variable CO2 or VOC ■ The change-over between heating and cooling can be
ST..... Standby either automatic or manual
– Cooling lock switch for automatic changeover
■ Main operating modes of recirculated air units: – Heating/cooling switch for manual changeover
REC.. Recirculation, infinitely variably adjustment ■ Additional room temperature sensors (max. 3)
DES... Destratification ■ Combination sensor room air quality, temperature and
ST..... Standby humidity
■ Combination sensor fresh air temperature and humidity
■ Forced heating (construction site heating) can be acti- ■ Transfer of actual values and setpoints from external
vated on each device before completion of the overall systems (0…10 V; 4 - 20 mA)
system (activation by Hoval service technician) ■ Load shedding input
■ Control of draught-free air distribution with the Hoval ■ Signal for external extract air fan
Air-Injector: the discharge direction is adjusted infinitely ■ Operating selector switches on terminal
variably and automatically according to the respec- ■ Operating selector button on terminal
tive operating condition and the existing temperatures ■ Control of distributor pump, incl. power supply
(heating/cooling).
Power distribution:
Operation ■ Circuit breakers and output terminals for Hoval indoor
■ TopTronic ® C-ST system operator terminal: touch panel climate units
for visualisation and control of all Hoval indoor climate ■ Safety relay (4-pin)
units registered on the bus
68
TopVent ® MC
Specification texts
4.3 TopTronic ® C – System control for TopVent ® C-SYS ■ Destratification mode for even temperature distribution
■ Main operating modes of supply air units:
Control system for the energy-optimised operation of decen- REC.. Recirculation, infinitely variably adjustment
tralised Hoval indoor climate systems. Maximum system DES... Destratification
size per system bus: 1 control zone with up to 6 supply air SA ���� Supply air, infinitely variably adjustment
handling units and 10 recirculation air handling units. With Hoval combination sensor (option) also
demand-driven control of the fresh air ratio, optional
System structure reference variable CO2 or VOC
■ Zone control panel, designed as compact cabinet for wall ST..... Standby
installation, made of coated sheet steel (light grey RAL
7035), 380 × 300 × 210 mm, with: ■ Main operating modes of recirculated air units:
– Operating panel REC.. Recirculation, infinitely variably adjustment
– Zone controller DES... Destratification
– Fresh air temperature sensor ST..... Standby
– 1 Room temperature sensor (expandable to up to
4 room temperature sensors) ■ Forced heating (construction site heating) can be acti-
– Safety relay vated on each device before completion of the overall
– Electrical cabinet internally pre-wired system (activation by Hoval service technician)
■ Zone bus: as serial bus for communication with all control- ■ Control of draught-free air distribution with the Hoval
lers in the control zone, with robust bus protocol via Air-Injector: the discharge direction is adjusted infinitely
shielded, twisted bus cable (provided by the client) variably and automatically according to the respec-
■ Unit controller: installed in the particular indoor climate tive operating condition and the existing temperatures
unit, works autonomously according to the specifications (heating/cooling).
of the zone controller
■ Circuit board with external connections for: Operation
– Power supply ■ Operating panel with LCD display, installed in the door of
– Zone bus the zone control panel for visualisation and control of all F
– Room temperature sensors (max. 4) Hoval indoor climate units registered on the bus
– Fresh air temperature sensor
– Combination sensor room air quality, temperature and Options for operation
humidity ■ Operating of the units via building management system
– Collective alarm via standardised interfaces:
– Forced off – BACnet
– Heating demand – Modbus IP
– Setpoint heating demand – Modbus RTU
– Fault heat supply
– Cooling demand Alarms, protection
– Fault cold supply ■ Central alarm management with registration of all alarms
– External enabling heating/cooling (for automatic (timestamp, priority, status) in an alarm list and alarm
changeover) memory of the last 50 alarms; forwarding via e-mail can
– External setting heating/cooling (for manual be set in the parameters.
changeover) ■ If there is a failure of communication, bus stations, sensor
– Changeover valves heating/cooling systems or supply media, each part of the system transi-
– External setpoint fresh air ratio tions to a protection mode which safeguards operation.
– Operating selector switch on terminal (digital) ■ A maintenance mode implemented in the control algorithm
– Operating selector button on terminal for testing all physical data points and alarms guarantees
high reliability.
Functions, standard ■ Pre-programmed data points retrievable via logger func-
■ Room temperature control via sequential control of the tion for 1 year
coils
■ Intelligent automatic heating to reach the desired room Options for the zone control panel
temperature at the switching time ■ Additional room temperature sensors (max. 3)
■ 4 adjustable room temperature set values per zone: ■ Combination sensor room air quality, temperature and
– Cooling protection (lower setpoint in standby) humidity
– Overheating protection (upper setpoint in standby) ■ Signal for external extract air fan
– Room set value winter
– Room set value summer
69
70
TopVent ® MHC
Content
TopVent ® MHC
G
Supply air units for ventilating, heating and cooling spaces up to 25 m in
height with central heat and cold supply (4-pipe-system)
1 Use . . . . . . . . . . . . . . . . . . . . . . . 72
3 Technical data . . . . . . . . . . . . . . . . . . 76
4 Specification texts . . . . . . . . . . . . . . . . 80
71
TopVent ® MHC
Use
TopVent ® MHC units are supply air units for ventilating, The TopVent ® MHC unit consists of the following
heating and cooling spaces up to 25 m in height with central components:
heat and cold supply. They have the following functions: ■ Fan unit:
■ Heating (with connection to a hot water supply) Diagonal fan with energy-saving EC motor, mainte-
■ Cooling (with connection to a water chiller) nance-free and infinitely variable
■ Fresh air supply ■ Heating section:
■ Mixed air operation Contains the heating coil for heating the supply air with
■ Recirculation operation hot water
■ Air distribution and destratification with adjustable ■ Cooling section:
Air-Injector Contains the cooling coil for cooling the supply air with
■ Air filtration cold water and the condensate separator for the conden-
sate generated
TopVent ® MHC units comply with all the requirements of the ■ Air-Injector:
Ecodesign Directive 2009/125/EC relating to environmentally The Air-Injector is a patented, infinitely variable vortex air
friendly design of energy-related products. It is a system of distributor for the draught-free introduction of air into the
the 'fan coil unit' type. hall under changing operating conditions.
■ Filter box:
The Hoval TopTronic ® C integrated control system ensures Contains 2 ISO Coarse 60 % bag filters (G4), easily
energy-efficient, demand-based operation of Hoval indoor accessible behind the sliding door
climate systems. ■ Mixed air box:
Contains fresh air damper and recirculation damper linked
Intended use also includes compliance with the operating to move in opposite directions and actuator with spring
instructions. Any usage over and above this use is consid- return
ered to be not as intended. The manufacturer can accept no As part of the TopTronic ® C control system, the unit control
liability for damage resulting from improper use. box is an integral component.
7 Fig. G1:
TopVent ® MHC components
72
TopVent ® MHC
Construction and operation
■ Actuator Air-Injector
1
■ Condensate connection
2
■ Frost controller
3
7
■ Heating coil
4
■ Filter box
5
■ Suspension set
8
5 ■ Air-Injector
13
10
11
2
12
13
1
Fig. G2: TopVent ® MHC construction
12
13
14
Fig. G3: TopVent ® MHC function diagram
73
TopVent ® MHC
Construction and operation
1) Percentage is adjustable
2) Depending on heat or cool demand
74
TopVent ® MHC
Construction and operation
ST Standby
The unit is ready for operation. The following operating modes are activated if
required:
CPR ■ Cooling protection: Fan................................... speed 2
If the room temperature drops below the set value for cooling protection, the unit Fresh air damper............... closed
heats up the room in recirculation operation. Heating............................. on
75
TopVent ® MHC
Technical data
Heating section
A with coil type A 3.4 Air flow rate
B with coil type B
C with coil type C Unit type MHC-6 MHC-9
Nominal air flow rate m³/h 6000 9000
Cooling section Floor area covered m² 537 946
C with coil type C Table G5: TopVent ® MHC air flow rate
D with coil type D
Further options
3.5 Sound level
Table G2: TopVent ® MHC type code Unit type MHC-6CC MHC-9CC
Sound pressure level (at a distance of dB(A) 60 60
5 m) 1)
3.2 Application limits Total sound power level dB(A) 82 82
Octave sound power level 63 Hz dB 41 47
Extract air temperature max. °C 50
125 Hz dB 53 67
Moisture content of extract air max. g/kg 15
250 Hz dB 67 70
Supply air temperature max. °C 60
500 Hz dB 71 74
Temperature of the heating medium 1) max. °C 90
1000 Hz dB 77 78
Pressure of the heating medium max. kPa 800
2000 Hz dB 77 76
Air flow rate Size 6: min. m³/h 3100
4000 Hz dB 75 74
Size 9: min. m³/h 5000
8000 Hz dB 69 67
Condensate quantity Size 6: max. kg/h 90 1) with a hemispherical radiation pattern in a low-reflection room
Size 9: max. kg/h 150
The units cannot be used in: Table G6: TopVent ® MHC sound level
■ Damp locations
■ Places with a corrosive or aggressive environment
■ Spaces with a large amount of dust
■ Areas where there is danger of explosion
1) Design for higher temperatures on request
76
TopVent ® MHC
Technical data
77
TopVent ® MHC
Technical data
TopVent ® MHC
Model Unit
6-AC 6-BC 6-CC 9-AC 9-BC 9-CC 9-AD 9-BD 9-CD
Cooling capacity (sensible) (Prated,c) 26.5 26.5 26.5 41.0 41.0 41.0 48.6 48.6 48.6 kW
Cooling capacity (latent) (Prated,c) 5.6 5.6 5.6 7.3 7.3 7.3 15.2 15.2 15.2 kW
Heating capacity (Prated,h) 13.2 18.9 29.8 22.6 28.5 46.2 22.6 28.5 46.2 kW
Total electric power input (Pelec) 1.54 1.58 1.68 1.59 1.72 1.64 1.77 1.79 1.92 kW
Hoval Aktiengesellschaft
Contact details Austrasse 70, 9490 Vaduz, Liechtenstein
www.hoval.com
Table G9: Product information according to Commission Regulation (EU) 2016/2281, Table 13
78
TopVent ® MHC
Technical data
3
4
5 G
■ Return heating
1 ■ Return cooling
3 ■ Condensate connection
5
■ Flow heating
2 ■ Flow cooling
4 ■ Access panel
6
79
TopVent ® MHC
Specification texts
80
TopVent ® MHC
Specification texts
Suspension set
For ceiling installation of the unit consisting of 4 pairs U-pro-
files made of magnesium zinc sheet, height-adjustable to
1300 mm.
Mixing valve
Mixing valve with modulating rotary actuator and plug-in
connection, sized for the coil in the unit.
Condensate pump
Consisting of a centrifugal pump and a drip tray, max.
delivery rate of 150 l/h with a delivery head of 3 m. Conden-
sate pump with connection cable enclosed.
81
TopVent ® MHC
Specification texts
4.2 TopTronic ® C – System control ■ Main operating modes of supply and extract air handling
units:
Zone-based control system for the energy-optimised VE..... Ventilation, infinitely variably adjustment
operation of decentralised Hoval indoor climate systems. AQ ���� Air quality, automatic control with Hoval combina-
Maximum system size per system bus: 64 control zones with tion sensor (option), optional reference variable:
up to 10 supply and extract air handling units or supply air – CO2 or VOC
handling units and 10 recirculation air handling units each. – Air humidity (optimised dehumidification mode)
REC.. Recirculation, infinitely variably adjustment
Zone allocation DES... Destratification
Configured in advance for the customer at the factory: EA..... Exhaust air, infinitely variably adjustment
SA..... Supply air, infinitely variably adjustment
Room designation Unit type ST..... Standby
Zone 1: ______________ ______________
Zone 2: ______________ ______________ ■ Main operating modes of supply air units:
… REC.. Recirculation, infinitely variably adjustment
DES... Destratification
System structure SA ���� Supply air, infinitely variably adjustment
■ Zone control panel made of coated sheet steel (light grey With Hoval combination sensor (option) also
RAL 7035), … x … x … mm, with: demand-driven control of the fresh air ratio, optional
– System operator terminal reference variable CO2 or VOC
– Fresh air temperature sensor ST..... Standby
– 1 zone controller and 1 room temperature sensor per
zone (expandable to up to 4 room temperature sensors ■ Main operating modes of recirculated air units:
per zone) REC.. Recirculation, infinitely variably adjustment
– Safety relay DES... Destratification
– Electrical cabinet internally pre-wired, all components ST..... Standby
routed to terminals
■ Zone bus: as serial bus for communication with all control- ■ Forced heating (construction site heating) can be acti-
lers in one control zone, with robust bus protocol via vated on each device before completion of the overall
shielded, twisted bus cable (provided by the client) system (activation by Hoval service technician)
■ Unit controller: installed in the particular indoor climate ■ Control of draught-free air distribution with the Hoval
unit, works autonomously according to the specifications Air-Injector: the discharge direction is adjusted infinitely
of the zone controller variably and automatically according to the respec-
■ Heating/cooling demand per zone with feedback tive operating condition and the existing temperatures
monitoring (heating/cooling).
82
TopVent ® MHC
Specification texts
Functions, standard
■ Room temperature control via sequential control of the
coils
■ Intelligent automatic heating to reach the desired room
temperature at the switching time
■ 4 adjustable room temperature set values per zone:
– Cooling protection (lower setpoint in standby)
– Overheating protection (upper setpoint in standby)
– Room set value winter
– Room set value summer
83
TopVent ® MHC
Specification texts
Operation
■ Operating panel with LCD display, installed in the door of
the zone control panel for visualisation and control of all
Hoval indoor climate units registered on the bus
Alarms, protection
■ Central alarm management with registration of all alarms
(timestamp, priority, status) in an alarm list and alarm
memory of the last 50 alarms; forwarding via e-mail can
be set in the parameters.
■ If there is a failure of communication, bus stations, sensor
systems or supply media, each part of the system transi-
tions to a protection mode which safeguards operation.
■ A maintenance mode implemented in the control algorithm
for testing all physical data points and alarms guarantees
high reliability.
■ Pre-programmed data points retrievable via logger func-
tion for 1 year
84
Options
Content
1 Type code. . . . . . . . . . . . . . . . . . . . 86
2 Outlet nozzle . . . . . . . . . . . . . . . . . . 90
3 Suspension set. . . . . . . . . . . . . . . . . . 90
4 Air filtration . . . . . . . . . . . . . . . . . . . 90
5 Paint finish . . . . . . . . . . . . . . . . . . . . 91
6 Recirculation silencer. . . . . . . . . . . . . . . 91
7 Acoustic cowl. . . . . . . . . . . . . . . . . . . 91
9 Mixing valve . . . . . . . . . . . . . . . . . . . 94
10 Condensate pump . . . . . . . . . . . . . . . . 94
12 Pump control. . . . . . . . . . . . . . . . . . 95
Options
H
85
Options
Type code
1 Type code
Availability THC - 9 B C / ST . D1 / S . FK . LH . UA / Y . KP / TC . - . PP . RF
Unit type
TH Recirculation unit with heating section
TC Recirculation unit with heating/cooling section
THC Recirculation unit with heating and cooling section
TH TC THC
Unit size
● ● ● 6 Size 6
● ● ● 9 Size 9
Heating section
● - without heating section
● ● A with coil type A
● ● B with coil type B
● ● C with coil type C
Heating/cooling section
● - without heating/cooling section
● ● C with coil type C
● ● D with coil type D
Design
● ● ● ST Standard
Air outlet
● ● ● D1 Design with Air-Injector
● DN Outlet nozzle
Installation
● ● ● - without
● ● ● S Suspension set
Filter box
● ● ● -- without
● ● ● FK Filter box
● ● ● FF Flat filter box
Paint finish
● ● ● -- without
● ● ● LH Standard paint finish
● ● ● LU Paint finish as desired
86
Options
Type code
Availability THC - 9 B C / ST . D1 / S . FK . LH . UA / Y . KP / TC . - . PP . RF
TH TC THC
Silencer
● ● ● -- without
● ● ● U- Recirculation silencer
● ● ● -A Acoustic cowl
● ● ● UA Recirculation silencer and acoustic cowl
Hydraulics
● ● ● - without
● ● ● Y Hydraulic assembly diverting system
● ● ● M Mixing valve
Condensate pump
● ● ● -- without
● ● KP Condensate pump
Control system
● ● ● TC TopTronic ® C
● ● KK Terminal box design
Reserve
Pump control
● ● ● -- without
● ● PH Heating pump
● ● PK Heating or cooling pump
H
● PP Heating pump and cooling pump
87
Options
Type code
Availability MHC - 9 B C / ST . D1 / S . -- . LH . A / Y . KP / TC . PP . RF
Unit type
MH Supply air unit with heating section
MC Supply air unit with heating/cooling section
MHC Supply air unit with heating and cooling section
MH MC MHC
Unit size
● ● ● 6 Size 6
● ● ● 9 Size 9
Heating section
● - without heating section
● ● A with coil type A
● ● B with coil type B
● ● C with coil type C
Heating/cooling section
● - without heating/cooling section
● ● C with coil type C
● ● D with coil type D
Design
● ● ● ST Standard
Air outlet
● ● ● D1 Design with Air-Injector
Installation
● ● ● - without
● ● ● S Suspension set
Reserve
Paint finish
● ● ● -- without
● ● ● LH Standard paint finish
● ● ● LU Paint finish as desired
Silencer
● ● ● -- without
● ● ● A Acoustic cowl
Hydraulics
● ● ● - without
● ● ● Y Hydraulic assembly diverting system
● ● ● M Mixing valve
88
Options
Type code
Availability MHC - 9 B C / ST . D1 / S . -- . LH . A / Y . KP / TC . PP . RF
MH MC MHC
Condensate pump
● ● ● -- without
● ● KP Condensate pump
Control system
● ● ● TC TopTronic ® C
Pump control
● ● ● -- without
● ● PH Heating pump
● ● PK Heating or cooling pump
● PP Heating pump and cooling pump
89
Options
Outlet nozzle
For low-cost recirculation heating the TopVent ® TH unit is For hygiene reasons, Hoval recommends always fitting
available with a simple outlet nozzle. The air discharge angle TopVent ® units with a filter.
cannot be adjusted. Units with outlet nozzle are well-suited
for applications with lower comfort requirements and for large
mounting heights (e.g. in high-bay warehouses). 4.1 Filter box
The outlet nozzle replaces the Air-Injector. The external
dimensions of the unit remain the same. The weight is A filter box with 2 bag filters can be installed for the purpose
reduced: of filtering the recirculation air. The modular construction
■ Size 6: – 15 kg made of magnesium zinc sheet with 2 sliding doors makes it
■ Size 9: – 21 kg easy to replace the filters.
Notice
In the planning phase make sure there is enough
space in front of the sliding doors so that the filters
can be replaced with ease.
Size 6 9
3 Suspension set A mm 900 1100
B mm 400 400
Filter class ISO coarse 60 % (G4)
A suspension set is available to make it easy to install the
Weight kg 20 24
units on the ceiling. The set consists of 4 pairs of U-profiles
Factory setting of TH, MH Pa 120 120
made of magnesium zinc sheet and is height-adjustable up
differential pressure
to 1300 mm. TC, THC, MC, MHC Pa 180 180
switches
Table H3: Filter box technical data
90
Options
Paint finish
Size 6 9 Caution
A mm 900 1100 Risk of injury from falling parts. The silencer cannot
B mm 140 165 bear the weight of the appliance. Do not locate any
Filter class ISO coarse 60 % (G4) suspension points on the silencer.
Weight kg 10 12.5
Factory setting of TH Pa 50 50
differential pressure
switches TC, THC Pa 100 100
A
Table H4: Flat filter box technical data
B
5 Paint finish
7 Acoustic cowl
91
Options
Hydraulic assembly diverting system
Assemblies for hydraulic diverting, which are optimally Default settings for the hydraulic alignment
matched to the units, are available for easy installation of Read off the default settings from the diagrams below. The
TopVent ® units. Please note the following: curves 1.0 to 4.0 correspond to the revolutions of the valve
■ Install the assembly horizontally. spindles of the balancing valve; they are shown on the
■ Mount the assembly so that its weight does not need to be turning knob:
absorbed by the coil. 0.0___ Valve closed
■ Insulate the assembly. 4.0___ Valve fully open
The coil and the hydraulic assembly are already included
in the specified pressure drops. Thus, only consider the
pressure drops of the distributor circuit up to the screw
connections.
16 0 160
14 0 140
12 0 120
10 0 100
80 80
60 60
40 40
20
0
6AB 20
0
9AB
1000 1500 2000 2500 3000 3500 4000 4500 5000 1000 2000 3000 4000 5000 6000 7000 8000 9000
1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 3.0
24 0 240
2.6 4.0
22 0 220
20 0 3.0 200
18 0 180
4.0
16 0 160
14 0 140
12 0 120
10 0 100
80 80
60 60
40 40
20
0
6C 20
0
9C
1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000
220
2.0
200
2.2
180
2.4
160 2.6
140 3.0
120 4.0
100
80
60
40
20
0
9D
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
92
Options
Hydraulic assembly diverting system
■ Control valve
3
■ Flow
E
■ Mixing valve
6
■ Ball valve
7
3
■ Return
8
C
5
2 4
A
D
7
2 4
8
93
Options
Mixing valve
Mixing valves, which are optimally matched to the units, are TopVent ® cooling units must be connected to a condensate
available for easy installation of TopVent ® units. They have drainage system. For applications in which connection to
the following specifications: the waste water system is too expensive or not possible for
■ 3-way mixing valve with modulating rotary actuator structural reasons, a condensate pump can be provided. This
(run time 9 s) is installed directly under the condensate drain connection;
■ Flow characteristic: the supplied container is prepared for installation on the unit.
– Equal percentage control path It pumps the condensate through a flexible hose to a delivery
– Linear bypass head of 3 m, thus enabling discharge of the condensate
■ Integrated position control and response ■ through waste water pipes directly below the ceiling,
■ onto the roof.
DI
L ≥Y M
Type DN kvs DA DI L H M X Y
m³/h " " mm mm mm mm mm
M-6AB 20 6.3 G 1¼ Rp ¾ 86 46 42 220 90
M-6C 25 10 G 1½ Rp 1 85 46 45 220 90
M-9AB 25 10 G 1½ Rp 1 85 46 45 220 90
M-9C 32 10 G2 Rp 1¼ 104 46 56 220 90 Fig. H5: Condensate pump
M-9D 40 16 G 2¼ Rp 1½ 115 51 56 230 90
Table H9: Mixing valve dimensions
Type Weight
M-6AB 2.6
M-6C 3.1 11 Return temperature sensor
M-9AB 3.1
M-9C 4.0
The return temperature sensor monitors the return
M-9D 4.7
temperature of the heating medium.
Table H10: Mixing valve weights (in kg)
94
Options
Pump control
12 Pump control
95
Options
Pump control
TopVent ® TH / MH
1
4
<2m
5
2 3
6
7 8 9 10
11
14
12
15
16
13
17
■ Zone bus
2 ■ Collective alarm
8 ■ Fault heat supply
14
■ Heating pump
5 ■ Distributor pump
11 ■ Heating circuit
17
■ Mixing valve
6 ■ System operator terminal
12
TopVent ® TH / MH
96
Options
Pump control
TopVent ® TC / MC
4
1
<2m
5
6
2 3
7 8 9 10
11
15
12
16
13 17
18 19
14
20
H
21
22
■ Zone bus
2 ■ Room temperature sensor
10 ■ Cooling demand
18
■ Heating/cooling pump
5 ■ Cooling lock switch (option)
13 ■ Heating circuit
21
■ Mixing valve
6 ■ Zone control panel
14 ■ Cooling circuit
22
■ Collective alarm
8 ■ Fault cold supply
16
97
Options
Pump control
4
1
<2m
5 6
2 3
7 8
9 10 11 12
13 14
18
15
19
16 20
21
22
17
23
24
■ Zone bus
2 ■ Collective alarm
10 ■ Fault heat supply
18
■ Cooling pump
5 ■ Distributor pump heating
13 ■ Cooling demand
21
■ Heating pump
6 ■ Distributor pump cooling
14 ■ Heating control panel
22
Fig. H8: Schematic diagram for injection system TopVent ® THC / MHC
98
Transport and installation
Content
1 Installation. . . . . . . . . . . . . . . . . . . 100
99
Transport and installation
Installation
Z
TopVent ® unit
■ Make sure that a lifting platform is available.
■ Only secure the unit to ceilings with sufficient load-bearing
capacity.
■ For the purposes of installation the unit is provided with X/2 X
Y
4 M10 rivet nuts with hexagon bolts and washers.
– Fasten the unit to the ceiling by means of the optional
suspension set or by means of flat iron bars, perforated
bars, angles, steel cables or similar.
– Do not use eyebolts.
Size 6 9
Unit clearance X min. m 12 14
max. m 23 31
Distance from ceiling Z min. m 0.3 0.4
Mounting height Y min. m 4 5
max. 1) m Approx. 9…25
1) The maximum mounting height varies depending on the boundary conditions (for values,
see table of heat outputs or calculation with the 'HK-Select' selection program)
100
Transport and installation
Hydraulic installation
Requirements on the boiler system and the distributor circuit 2.2 Condensate connection
■ Hydraulically balance the pipework for the the individual
units within a control zone to ensure even distribution. Condensate arising in cooling units must be removed via a
■ The heating medium must be available at the mixing valve condensate-proof line.
without delay in the required amount and temperature. ■ Install and insulate the supplied trap on the condensate
■ The condensate separator in cooling units only functions connection of the unit.
while the fan is running. No coolant must be allowed to ■ Dimension the slope and cross-section of the condensate
circulate in the coil when the unit is switched off. line so that no condensate backflow takes place.
■ Depending on local conditions, check whether ■ Make sure that the condensate produced is drained in
compensators for linear expansion are required for the compliance with local regulations.
supply and return lines and/or articulated connections are ■ Route the condensate line from the pump directly
required for the units. upwards.
■ Do not fasten any loads to the coil, e.g. by means of the
flow or return lines. Notice
■ Insulate the hydraulic lines. Use the 'Condensate pump' option for quick and easy
hydraulic installation.
The TopTronic ® C control system switches on the heating/
cooling pumps and the heating/cooling demand every day.
This prevents the pumps from blocking in case of a long
shutdown.
Notice
Use the 'Hydraulic assembly' or 'Mixing valve' options
for quick and easy hydraulic installation.
101
Transport and installation
Hydraulic installation
TopVent ® TH / MH
1
4
5 <2m
2 3
6 7 8 9
10
13
11
14
15
12
16
■ Zone bus
2 ■ Fresh air temperature sensor
8 ■ Heating demand
14
■ Mixing valve
5 ■ System operator terminal
11
102
Transport and installation
Hydraulic installation
TopVent ® TC / MC
4
1
5 <2m
2 3
6 7 8 9
10
14
11
15
12 16
17 18
13
19
20
21 I
■ Zone bus
2 ■ Room temperature sensor
9 ■ Heating demand
16
■ Mixing valve
5 ■ Cooling lock switch (option)
12 ■ Changeover valves heating/cooling
19
■ Collective alarm
7 ■ Fault heat supply
14 ■ Cooling circuit
21
103
Transport and installation
Hydraulic installation
4
1
5 6 <2m
2 3
7 8 9 10
11 12
16
13
17
14 18
19
20
15
21
22
■ Zone bus
2 ■ Room temperature sensor
10 ■ Heating demand
18
■ Collective alarm
8 ■ Fault heat supply
16
Fig. I4: Conceptual drawing for hydraulic diverting system TopVent ® THC / MHC
104
Transport and installation
Electrical installation
3 Electrical installation
105
3.1 Cable list for on-site connections – TopTronic ® C
106
Component Designation Voltage Cable Comments Start Target
TopTronic ® C 3 × 400 V AC NYM-J 5 × … mm² On-site Zone control panel
Power supply
System control 1 × 230 V AC NYM-J 3 × … mm² On-site Zone control panel
Zone bus J-Y(ST)Y 2 × 2 × 0.8 mm max. 500 m length Zone control panel Hoval units
Zone control Further zone control
System bus Ethernet ≥ CAT 5 For connecting several zone control panels Zone control panel
panel panel
Electrical installation
Integration into the Ethernet ≥ CAT 5 BACnet, Modbus IP Zone control panel On-site (BMS)
building management system J-Y(ST)Y 2 × 2 × 0.8 mm Modbus RTU Zone control panel On-site (BMS)
Room temperature sensor J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
Additional room temperature sensors J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
Transport and installation
Operating selector button on terminal 24 V AC J-Y(ST)Y 6 × 2 × 0.8 mm On-site (button) Zone control panel
Forced off 24 V AC NYM-O 2 × 1.5 mm² max. 1 A On-site Zone control panel
Signal external enabling/setting
Heating/cooling changeover 24 V AC NYM-O 2 × 1.5 mm² On-site Zone control panel
max. 1 A
Transport and installation
Changeover valve flow 24 V AC NYM-O 7 × 1.5 mm² see valve specification Zone control panel Valve
Changeover valve return 24 V AC NYM-O 7 × 1.5 mm² see valve specification Zone control panel Valve
TopTronic ® C Power supply 1 × 230 V AC NYM-J 3 × 1.5 mm² On-site Zone control panel
System control Zone bus J-Y(ST)Y 2 × 2 × 0.8 mm max. 500 m length Zone control panel Hoval units
for TopVent ® Integration into the Ethernet ≥ CAT 5 BACnet, Modbus IP Zone control panel On-site (BMS)
(C-SYS) building management system J-Y(ST)Y 2 × 2 × 0.8 mm Modbus RTU Zone control panel On-site (BMS)
Room temperature sensor J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
Zone control Additional room temperature sensors J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
panel Combination sensor room air quality,
J-Y(ST)Y 4 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
temperature and humidity
Fresh air temperature sensor J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel Sensors
Volt-free
Heating demand max. 250 V AC NYM-O 2 × 1.5 mm² max. 8 A Zone control panel On-site
max. 24 V DC
Setpoint heating demand 2-10 V DC J-Y(ST)Y 2 × 2 × 0.8 mm max. 250 m Zone control panel On-site
Volt-free
Cooling demand max. 250 V AC NYM-O 2 × 1.5 mm² max. 8 A Zone control panel On-site
max. 24 V DC
Fault heat supply 24 V AC NYM-O 2 × 1.5 mm² max. 1 A On-site Zone control panel
Fault cold supply 24 V AC NYM-O 2 × 1.5 mm² max. 1 A On-site Zone control panel
Volt-free
Collective alarm max. 250 V AC NYM-O 2 × 1.5 mm² max. 8 A Zone control panel On-site
max. 24 V DC max. 2 A
External setpoint fresh air ratio 0-10 V DC J-Y(ST)Y 2 × 2 × 0.8 mm On-site Zone control panel
Operating selector switch on terminal
0-10 V DC J-Y(ST)Y 6 × 2 × 0.8 mm On-site (switch) Zone control panel
(digital)
Operating selector button on terminal 24 V AC J-Y(ST)Y 6 × 2 × 0.8 mm On-site (button) Zone control panel
Forced off 24 V AC NYM-O 2 × 1.5 mm² max. 1 A On-site Zone control panel
Signal external enabling/setting
Heating/cooling changeover 24 V AC NYM-O 2 × 1.5 mm² On-site Zone control panel
max. 1 A
107
I
Component Designation Voltage Cable Comments Start Target
108
Changeover valve flow 24 V AC NYM-O 7 × 1.5 mm² see valve specification Zone control panel Valve
Changeover valve return 24 V AC NYM-O 7 × 1.5 mm² see valve specification Zone control panel Valve
TopVent ® unit Zone control panel
Power supply 3 × 400 V AC NYM-J 5 × 1.5 mm² (min.) TopVent ® unit
or on-site
Zone bus J-Y(ST)Y 2 × 2 × 0.8 mm max. 500 m length Zone control panel TopVent ® unit
with Hydraulic assembly or Mixing valve
Mixing valve heating 24 V AC NYM-O 4 × 1.0 mm² TopVent ® unit Valve
option: cable connected to the mixing valve
Electrical installation
3.2 EasyTronic EC
Component Designation Voltage Cable Comments Start Target
EasyTronic EC Power supply 1 × 230 V AC NYM 2 × 1.5 mm² (min.) On-site Hoval controller
Heating/cooling changeover 24 V AC NYM-O 2 × 1.5 mm² max. 1 A On-site Hoval controller
Controller Door contact 24 V DC NYM 2 × 1.0 mm² On-site Hoval controller
Modbus RTU J-Y(ST)Y 2 × 2 × 0.8 mm max. 300 m length On-site (BMS) Hoval controller
External room temperature sensor J-Y(ST)Y 2 × 2 × 0.8 mm shielded, max. 30 m length Sensors Hoval controller
System bus J-Y(ST)Y 4 × 2 × 0.8 mm Fan, air distribution Hoval controller Hoval units
230 V AC Depending on the number of
Pump/valve control via field-supplied relay, max 3 A Pump/valve Relay (On-site)
24 V DC contacts
TopVent ® Power supply 3 × 400 V AC NYM-J 5 × 1.5 mm² (min.) max. 1 A On-site TopVent ® unit
System bus J-Y(ST)Y 4 × 2 × 0.8 mm Fan, air distribution Hoval controller TopVent ® unit
Unit Differential pressure switch air filter NYM 2 × 1.0 mm² Signal to on-site lamp or controller TopVent ® unit On-site
230 V AC NYM-J 3 × 1.5 mm² Power supply On-site TopVent ® unit
Condensate pump
J-Y(ST)Y 1 × 2 × 0.8 mm Control line TopVent ® unit On-site
Table I3: Cable list for on-site connections – EasyTronic EC
3.3 Terminal box design
Actuator Air-Injector
Control voltage 2…10 V DC
Setting range 2 - 6.44 V / 0° - 50°
Position response 2…10 V DC
Fan
Enable signal digital
Electrical installation
109
I
110
System design
Content
System design
J
111
System design
Design example
1 Design example
Notice
Use the 'HK-Select' program to design Hoval Indoor Climate Systems.
You can download it free of charge on the Internet.
Mounting height
■ Calculate the actual mounting height (= distance between the floor and the bottom edge of Supply air units:
the units). Size 6 → OK
Size 9 → OK
Y = Hall height – distance from ceiling – unit height
■ Compare the actual mounting height with the minimum and maximum mounting height (see Recirculation units:
Table I1 on page 100 and HK-Select). Size 6 → OK
Size 9 → OK
112
System design
Design example
Recirculation Minimum
Supply air unit Required number of recirculation units
units number of
Floor area Cooling recirculation
Type Type Heat output Unit clearances
covered capacity units
TC-6/C 5 7 6 5 7
1 unit
TC-9/C 3 5 4 5 5
MC-6/C
TC-9/D 3 4 3 5 5
TC-6/C 4 7 5 5 7
1 unit
TC-9/C 3 4 4 3 4
MC-9/C
TC-9/D 3 4 3 3 4
TC-6/C 4 6 5 5 6
1 unit
TC-9/C 3 4 ≈ 3 (-1 kW) 3 4
MC-9/D
TC-9/D 3 ≈ 3 (-2 kW) 3 3 3 J
■ Choose the final solution from the remaining possibilities, depending on the geometry of the hall and the costs.
113
System design
Maintenance schedule
2 Maintenance schedule
Activity Interval
Renew air filter When the filter alarm is displayed,
at least annually
Comprehensively checking function; cleaning Annually by Hoval customer service
and possibly repairing the TopVent ® units
Table J1: Maintenance schedule
114
System design
Checklist for project discussions
Project Name
Address
Tel.
Fax
Date E-mail
Application Length
Type Width
Insulation Height
115
System design
Checklist for project discussions
Design data
Unit size
Control zones
■ Room temperature °C
Further information
116
Hoval quality.
You can count on us.
United Kingdom
Hoval Ltd.
Northgate, Newark
Responsibility Nottinghamshire
NG24 1JN
for energy and environment hoval.co.uk