VETROPACK STRAŽA
49231 Hum na Sutli
Proizvodni pogon
Z-208/01-19-19
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 2 od 21
VETROPACK STRAŽA
ODOBRIO POTPIS DATUM
EKOVENT-INFO
ODOBRIO POTPIS DATUM
Ispitivao i Pripremio:
Vladimir Vorkapić
Voditeljica osiguranja kvalitete:
Marija Bradić
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 3 od 21
SADRŽAJ
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 4 od 21
1. CILJ ISPITIVANJA
Potrebno je potvrditi prije početka ispitivanja i rada na ventilacijskim sustavima da sve radnje
obavljaju stručne osobe sa adekvatnim iskustvom i referencama u izvođenju traženih radova
na ventilacijskim sustavima te sukladno pravilniku da su akreditirani kao ispitni ISO 17025
laboratorij.
Potrebno je potvrditi prije početka ispitivanja da se ovlaštena firma i osobe koje vrše
ispitivanja ne nalaze u sukobu interesa tj. da mjeritelj nije sudjelovao pri projektiranju,
izvođenju ili prodaji ili instalaciji opreme.
Sve ispitne radnje obrađene unutar ovog zapisnika su tražene i odobrene od strane naručitelja.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 5 od 21
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 6 od 21
Slijedeći pojedinci su pripadnici Ispitne radne grupe koja je izvela sve navedene ispitne
radnje i pripremila ovaj izvještaj te je odgovorna za sve ovdje navedene radnje, korištenu
metodologiju i za prikazane rezultate.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 7 od 21
5. OPIS SUSTAVA
U sklopu ispitivanja ventilacije te određivanja ukupne bilance sustava u pogledu dobave i odsisa
zraka, izvođena je i vizualizacija strujanja zraka unutar proizvodne hale u svrhu određivanja
gradijenta strujanja zraka po svim pozicijama unutar hale tj. i unutar tople i hladne zone.
Izvedeno je tri tipa HOVAL-a i svi podaci uređaja nalaze se u tablici 1 ovog zapisnika.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 8 od 21
Tlačno-
1 HOVAL S31 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
2 HOVAL S32 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
3 HOVAL S33 LK-9/C 5000
recirkulacijom
Tlačno-
4 HOVAL S34 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
5 HOVAL S35 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
6 HOVAL S36 LK-9/C 5000
recirkulacijom
Tlačno-
7 HOVAL S41 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
8 HOVAL S42 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
9 HOVAL S43 LK-9/C 5000
recirkulacijom
Tlačno-
10 HOVAL S44 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
11 HOVAL S45 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
12 HOVAL S46 LK-9/C 5000
recirkulacijom
Tlačno-Odsisna s
13 HOVAL S51 LK-9/C 5000
recirkulacijom
Tlačno-
14 HOVAL S52 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
15 HOVAL S53 LKW-9/C 5000
rekuperacijom
Tlačno-Odsisna s
16 HOVAL S61 LK-9/C 5000
recirkulacijom
Tlačno-
17 HOVAL S62 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
18 HOVAL S63 LKW-9/C 5000
rekuperacijom
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 9 od 21
The TSI Prohood Modular Air Balancing Tool is ideal for HVAC testing and bal¬ancing and also for
industrial hygiene applications. The heart of the Prohood 731 is a revolutionary micromanometer that
easily detachs from the base for use with a wide variety of probes to measure diffuser flow rate, point
velocity, average velocity, pressure differential, temperature and humidity. Simplify your business with
this economical and comprehensive measurement solution.
Applications
• HVAC system testing, adjusting and balancing
• Building and system commissioning
• Energy efficiency studies
• Filter face velocity testing
• Clean room testing
• Industrial hygiene studies
• Regulatory compliance checks
• Fume hood and biological safety cabinet flow measurements with
optional BSC accessory
• New 16-point velocity matrix for fume hood face velocity, filter face
velocity, and irregular area velocity averages
Specifications
Air velocity range: 0,13 to 41 m/s
Accuracy: ±0,04 m/s
Volume range: 42 to 4250 m3/h (Capture hood)
Accuracy: ±3% of reading
Resolution: 1 m3/h
Differential pressure
-3735 to +3735 Pa
range:
Accuracy: 2% of reading
Resolution: 0,001 Pa to 10 Pa, 0,1 Pa to 100 Pa, 1 Pa to 3735 Pa
Absolute pressure
356 to 1016 mm Hg
range:
Accuracy: 2% of reading
Resolution: 1 mm Hg
Balometer - Micromanometer
Manufacturer and Type: Serial number: Internal mark:
TSI PROHOOD 731 PH7311646008 EV-I/A-01-04
Calibration Reference: Calibration Date:
C-001/004-53-19 09.07.2019.
Calibrated in accredited HRN EN ISO/IEC 17025:2007 calibration laboratory
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 10 od 21
They are designed to measure air velocity, temperature, humidity, CO and CO2. Calculations include
air flow, heat flow, turbulence, wet bulb and dew point temperature.
Applications
o HVAC commissioning and troubleshooting
o Clean room certification
o Testing and balancing
o Ventilation evaluations
o Thermal comfort studies
o IAQ investigations
o Process air flow testing
Temperature
Range 0 to 200°F (-18 to 93°C)
Accuracy ±0.5°F (±0.3°C)
Resolution 0.1°F (0.1°C)
Relative Humidity
Range 0 to 95% RH
Accuracy ±3% RH
Resolution 0.1% RH
Static/Differential Pressure
Range: -15 to +15 in. H2O (-28.0 to +28.0 mm Hg, -3735 to +3735 Pa)
Accuracy ±1% of reading ±0.005 in. H2O (±0.01 mm Hg, ±1 Pa)
Resolution 0.001 in. H2O (1 Pa, 0.01 mm Hg)
Barometric Pressure
Range 2.036 to 36.648 in. Hg (517.15 to 930.87 mm Hg)
Accuracy 2% of reading
Data Storage Capabilities
Range 26,500+ samples and 100 test Ids
Logging Interval 1 second to 1 hour
Time Constant User selectable
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 11 od 21
For the detection of the air flow and strength of air currents.
In many fields, such as mining or industry, it is very important to detect
even the smallest air flows, in order to quickly and reliably evaluate the
possible diffusion of dangerous substances. With the air flow test tubes, the
source, direction and speed of the air flow are visible immediately. The air
flow test tubes can be used until the "white smoke" has completely
disappeared. If the test is completed before all the smoke disappears, the
,,tube can be sealed again using the rubber cap provided.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 12 od 21
7. ISPITNE RADNJE
Ispitne radnje
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 13 od 21
Cilj:
Cilj ovog mjerenja je izmjeriti ukupne protoke zraka ventilatora HOVAL uređaj direktno protoka
zraka ili brzina strujanja zraka direktno na usisnim (usis svježeg zraka) ili tlačnim (odsis
otpadnog zraka) otvorima HOVAL-a te izvesti provjeru da li su ti izmjereni protoci u skladu sa
projektom i podacima datim od strane proizvođača ventilacijskih sustava.
Preduvjet ispitivanja:
• Provjeri da su svi ventilacijski sustavi koji su predmet mjerenja uključeni, i da su svi
elementi instalacije kao PPZ, RŽ, RKP i RVP otvoreni i ispravni.
• Provjeri sustave koji su predmet mjerenja da rade na radnim točkam na kojima se žele
ispitati protoci dobave/odsisa zraka.
Metodologija:
a) Korištena metodologija je u skladu sa HRN EN 12599-2013 i ISO 3966-2018.
b) Za mjerenje će se koristiti mjerna hauba tzv. Balometar ili mjerna horna, koja u
potpunosti prekriva distribucijske elemente bilo koje izvedbe.
c) Odaberi prikladnu veličinu mjernog otvora za prekrivanje istrujnog elementa tako da
otvor mjernog instrumenta u potpunosti prekrije istrujni kako dobavni tako i odsisni
element.
d) Odaberi zasebnu grupu i program u kojeg će se pohranjivati rezultati mjerenja.
e) Postavi mjerni uređaj, balometar ili hornu sa usisne ili tlačne strane istrujnog elementa i
izmjeri protok dobave/odsisa zraka u [m³/h].
f) Očitaj prikazan izmjereni protok zraka kroz istrujni element te ga memoriraj.
g) Izvedi ukupno ostvarenu količinu dobave/odsisa zraka zbrajanjem izmjerenih količina
zraka svakog distributivnog elementa
Kriterij prihvatljivosti:
• Ventilacijski sustavi moraju ostvarivati proizvođačke, projektirane protoke dobave i
odsisa zraka uz dozvoljeno odstupanje na osnovu proračuna mjerne nesigurnosti od
±10%.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 14 od 21
Korištena oprema:
• TSI Prohood, DPCalc 8710, 8375 ili 9555-P sa Pitot-Prandtl sondom ili matricom je
uređaj za mjerenje protoka zraka na istrujnim otvorima. Minimalna brzina strujanja zraka
koja se može mjeriti iznosi 0.15 m/s, dok je maksimalna brzina strujanja zraka 50 m/s uz
mjernu točnost od ±2%.
• TSI VelCalc sa Pitot-Prandtl sondom je uređaj za mjerenje protoka zraka kroz
ventilacijske kanale te mjeri istovremeno diferencijalni pad tlaka, temperaturu, relativnu
vlagu i dr. Minimalna brzina strujanja zraka koja se može mjeriti iznosi 0.01 m/s, dok je
maksimalna brzina strujanja zraka 50 m/s uz mjernu točnost od ±2%.
• Detaljan opis mjernih uređaja dat je u točci 6 ovog izvještaja.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 15 od 21
CAU jedinice imaju izvedena dva usisna otvora za usis svježeg zraka 340 x 650 mm, debljine
žaluzine 130 mm
Ostale jedinice imaju jedan usisni otvor 1113 x 710 mm s debljinom žaluzine 130 mm
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 16 od 21
Foto dokumentacija filtera u vidljivo zapunjenom stanju ali otpori na filterima u numeričkom smislu
ne pokazuju vrijednosti pri kojima bi se filtera trebali zamijeniti ali vizualno filteri su definitivno za
zamijenu
Desna slika pokazuje koliko se filteri rašire uslijed loše izrade i uslijed otpora zraka od zapunjenosti
filtera te praktično bolokiraju usisa zraka, usisno ušće blokirano cca 80-90%.
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 17 od 21
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 18 od 21
8. LISTA DODATAKA
Lista Nedostataka
2
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 19 od 21
Dodatak 1 - ZAKLJUČAK
Za Ekovent-Info
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 20 od 21
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 21 od 21
Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2