You are on page 1of 21

Objekt:

VETROPACK STRAŽA
49231 Hum na Sutli

Proizvodni pogon

ZAPISNIK O ISPITIVANJU PROTOKA ZRAKA 'HOVAL'


VENTILACIJSKO-KLIMATIZACIJSKIH SUSTAVA

Z-208/01-19-19
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 2 od 21

NASLOV: ZAPISNIK O ISPITIVANJU UČINKOVITOSTI VENTILACIJE

PREGLED I ODOBRENJE IZVJEŠTAJA

VETROPACK STRAŽA
ODOBRIO POTPIS DATUM

EKOVENT-INFO
ODOBRIO POTPIS DATUM

Ispitivao i Pripremio:
Vladimir Vorkapić
Voditeljica osiguranja kvalitete:
Marija Bradić

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 3 od 21

SADRŽAJ

1. CILJ ISPITIVANJA ...........................................................................................................................................4


2. KORIŠTENE NORME & DOKUMENTACIJA ................................................................................................5
3. DATUM IZVOĐENJA ISPITNIH I REGULACIJSKIH RADNJI ...................................................................6
4. ISPITNA RADNA GRUPA .................................................................................................................................6
5. OPIS SUSTAVA..................................................................................................................................................7
Tablica 1 – Tehnički podaci HOVAL-a ..................................................................................................................8
6. KORIŠTENA MJERNA OPREMA ...................................................................................................................9
7. ISPITNE RADNJE............................................................................................................................................ 12
7.1 ISPITIVANJE PROTOKA ZRAKA .............................................................................................................................. 13
Rezultati mjerenja protoka zraka prinudne ventilacije_19.07.2019. godine........................................................... 15
8. LISTA DODATAKA .............................................................................................................................................. 18
DODATAK 1 - ZAKLJUČAK ................................................................................................................................... 19
DODATAK 2 – POTVRDE UMJERAVANJA KORIŠTENE MJERNE OPREMA ............................................... 20
DODATAK 3 – OVLAŠTENJA, CERTIFIKATI I AKREDITACIJA FIRME I VALIDATORA .......................... 21

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 4 od 21

1. CILJ ISPITIVANJA

Cilj ispitivanja je izvršiti u dogovoru sa naručiteljem, slijedeće radnje:


• pregled i ispitivanje HOVAL ventilacijsko-klimatizacijskih sustava koji se koriste i za
ventilaciju i klimatizaciju proizvodnog prostora

Sve ispitne radnje izvedene su u skladu sa projektnom dokumentacijom te su dobiveni


rezultati uspoređeni sa projektnim - proizvođačkim vrijednostima ventilacijskih sustava.

Potrebno je potvrditi prije početka ispitivanja i rada na ventilacijskim sustavima da sve radnje
obavljaju stručne osobe sa adekvatnim iskustvom i referencama u izvođenju traženih radova
na ventilacijskim sustavima te sukladno pravilniku da su akreditirani kao ispitni ISO 17025
laboratorij.

Potrebno je potvrditi prije početka ispitivanja da je sva oprema s kojom će se ispitivanje


odvijati, umjerena u akreditiranom EN ISO/IEC 17025:2007 umjernom laboratoriju.

Potrebno je potvrditi prije početka ispitivanja da se ovlaštena firma i osobe koje vrše
ispitivanja ne nalaze u sukobu interesa tj. da mjeritelj nije sudjelovao pri projektiranju,
izvođenju ili prodaji ili instalaciji opreme.

Potrebno je savjetovati i pomoći krajnjeg korisnika u pogledu pred ispitnih radnji.

Potrebno je osigurati sažetak svih rezultata ispitivanja te izvesti zaključke i preporuke u


pogledu eventualno pronađenih nedostataka.

Potrebno je izvesti zaključke da li HVAC sustavi te izvedena instalacija udovoljavaju


projektnim zahtjevima te zahtjevima normi, pravilnika i smjernica.

Sve ispitne radnje obrađene unutar ovog zapisnika su tražene i odobrene od strane naručitelja.

Ispitne radnje uključuju slijedeća ispitivanja:


- Ispitivanje protoka zraka

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 5 od 21

2. KORIŠTENE NORME & DOKUMENTACIJA

Popis korištenih normi korištene ocjenjivanju, metodologiji i kvalifikaciji validacijskih


radnji:

- Pravilnik o t/n za klimatizacijske i ventilacijske sustave (Sl.list br. 38/89)


- Tehnički propisi o sustavima ventilacije, djelomične klimatizacije i klimatizacije zgrada
(NN 03/07)
- EN 12599-2013: Ventilacija u zgradama: Ispitni postupci i mjerne metode za primopredaju
izvedenih sustava ventilacije i klimatizacije
- ANSI/ASHRAE 111-2008 “Practices for Measurament, Testing, and Adjusting, and
Balancing of Heating, Ventilation, Air-Conditioning, and Refrigeration Systems”.
- EN 16211:2015: Ventilacija u zgradama – Mjerenje protoka zraka na licu mjesta – Metode
- ISO 3966:2008 Measurement of fluid flow in closed conduits – Velocity area method using
Pitot Static tubes
- CR 1752-2004: Ventilacija u zgradama – Projektni kriteriji za unutrašnjost
- EN 15251-2008: Ulazni mikroklimatski parametri za projektiranje i ocjenjivenje energijskih
značajka zgrada koje se odnose na kvalitetu zraka, toplinsku lagodnost, osvjetljenje i akustiku
- EN 12792: 2004 – Ventilacija u zgradama, simboli, nazivlje i grafički simboli,
- ISO 4225:1994 – Air Quality – General Aspects – Vocabulary
- HRN ISO 7730-2008 – Ergonomics of the thermal environment – Analytical determination and
interpretation of thermal comfort using calculation PMV and PPD indices and local thermal
comfort criteria.
- Department of Environment and Conservation – A Guideline for managing the imapacts of
dust and associated contaminants from land development sites remediation and other related
activities.
- WHO Air Quality Guidelines for Particulate Matter, Ozone, Nitrogen dioxide and sulfur
dioxide – year 2005 – Summary of Risk Assesment

Korištena projektna dokumentacija:

• Proizvodni pogon kota '0' m – prozori, kupole


• Proizvodni pogon kota '-4' m
• Instalacija na koti '-4' m, dopune 03.2018

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 6 od 21

3. DATUM IZVOĐENJA ISPITNIH I REGULACIJSKIH RADNJI

• Sva ispitne radnje izvedene su dana 19.07.2019. godine.

4. ISPITNA RADNA GRUPA

Slijedeći pojedinci su pripadnici Ispitne radne grupe koja je izvela sve navedene ispitne
radnje i pripremila ovaj izvještaj te je odgovorna za sve ovdje navedene radnje, korištenu
metodologiju i za prikazane rezultate.

Ime i Prezime Pozicija Inicijali


Voditelj ispitnog
Vladimir Vorkapić V.V.
laboratorija
Voditelj osiguranja
Marija Bradić M.B.
kvalitete

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 7 od 21

5. OPIS SUSTAVA

Na osnovu dogovora s korisnikom i nakon obavljenog čišćenja i servisa HOVAL ventilacijsko-


klimatizacijskih krovnih sustava, izveden je pregled te ispitivanje protoka zraka instalacija u
objektu, proizvodnom pogonu firme VATROPACK STRAŽA, Hum na Sutli. Proizvodni pogon
izveden je u prizemlju objekta na koti '0', koji se sastoji od tri peći oznaka W61, W62 i W63 te
proizvodnih linija označenih kao Linija 611, 612, 613, 621, 622, 623631, 632, 633, 634 i 635.

U sklopu ispitivanja ventilacije te određivanja ukupne bilance sustava u pogledu dobave i odsisa
zraka, izvođena je i vizualizacija strujanja zraka unutar proizvodne hale u svrhu određivanja
gradijenta strujanja zraka po svim pozicijama unutar hale tj. i unutar tople i hladne zone.

Izvedeno je tri tipa HOVAL-a i svi podaci uređaja nalaze se u tablici 1 ovog zapisnika.

Ispitivanja su provedena na maksimalnim režimima rada ventilatora HOVAL-a te kod otvorenih


žaluzina svježeg zraka 100%, rad sa svježim zrakom.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 8 od 21

Tablica 1 – Tehnički podaci HOVAL-a

Red. Porizvođač Inventarna Model Izvedba Nom.količ/otpor


br. oznaka [m3/h] / [Pa]

Tlačno-
1 HOVAL S31 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
2 HOVAL S32 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
3 HOVAL S33 LK-9/C 5000
recirkulacijom
Tlačno-
4 HOVAL S34 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
5 HOVAL S35 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
6 HOVAL S36 LK-9/C 5000
recirkulacijom
Tlačno-
7 HOVAL S41 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
8 HOVAL S42 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
9 HOVAL S43 LK-9/C 5000
recirkulacijom
Tlačno-
10 HOVAL S44 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-
11 HOVAL S45 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
12 HOVAL S46 LK-9/C 5000
recirkulacijom
Tlačno-Odsisna s
13 HOVAL S51 LK-9/C 5000
recirkulacijom
Tlačno-
14 HOVAL S52 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
15 HOVAL S53 LKW-9/C 5000
rekuperacijom
Tlačno-Odsisna s
16 HOVAL S61 LK-9/C 5000
recirkulacijom
Tlačno-
17 HOVAL S62 CAU-9/C 6800 / 46 Pa
Recirkulacijski
Tlačno-Odsisna s
18 HOVAL S63 LKW-9/C 5000
rekuperacijom

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 9 od 21

6. KORIŠTENA MJERNA OPREMA

01) TSI PROHOOD 731

The TSI Prohood Modular Air Balancing Tool is ideal for HVAC testing and bal¬ancing and also for
industrial hygiene applications. The heart of the Prohood 731 is a revolutionary micromanometer that
easily detachs from the base for use with a wide variety of probes to measure diffuser flow rate, point
velocity, average velocity, pressure differential, temperature and humidity. Simplify your business with
this economical and comprehensive measurement solution.
Applications
• HVAC system testing, adjusting and balancing
• Building and system commissioning
• Energy efficiency studies
• Filter face velocity testing
• Clean room testing
• Industrial hygiene studies
• Regulatory compliance checks
• Fume hood and biological safety cabinet flow measurements with
optional BSC accessory
• New 16-point velocity matrix for fume hood face velocity, filter face
velocity, and irregular area velocity averages

Specifications
Air velocity range: 0,13 to 41 m/s
Accuracy: ±0,04 m/s
Volume range: 42 to 4250 m3/h (Capture hood)
Accuracy: ±3% of reading
Resolution: 1 m3/h
Differential pressure
-3735 to +3735 Pa
range:
Accuracy: 2% of reading
Resolution: 0,001 Pa to 10 Pa, 0,1 Pa to 100 Pa, 1 Pa to 3735 Pa
Absolute pressure
356 to 1016 mm Hg
range:
Accuracy: 2% of reading
Resolution: 1 mm Hg

Balometer - Micromanometer
Manufacturer and Type: Serial number: Internal mark:
TSI PROHOOD 731 PH7311646008 EV-I/A-01-04
Calibration Reference: Calibration Date:
C-001/004-53-19 09.07.2019.
Calibrated in accredited HRN EN ISO/IEC 17025:2007 calibration laboratory

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 10 od 21

02) TSI VelociCalc model: 9555-P, Multifunction Ventilation Meter

They are designed to measure air velocity, temperature, humidity, CO and CO2. Calculations include
air flow, heat flow, turbulence, wet bulb and dew point temperature.

Applications
o HVAC commissioning and troubleshooting
o Clean room certification
o Testing and balancing
o Ventilation evaluations
o Thermal comfort studies
o IAQ investigations
o Process air flow testing

Velocity (TA Probe Models 960 and 962)


Range 0 to 9,999 ft/min (0 to 50 m/s)
Accuracy ±3% of reading or ±3 ft/min (±0.015 m/s), whichever
is greater
Resolution 1 ft/min (0.01 m/s)

Velocity (Pitot Tube for Meter Model 9555-A)


Range 250 to 15,500 ft/min (1.27 to 78.7 m/s)
Accuracy ±1.5% at 2,000 ft/min (10.16 m/s)
Resolution 1 ft/min (0.01 m/s)

Temperature
Range 0 to 200°F (-18 to 93°C)
Accuracy ±0.5°F (±0.3°C)
Resolution 0.1°F (0.1°C)

Relative Humidity
Range 0 to 95% RH
Accuracy ±3% RH
Resolution 0.1% RH

Static/Differential Pressure
Range: -15 to +15 in. H2O (-28.0 to +28.0 mm Hg, -3735 to +3735 Pa)
Accuracy ±1% of reading ±0.005 in. H2O (±0.01 mm Hg, ±1 Pa)
Resolution 0.001 in. H2O (1 Pa, 0.01 mm Hg)
Barometric Pressure
Range 2.036 to 36.648 in. Hg (517.15 to 930.87 mm Hg)
Accuracy 2% of reading
Data Storage Capabilities
Range 26,500+ samples and 100 test Ids
Logging Interval 1 second to 1 hour
Time Constant User selectable

Micromanometer, multi measuring device


Manufacturer and Type: Serial number: Internal mark:
TSI VelociCalc 9555-P 9555P0945010 EV-I/A-01-05
Calibration Reference: Calibration Date:
C-001/002-53-19 09.07.2019.
Calibrated in accredited HRN EN ISO/IEC 17025:2007 calibration laboratory

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 11 od 21

03) DRAGER Air Flow Tester tubes

For the detection of the air flow and strength of air currents.
In many fields, such as mining or industry, it is very important to detect
even the smallest air flows, in order to quickly and reliably evaluate the
possible diffusion of dangerous substances. With the air flow test tubes, the
source, direction and speed of the air flow are visible immediately. The air
flow test tubes can be used until the "white smoke" has completely
disappeared. If the test is completed before all the smoke disappears, the
,,tube can be sealed again using the rubber cap provided.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 12 od 21

7. ISPITNE RADNJE

Ispitne radnje

Naziv ispitivanja Poglavlje

Ispitivanje protoka zraka 7.1

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 13 od 21

7.1 Ispitivanje protoka zraka

Cilj:
Cilj ovog mjerenja je izmjeriti ukupne protoke zraka ventilatora HOVAL uređaj direktno protoka
zraka ili brzina strujanja zraka direktno na usisnim (usis svježeg zraka) ili tlačnim (odsis
otpadnog zraka) otvorima HOVAL-a te izvesti provjeru da li su ti izmjereni protoci u skladu sa
projektom i podacima datim od strane proizvođača ventilacijskih sustava.
Preduvjet ispitivanja:
• Provjeri da su svi ventilacijski sustavi koji su predmet mjerenja uključeni, i da su svi
elementi instalacije kao PPZ, RŽ, RKP i RVP otvoreni i ispravni.
• Provjeri sustave koji su predmet mjerenja da rade na radnim točkam na kojima se žele
ispitati protoci dobave/odsisa zraka.
Metodologija:
a) Korištena metodologija je u skladu sa HRN EN 12599-2013 i ISO 3966-2018.
b) Za mjerenje će se koristiti mjerna hauba tzv. Balometar ili mjerna horna, koja u
potpunosti prekriva distribucijske elemente bilo koje izvedbe.
c) Odaberi prikladnu veličinu mjernog otvora za prekrivanje istrujnog elementa tako da
otvor mjernog instrumenta u potpunosti prekrije istrujni kako dobavni tako i odsisni
element.
d) Odaberi zasebnu grupu i program u kojeg će se pohranjivati rezultati mjerenja.
e) Postavi mjerni uređaj, balometar ili hornu sa usisne ili tlačne strane istrujnog elementa i
izmjeri protok dobave/odsisa zraka u [m³/h].
f) Očitaj prikazan izmjereni protok zraka kroz istrujni element te ga memoriraj.
g) Izvedi ukupno ostvarenu količinu dobave/odsisa zraka zbrajanjem izmjerenih količina
zraka svakog distributivnog elementa

Kriterij prihvatljivosti:
• Ventilacijski sustavi moraju ostvarivati proizvođačke, projektirane protoke dobave i
odsisa zraka uz dozvoljeno odstupanje na osnovu proračuna mjerne nesigurnosti od
±10%.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 14 od 21

Korištena oprema:
• TSI Prohood, DPCalc 8710, 8375 ili 9555-P sa Pitot-Prandtl sondom ili matricom je
uređaj za mjerenje protoka zraka na istrujnim otvorima. Minimalna brzina strujanja zraka
koja se može mjeriti iznosi 0.15 m/s, dok je maksimalna brzina strujanja zraka 50 m/s uz
mjernu točnost od ±2%.
• TSI VelCalc sa Pitot-Prandtl sondom je uređaj za mjerenje protoka zraka kroz
ventilacijske kanale te mjeri istovremeno diferencijalni pad tlaka, temperaturu, relativnu
vlagu i dr. Minimalna brzina strujanja zraka koja se može mjeriti iznosi 0.01 m/s, dok je
maksimalna brzina strujanja zraka 50 m/s uz mjernu točnost od ±2%.
• Detaljan opis mjernih uređaja dat je u točci 6 ovog izvještaja.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 15 od 21

Rezultati mjerenja protoka zraka prinudne ventilacije_19.07.2019. godine

Režim rada ventilatora: 100%, 100% svježi zrak

CAU jedinice imaju izvedena dva usisna otvora za usis svježeg zraka 340 x 650 mm, debljine
žaluzine 130 mm
Ostale jedinice imaju jedan usisni otvor 1113 x 710 mm s debljinom žaluzine 130 mm

Red HOVAL-oznaka_ Izmjereni protok Izmjereni statički Primjedba


Br. int.oznaka s BMS-a zraka (m3/h) tlak svježi zrak (Pa)
Svježi Otpadni
Žaluzine Filter
zrak zrak
1 TopVent, 2100
- 70 -
CAU-9/C _31 1900
2 TopVent, 1300
- 70 -
CAU-9/C _32 1950
3 RoofVent, BMS prikaz pokazuje da je
LK-9/C_33 žaluzina na otpadnom zraku
250 7100 55 55
otvorena a u stvarnosti je
zatvorena
4 RoofVent,
6350 4460 35 95
LK-9/C_36
5 TopVent, 2000
CAU-9/C _35 - 70 -
1800
6 TopVent, 1900
- 70 -
CAU-9/C _34 1900
7 TopVent, 2400
CAU-9/C _41 - 70 -
2000
8 TopVent, 2050
- 70 -
CAU-9/C _42 1850
9 RoofVent,
6000 4145 35 62
LK-9/C_43
10 RoofVent, Zatvorene sve žaluzine a BMS
LK-9/C_46 - - - - prikazuje 'lažno' da su žaluzine
otvorene
11 TopVent, 2200
- 70 -
CAU-9/C _45 1800
12 TopVent, 2030
- 70 -
CAU-9/C _44 1900
13 RoofVent, Isključen uređaj zbog
LK-9/C_51 6450 0 76 92 zaprljanosti filtera i nedostaka
filtera da ga se zamijeni
14 TopVent 1900
- 70 -
CAU-9/C _52 1800
15 RoofVent, Raspadnuta izolacija
5650 2705 51 56
LKW-9/C_53

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 16 od 21

16 RoofVent, Filteri onečišćeni, vidljivo


LKW-9/C_63 6020 3120 55 81 prljavi te upitna otvorenost
žaluzine
17 TopVent,
2000
CAU-9/C _62 - 70 -
1790
18 RoofVent, Filteri onečišćeni, vidljivo
LK-9/C_61 6988 6897 25 - prljavi

Foto dokumentacija filtera u vidljivo zapunjenom stanju ali otpori na filterima u numeričkom smislu
ne pokazuju vrijednosti pri kojima bi se filtera trebali zamijeniti ali vizualno filteri su definitivno za
zamijenu

Desna slika pokazuje koliko se filteri rašire uslijed loše izrade i uslijed otpora zraka od zapunjenosti
filtera te praktično bolokiraju usisa zraka, usisno ušće blokirano cca 80-90%.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 17 od 21

Zaprljanost vanjske žaluzine

Gotovo zatvorena žaluzina a na BMS pokazuje 100% otvorenost

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 18 od 21

8. LISTA DODATAKA

Broj Ref Inicijali da se


Sadržaj Dokumenta Dodatka
Dodatka Sekcija potvrdi dodatak
Zaključak
1

Lista Nedostataka
2

Potvrde umjeravanja korištene mjerne


3
opreme
Ovlaštenja, certifikati i akreditacija
4
firme i ispitivača

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 19 od 21

Dodatak 1 - ZAKLJUČAK

Na temelju pregleda izvedenih instalacija te provedenog ispitivanja funkcionalnosti ventilacijsko-


klimatizacijskih sustava HOVAL, unutar proizvodne hale firme VETROPACK STRAŽA, Hum na
Sutli, doneseni su slijedeći zaključci:

• s obzirom na vizualnu zapunjenost filtera izmjereni protoci zraka ukazuju da HOVAL-i u


principu ostvaruju protoke zraka koje su blizu projektiranim vrijendostima
• dvije jedinice LK-9/C_33, zatvorena žalulzina na otpadnom zraku i LK-9/C_46 imala zatvorene obje
žaluzine dok su ventilatori bilu u funkciji na 100%, prema prikazu na BMS-u žaluzine su prikazane
kao otvorene što je lažan prikaz i dovodi u zabludu korisnika te dovodi do mogućnosti do
pregrijavanja i pregaranja motora ventilatora.
• trebalo bi napomenuti da diferencijalni presostati nisu u stanju prikazati stvarnu zapunjenost filtera te
čak ni sama mjerenja razlike tlaka filtera ne ukazuju da su filter zapunjeni što u stvarnosti kada ih se
pogleda vizualno, oni su u poprilično zapunjenom stanju te bi trebalo uvesti češće zamijene filtera
koje su bazirane na vremenskom okviru kao npr. svaka 3 mjeseca tj. u redovitom vremenskom
intervalu i pri tome nakon vizualnog pregleda filtera tijekom zamijena mogu se raditi korekcije oko
tog vremenskog intervala koji se može ili produljiti ili prema potrebi skratiti.

Za Ekovent-Info

Vladimir Vorkapić, dipl.ing.stroj.

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 20 od 21

Dodatak 2 – POTVRDE UMJERAVANJA KORIŠTENE MJERNE OPREMA

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2
Ekovent-Info d.o.o.
Br. izvještaja:
Authorised HVAC & Clean
room room professionals & ISO Z-208/01-19-19
17025 accredited testing
& calibration laboratory Strana 21 od 21

Dodatak 3 – OVLAŠTENJA, CERTIFIKATI I AKREDITACIJA FIRME I VALIDATORA

Ovlaštenje i rješenje Zavoda za unapređivanje zaštite na radu Republike Hrvatske UP/I-115-01/15-


01/37 od 08. lipnja 2015. godine za ispitivanje radne opreme te fizikalnih i kemijskih parametara
radne okoline.
Rješenje ovlaštenog inženjera strojarstva SEGP 1553
Akreditacijski certifikat HRN EN ISO/IEC 17025 kao ispitni laboratorij

Copyright©EkoVent-Info d.o.o.
Formular F 5,10/1-2