You are on page 1of 1

Provide double roof joist

trimming around new roof lights

Party wall line


1

B1 (2nr.)

B1
C1

2
B1 (2nr.)
3

B1 (2nr.)
C1 C1

Allow for pairs of new steel


beams to accommodate the
4 thickness of all external walls.

A B C D E F

The extent of the new wall construction


Legend atop existing walls/lintels/foundations
below. May need to use lightweight
New solid or cavity? load masonry blocks pending site
bearing masonry wall investigations of the existing structure.

Lightweight non-structural partitions


supported on existing floor (allow to
double up existing joists) Proposed First Floor alterations
C1 = New 152x152x37UC (S355)
column built into walls

B1 = New 203x133x30UB (S355)


beams with concrete padstones
where supported on masonry walls

New 200x50 C24 timber floor joists


@ 400 c/c

213 Long Lane Proposed First Floor Structural Alterations SP EP 05.04.24 NTS
Bexley Heath
DA7 5JB
8156-SK-002 P01