COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1

1C1 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 112.7 -2.3 2.0 106.1 4.7 -4.2
2 80.0 -1.6 1.5 75.3 3.3 -3.0
3 114.0 -2.2 2.2 107.3 4.6 -4.4
4 78.8 -1.5 1.2 72.1 3.2 -2.5
5 94.7 1.1 1.8 89.0 1.1 -3.6
6 97.4 -5.0 1.7 91.7 6.9 -3.5
7 97.5 -2.0 4.9 91.8 4.0 -6.6
8 94.5 -1.9 -1.5 88.9 4.0 -0.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 112.7 - 112.7
M1 (kN.m) 4.7 1.3 8.4 225
M2 (kN.m) -4.2 -1.3 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.089 Le1/b1 = 11.7 < 15.0 225
Beta = 0.89 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 3.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.07 N/mm2
Links = Y10-175

2C1 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.4 -6.1 5.6 9.3 3.3 -3.0
2 10.3 -4.3 3.9 6.6 2.3 -2.1
3 14.2 -6.0 5.8 9.1 3.1 -3.0
4 11.8 -4.2 3.5 6.7 2.4 -2.0
5 12.2 -5.2 4.7 7.8 2.6 -2.6
6 12.4 -5.3 4.7 8.0 3.0 -2.6
7 12.4 -5.2 4.8 8.0 2.8 -2.8
8 12.2 -5.2 4.7 7.8 2.8 -2.3
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 14.2 - 14.2
M1 (kN.m) -6.0 -0.2 -11.7 225
M2 (kN.m) 5.8 0.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.9 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.1 / 2.9 kN As (Required): %0.64 324.35 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.08 / 0.07 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2

1C2 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 199.2 -3.7 0.6 192.6 7.7 -1.2
2 141.2 -2.6 0.4 136.5 5.4 -0.8
3 181.8 -3.7 1.0 175.2 7.7 -2.0
4 154.4 -2.4 0.0 147.8 4.9 0.0
5 167.7 -0.1 0.5 162.0 3.6 -1.0
6 171.2 -6.2 0.5 165.5 9.5 -1.0
7 170.0 -3.1 3.8 164.3 6.5 -4.3
8 169.0 -3.2 -2.8 163.3 6.5 2.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 199.2 - 199.2
M1 (kN.m) 7.7 2.2 9.6 225
M2 (kN.m) -1.2 -2.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.157 Le1/b1 = 11.7 < 15.0 225
Beta = 0.82 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.83 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.00 N/mm2
Links = Y10-175

2C2 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 17.3 -9.4 1.4 12.2 3.7 -0.4
2 12.4 -6.7 1.0 8.7 2.6 -0.3
3 16.2 -9.5 2.4 11.1 3.7 -1.0
4 14.9 -6.0 -0.1 9.8 2.4 0.3
5 14.7 -7.8 1.2 10.3 2.9 -0.3
6 15.0 -8.2 1.2 10.6 3.4 -0.3
7 14.8 -8.0 1.5 10.4 3.1 -0.7
8 14.9 -8.0 0.8 10.5 3.1 0.1
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 16.2 - 16.2
M1 (kN.m) -9.5 -0.2 -11.9 225
M2 (kN.m) 2.4 0.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 8.9 < 15.0 225
Beta = 0.98 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.4 / 1.1 kN As (Required): %0.64 325.96 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.11 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3

1C3 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 121.2 1.5 -0.4 114.6 -2.8 0.8
2 86.1 1.1 -0.3 81.3 -2.0 0.6
3 115.8 1.6 -0.3 109.2 -2.9 0.8
4 91.2 0.9 -0.3 84.6 -1.7 0.6
5 102.1 4.5 -0.3 96.4 -5.5 0.7
6 104.5 -1.9 -0.3 98.8 0.8 0.7
7 100.4 1.3 2.9 94.8 -2.4 -2.5
8 106.2 1.3 -3.6 100.5 -2.3 3.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 121.2 - 121.2
M1 (kN.m) -2.8 -1.4 -4.0 225
M2 (kN.m) 0.8 1.4 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.096 Le1/b1 = 11.6 < 15.0 225
Beta = 0.89 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.83 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.01 N/mm2
Links = Y10-175

2C3 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.4 3.8 -1.4 6.3 -2.4 1.1
2 8.1 2.7 -1.0 4.5 -1.7 0.8
3 10.6 3.9 -1.3 5.5 -2.5 0.9
4 10.4 2.4 -1.0 5.3 -1.5 0.9
5 9.7 3.6 -1.2 5.3 -2.5 0.9
6 9.9 2.8 -1.2 5.5 -1.7 0.9
7 9.6 3.2 -0.9 5.2 -2.0 0.6
8 9.9 3.2 -1.4 5.6 -2.1 1.2
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 10.6 - 10.6
M1 (kN.m) 3.9 0.1 5.2 225
M2 (kN.m) -1.3 -0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 8.5 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 0.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.02 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4

1C6 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 170.3 1.2 2.5 163.6 -2.4 -5.1
2 120.8 0.9 1.8 116.0 -1.7 -3.6
3 139.0 1.4 1.5 132.4 -2.7 -3.0
4 149.4 0.7 2.6 142.8 -1.3 -5.3
5 144.8 4.2 2.2 139.2 -5.2 -4.3
6 145.0 -2.1 2.1 139.3 1.1 -4.3
7 146.6 1.0 5.4 141.0 -2.0 -7.3
8 143.2 1.1 -1.1 137.5 -2.1 -1.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 170.3 - 170.3
M1 (kN.m) -2.4 -1.9 0.0 225
M2 (kN.m) -5.1 -1.9 -7.1
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 11.6 < 15.0 225
Beta = 0.84 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.7 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

2C6 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.3 3.5 6.5 9.2 -2.3 -3.3
2 10.2 2.5 4.6 6.6 -1.6 -2.4
3 12.7 3.9 3.9 7.6 -2.5 -2.2
4 13.3 2.0 6.8 8.2 -1.4 -3.3
5 12.2 3.4 5.5 7.8 -2.4 -2.8
6 12.3 2.6 5.5 8.0 -1.6 -2.8
7 12.4 3.0 5.6 8.1 -1.9 -3.1
8 12.1 3.0 5.4 7.7 -2.0 -2.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 14.3 - 14.3
M1 (kN.m) 3.5 0.2 0.0 225
M2 (kN.m) 6.5 0.2 10.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 3.4 kN As (Required): %0.53 266.26 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.08 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5

1C7 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 207.4 4.1 -0.7 200.7 -8.0 1.5
2 146.7 2.9 -0.5 141.9 -5.7 1.1
3 197.8 4.1 -0.9 191.2 -8.0 2.0
4 149.4 2.6 -0.3 142.8 -5.2 0.6
5 177.3 6.6 -0.6 171.6 -9.7 1.3
6 174.7 0.4 -0.6 169.1 -3.9 1.3
7 177.2 3.5 2.7 171.5 -6.8 -2.0
8 174.8 3.5 -4.0 169.1 -6.8 4.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 207.4 - 207.4
M1 (kN.m) -8.0 -2.3 -9.9 225
M2 (kN.m) 1.5 2.3 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.164 Le1/b1 = 11.7 < 15.0 225
Beta = 0.81 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.92 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.01 N/mm2
Links = Y10-175

2C7 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.9 9.8 -2.4 11.8 -4.0 1.7
2 12.1 6.9 -1.7 8.4 -2.9 1.2
3 15.7 9.7 -3.0 10.6 -4.0 2.0
4 14.7 6.4 -1.0 9.6 -2.8 0.9
5 14.5 8.4 -2.1 10.2 -3.7 1.5
6 14.4 8.1 -2.1 10.0 -3.1 1.5
7 14.6 8.3 -1.6 10.2 -3.4 1.0
8 14.3 8.3 -2.5 9.9 -3.4 2.0
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 15.7 - 15.7
M1 (kN.m) 9.7 0.2 12.7 225
M2 (kN.m) -3.0 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.9 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.6 / 1.7 kN As (Required): %0.70 355.14 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.11 / 0.04 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6

1C8 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 162.3 -6.0 0.0 155.6 12.4 0.1
2 114.8 -4.2 0.0 110.1 8.7 0.1
3 147.0 -6.0 0.1 140.3 12.4 -0.2
4 125.9 -3.9 -0.2 119.2 7.9 0.4
5 137.1 -2.1 0.0 131.4 7.7 0.1
6 138.4 -8.1 0.0 132.7 13.3 0.1
7 138.9 -5.1 3.3 133.2 10.5 -3.2
8 136.6 -5.1 -3.4 131.0 10.5 3.4
Critical Combination:6 - (G+Q-Nx)
Min Design
N (kN) 138.4 - 138.4
M1 (kN.m) 13.3 1.6 14.6 225
M2 (kN.m) 0.1 1.6 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.109 Le1/b1 = 11.8 < 15.0 225
Beta = 0.87 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.5 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.84 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.13 / 0.00 N/mm2
Links = Y10-175

2C8 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.0 -15.5 -0.5 9.9 6.9 0.6
2 10.7 -11.0 -0.3 7.1 4.9 0.4
3 15.1 -15.5 -0.1 9.9 6.9 0.4
4 12.2 -10.1 -0.7 7.1 4.7 0.6
5 12.9 -13.2 -0.4 8.5 5.7 0.6
6 12.9 -13.1 -0.4 8.5 6.1 0.5
7 12.9 -13.2 0.1 8.5 5.9 0.0
8 12.9 -13.1 -0.9 8.5 5.9 1.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 15.0 - 15.0
M1 (kN.m) -15.5 -0.2 -16.2 225
M2 (kN.m) 0.6 0.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 9.0 < 15.0 225
Beta = 0.99 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.5 / 0.6 kN As (Required): %0.95 479.80 mm2 4Y16
vc'(1/2)= 0.78 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.18 / 0.02 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7

1C9 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 103.4 0.9 -0.5 96.7 -1.5 1.2
2 73.5 0.6 -0.4 68.8 -1.0 0.9
3 98.5 1.0 -0.5 91.8 -1.7 1.2
4 79.6 0.5 -0.4 73.0 -0.8 0.8
5 87.3 3.9 -0.4 81.7 -4.3 1.0
6 89.1 -2.4 -0.5 83.4 1.9 1.0
7 85.0 0.8 2.8 79.3 -1.3 -2.1
8 91.4 0.7 -3.8 85.7 -1.2 4.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 103.4 - 103.4
M1 (kN.m) -1.5 -1.2 -2.6 225
M2 (kN.m) 1.2 1.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.082 Le1/b1 = 11.6 < 15.0 225
Beta = 0.90 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.05 N/mm2
Links = Y10-175

2C9 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.8 1.8 -2.3 10.7 -1.1 2.4
2 11.2 1.3 -1.6 7.6 -0.8 1.7
3 14.7 2.1 -2.2 9.6 -1.2 2.1
4 13.6 0.9 -1.6 8.5 -0.6 1.9
5 13.4 1.9 -1.9 9.0 -1.3 2.0
6 13.5 1.2 -2.0 9.2 -0.5 2.1
7 13.3 1.6 -1.8 8.9 -0.9 1.8
8 13.7 1.5 -2.1 9.3 -0.9 2.3
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 14.7 - 14.7
M1 (kN.m) 2.1 0.2 0.0 225
M2 (kN.m) -2.2 -0.2 -4.2
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.1 / 1.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.04 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8

1C10 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 269.7 3.3 -1.2 263.1 -6.4 2.6
2 191.1 2.3 -0.9 186.4 -4.5 1.8
3 234.8 3.5 -0.7 228.1 -6.7 1.5
4 218.4 1.9 -1.3 211.8 -3.8 2.7
5 227.9 6.0 -1.0 222.3 -8.5 2.2
6 230.7 -0.4 -1.0 225.0 -2.2 2.2
7 231.8 2.8 2.3 226.1 -5.4 -1.1
8 226.8 2.8 -4.4 221.2 -5.4 5.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 269.7 - 269.7
M1 (kN.m) -6.4 -3.0 -8.7 225
M2 (kN.m) 2.6 3.0 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.213 Le1/b1 = 11.6 < 15.0 225
Beta = 0.75 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y10-175

2C10 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.7 8.4 -3.8 8.6 -4.6 2.7
2 9.9 6.0 -2.7 6.2 -3.3 1.9
3 12.1 8.9 -2.4 7.0 -4.9 1.8
4 13.4 5.0 -3.9 8.3 -2.8 2.7
5 11.7 7.6 -3.2 7.3 -4.3 2.2
6 11.9 6.7 -3.2 7.6 -3.5 2.3
7 11.9 7.2 -2.8 7.6 -3.9 1.9
8 11.7 7.2 -3.6 7.4 -3.9 2.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 13.7 - 13.7
M1 (kN.m) 8.4 0.2 12.2 225
M2 (kN.m) -3.8 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.6 / 2.2 kN As (Required): %0.68 343.04 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.11 / 0.05 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9

1C11 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 171.1 0.2 1.4 164.5 -0.2 -2.7
2 121.5 0.1 1.0 116.7 -0.2 -1.9
3 137.0 0.1 1.0 130.4 0.1 -1.8
4 153.4 0.3 1.4 146.8 -0.4 -2.8
5 144.8 3.4 1.2 139.1 -3.3 -2.3
6 146.7 -3.0 1.2 141.0 2.9 -2.3
7 144.0 0.2 4.6 138.3 -0.2 -5.6
8 147.5 0.2 -2.1 141.8 -0.2 0.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 171.1 - 171.1
M1 (kN.m) -0.2 -1.9 0.0 225
M2 (kN.m) -2.7 -1.9 -4.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 11.6 < 15.0 225
Beta = 0.84 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.06 N/mm2
Links = Y10-175

2C11 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 19.4 0.3 4.0 14.3 -0.3 -2.6
2 13.8 0.2 2.8 10.2 -0.2 -1.8
3 17.6 -0.2 2.6 12.5 0.0 -1.8
4 16.8 0.6 4.0 11.7 -0.3 -2.5
5 16.5 0.6 3.4 12.1 -0.7 -2.2
6 16.6 -0.2 3.4 12.3 0.2 -2.2
7 16.5 0.2 3.7 12.1 -0.2 -2.6
8 16.6 0.2 3.1 12.3 -0.2 -1.8
Critical Combination:4 - ((G+Q)P2 *F)
Min Design
N (kN) 16.8 - 16.8
M1 (kN.m) 0.6 0.2 0.0 225
M2 (kN.m) 4.0 0.2 4.6
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 8.6 < 15.0 225
Beta = 0.98 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 2.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.05 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10

1C12 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 164.6 -0.9 2.5 158.0 1.9 -5.0
2 116.8 -0.6 1.8 112.0 1.3 -3.5
3 126.0 -0.4 1.7 119.3 1.0 -3.3
4 153.1 -1.0 2.4 146.4 2.1 -4.8
5 140.9 2.4 2.1 135.2 -1.5 -4.2
6 139.4 -3.9 2.1 133.7 4.7 -4.2
7 142.0 -0.8 5.4 136.3 1.6 -7.3
8 138.3 -0.7 -1.1 132.6 1.6 -1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 164.6 - 164.6
M1 (kN.m) 1.9 1.9 0.0 225
M2 (kN.m) -5.0 -1.9 -6.5
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.130 Le1/b1 = 11.6 < 15.0 225
Beta = 0.85 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y10-175

2C12 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.9 -2.7 6.4 9.8 1.9 -3.1
2 10.7 -1.9 4.5 7.0 1.3 -2.2
3 12.8 -1.5 4.3 7.7 1.1 -2.3
4 14.3 -3.1 6.2 9.2 2.1 -2.9
5 12.9 -2.0 5.4 8.5 1.2 -2.6
6 12.7 -2.6 5.4 8.4 2.0 -2.7
7 13.0 -2.3 5.5 8.6 1.6 -2.9
8 12.6 -2.3 5.4 8.2 1.6 -2.4
Critical Combination:4 - ((G+Q)P2 *F)
Min Design
N (kN) 14.3 - 14.3
M1 (kN.m) -3.1 -0.2 0.0 225
M2 (kN.m) 6.2 0.2 9.2
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 3.2 kN As (Required): %0.47 239.58 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.08 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11

1C13 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 60.5 0.1 0.4 53.9 0.0 -0.7
2 43.2 0.0 0.3 38.5 0.0 -0.5
3 46.1 -0.1 0.4 39.5 0.4 -0.8
4 60.7 0.2 0.2 54.0 -0.4 -0.4
5 51.7 3.2 0.3 46.1 -3.1 -0.6
6 51.9 -3.1 0.3 46.2 3.1 -0.6
7 55.7 0.0 3.6 50.0 0.0 -3.8
8 47.9 0.1 -2.9 42.3 0.0 2.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 60.5 - 60.5
M1 (kN.m) 0.1 0.7 0.0 225
M2 (kN.m) -0.7 -0.7 -1.3
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.048 Le1/b1 = 11.6 < 15.0 225
Beta = 0.94 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.6 / 1.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.81 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y10-175

2C13 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 18.9 0.2 1.5 13.8 -0.3 -1.8
2 13.4 0.1 1.1 9.8 -0.2 -1.3
3 17.4 -0.3 1.6 12.3 0.0 -1.9
4 15.8 0.6 0.9 10.7 -0.4 -1.0
5 16.2 0.5 1.3 11.8 -0.6 -1.5
6 16.1 -0.2 1.3 11.7 0.2 -1.5
7 16.3 0.2 1.4 11.9 -0.2 -1.8
8 16.0 0.2 1.1 11.6 -0.2 -1.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 18.9 - 18.9
M1 (kN.m) -0.3 -0.2 0.0 225
M2 (kN.m) -1.8 -0.2 -2.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.015 Le1/b1 = 8.6 < 15.0 225
Beta = 0.98 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 1.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12

1C15 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 178.3 0.5 0.0 171.7 -0.7 0.1
2 126.3 0.3 0.0 121.6 -0.5 0.1
3 147.6 0.5 -0.6 140.9 -0.8 1.3
4 153.3 0.3 0.6 146.7 -0.4 -1.1
5 154.2 3.5 0.0 148.5 -3.6 0.1
6 149.0 -2.7 0.0 143.3 2.3 0.1
7 151.3 0.4 3.3 145.7 -0.6 -3.1
8 151.9 0.4 -3.3 146.2 -0.6 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 178.3 - 178.3
M1 (kN.m) -0.7 -2.0 0.0 225
M2 (kN.m) 0.1 2.0 3.7
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.141 Le1/b1 = 11.6 < 15.0 225
Beta = 0.84 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.2 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y10-175

2C15 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.0 0.9 0.4 9.9 -0.6 -0.7
2 10.7 0.7 0.3 7.1 -0.4 -0.5
3 13.4 1.0 -1.4 8.3 -0.6 0.3
4 13.8 0.6 2.0 8.7 -0.5 -1.5
5 13.1 1.0 0.3 8.7 -0.8 -0.6
6 12.6 0.6 0.3 8.3 -0.2 -0.6
7 13.0 0.8 0.5 8.6 -0.5 -0.9
8 12.7 0.8 0.1 8.4 -0.5 -0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 15.0 - 15.0
M1 (kN.m) 0.9 0.2 1.6 225
M2 (kN.m) -0.7 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 1.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13

1C16 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 198.9 0.7 -2.8 192.2 -1.2 5.6
2 140.6 0.5 -1.9 135.9 -0.8 4.0
3 179.7 1.0 -2.8 173.0 -1.8 5.7
4 153.2 0.1 -1.8 146.5 -0.2 3.6
5 167.7 3.7 -2.3 162.0 -4.1 4.8
6 169.8 -2.6 -2.3 164.1 2.1 4.8
7 167.2 0.6 0.9 161.5 -1.0 1.7
8 170.3 0.6 -5.6 164.6 -1.0 7.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 198.9 - 198.9
M1 (kN.m) -1.2 -2.2 0.0 225
M2 (kN.m) 5.6 2.2 7.5
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.157 Le1/b1 = 11.6 < 15.0 225
Beta = 0.82 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y10-175

2C16 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.7 1.7 -7.2 11.6 -1.2 3.4
2 11.9 1.2 -5.1 8.3 -0.9 2.4
3 15.6 2.5 -7.4 10.5 -1.7 3.5
4 14.5 0.3 -4.6 9.4 -0.4 2.2
5 14.2 1.8 -6.1 9.8 -1.5 2.9
6 14.4 1.1 -6.1 10.1 -0.6 2.9
7 14.2 1.5 -6.1 9.8 -1.1 2.6
8 14.5 1.4 -6.2 10.1 -1.0 3.2
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 15.6 - 15.6
M1 (kN.m) 2.5 0.2 0.0 225
M2 (kN.m) -7.4 -0.2 -9.8
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.4 / 3.6 kN As (Required): %0.50 255.09 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.09 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14

1C17 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 112.5 -2.0 -2.2 105.9 4.3 4.3
2 79.9 -1.4 -1.5 75.2 3.1 3.1
3 113.9 -2.0 -2.2 107.2 4.3 4.5
4 78.7 -1.3 -1.4 72.0 2.9 2.7
5 94.5 1.4 -1.8 88.8 0.8 3.6
6 97.3 -4.7 -1.9 91.6 6.5 3.7
7 94.3 -1.7 1.4 88.7 3.6 0.6
8 97.5 -1.7 -5.0 91.8 3.7 6.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 112.5 - 112.5
M1 (kN.m) 4.3 1.3 8.2 225
M2 (kN.m) 4.3 1.3 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.089 Le1/b1 = 11.7 < 15.0 225
Beta = 0.89 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.9 / 3.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.07 / 0.07 N/mm2
Links = Y10-175

2C17 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.2 -5.8 -5.7 9.1 2.9 3.1
2 10.1 -4.1 -4.0 6.5 2.0 2.2
3 14.1 -5.8 -5.9 9.0 2.8 3.1
4 11.5 -3.9 -3.6 6.4 2.0 2.1
5 12.0 -4.9 -4.9 7.7 2.2 2.6
6 12.3 -5.0 -4.9 7.9 2.7 2.6
7 12.0 -4.9 -4.8 7.6 2.4 2.4
8 12.3 -4.9 -4.9 7.9 2.5 2.8
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 14.1 - 14.1
M1 (kN.m) -5.8 -0.2 0.0 225
M2 (kN.m) -5.9 -0.2 -11.6
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.9 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.9 / 3.0 kN As (Required): %0.63 320.81 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.07 / 0.07 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15

1C18 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 128.8 0.3 0.1 122.1 -0.4 0.0
2 91.2 0.2 0.1 86.5 -0.3 0.0
3 112.4 0.2 0.0 105.7 -0.3 0.3
4 105.8 0.3 0.2 99.2 -0.4 -0.4
5 107.2 3.3 0.1 101.5 -3.3 0.0
6 111.8 -2.8 0.1 106.1 2.6 0.0
7 108.4 0.3 3.5 102.7 -0.3 -3.4
8 110.6 0.3 -3.3 104.9 -0.3 3.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 128.8 - 128.8
M1 (kN.m) -0.4 -1.4 0.0 225
M2 (kN.m) 0.1 1.4 2.7
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.102 Le1/b1 = 11.6 < 15.0 225
Beta = 0.88 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y10-175

2C18 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 20.4 -1.9 0.9 15.3 3.4 -0.3
2 14.6 -1.4 0.7 10.9 2.4 -0.2
3 19.7 -2.0 0.4 14.6 3.5 0.0
4 16.8 -1.2 1.1 11.6 2.3 -0.4
5 17.4 -1.4 0.8 13.0 2.6 -0.2
6 17.6 -1.9 0.8 13.3 3.3 -0.2
7 17.8 -1.7 1.2 13.4 3.0 -0.6
8 17.2 -1.6 0.4 12.8 2.9 0.2
Critical Combination:7 - (G+Q+Ny)
Min Design
N (kN) 17.8 - 17.8
M1 (kN.m) 3.0 0.2 4.1 225
M2 (kN.m) 1.2 0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.014 Le1/b1 = 8.9 < 15.0 225
Beta = 0.98 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16

1C19 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 110.4 0.9 -0.5 103.8 -1.5 1.2
2 78.6 0.6 -0.3 73.9 -1.0 0.8
3 101.1 1.1 -0.5 94.5 -1.9 1.2
4 89.8 0.3 -0.3 83.1 -0.5 0.7
5 94.3 3.9 -0.4 88.7 -4.3 1.0
6 94.4 -2.4 -0.4 88.7 1.8 1.0
7 92.1 0.8 2.9 86.4 -1.3 -2.2
8 96.6 0.7 -3.7 90.9 -1.2 4.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 110.4 - 110.4
M1 (kN.m) -1.5 -1.2 -2.6 225
M2 (kN.m) 1.2 1.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.087 Le1/b1 = 11.6 < 15.0 225
Beta = 0.90 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.05 N/mm2
Links = Y10-175

2C19 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.6 1.4 -0.2 10.5 -0.3 -0.4
2 11.1 1.0 -0.1 7.5 -0.2 -0.3
3 14.5 2.0 -0.3 9.4 -0.7 -0.4
4 13.5 0.3 0.0 8.4 0.2 -0.3
5 13.4 1.5 -0.2 9.0 -0.6 -0.3
6 13.3 0.9 -0.1 8.9 0.1 -0.4
7 13.1 1.2 0.0 8.8 -0.2 -0.6
8 13.5 1.2 -0.3 9.1 -0.3 -0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 15.6 - 15.6
M1 (kN.m) 1.4 0.2 1.8 225
M2 (kN.m) -0.4 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17

1C20 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 160.2 -0.1 4.4 153.6 0.4 -8.5
2 113.6 -0.1 3.1 108.9 0.3 -6.0
3 150.0 -0.3 4.4 143.3 0.7 -8.6
4 121.5 0.1 2.8 114.9 -0.1 -5.4
5 136.5 3.0 3.7 130.8 -2.8 -7.2
6 136.1 -3.3 3.7 130.5 3.4 -7.2
7 137.3 -0.1 6.9 131.6 0.4 -10.2
8 135.3 -0.1 0.5 129.7 0.3 -4.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 160.2 - 160.2
M1 (kN.m) 0.4 1.8 0.0 225
M2 (kN.m) -8.5 -1.8 -10.1
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.127 Le1/b1 = 11.6 < 15.0 225
Beta = 0.85 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 4.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.11 N/mm2
Links = Y10-175

2C20 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.3 -0.4 7.3 7.2 0.1 0.0
2 8.8 -0.3 5.1 5.2 0.1 0.0
3 10.7 -0.7 7.3 5.6 0.1 0.0
4 11.9 0.1 4.7 6.8 0.1 0.0
5 10.6 0.0 6.2 6.2 -0.3 0.0
6 10.5 -0.7 6.2 6.2 0.4 0.0
7 10.6 -0.3 6.2 6.2 0.1 0.0
8 10.5 -0.3 6.1 6.1 0.1 0.0
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 10.7 - 10.7
M1 (kN.m) -0.7 -0.1 0.0 225
M2 (kN.m) 7.3 0.1 8.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.4 kN As (Required): %0.41 207.26 mm2 4Y16
vc'(1/2)= 0.76 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.06 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18

1C23 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 217.0 1.8 0.5 210.4 -3.4 -0.6
2 153.3 1.3 0.4 148.5 -2.4 -0.5
3 195.7 2.1 0.5 189.1 -4.0 -0.6
4 166.0 0.8 0.3 159.4 -1.6 -0.4
5 182.7 4.7 0.4 177.0 -6.0 -0.6
6 185.2 -1.7 0.4 179.5 0.3 -0.5
7 183.8 1.5 2.9 178.1 -2.9 -2.0
8 184.1 1.5 -2.0 178.4 -2.9 0.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 217.0 - 217.0
M1 (kN.m) -3.4 -2.4 -5.3 225
M2 (kN.m) -0.6 -2.4 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.171 Le1/b1 = 11.6 < 15.0 225
Beta = 0.80 Le2/b2 = 13.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.02 N/mm2
Links = Y10-175

2C23 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 9.2 3.2 0.1 4.1 -1.2 0.0
2 6.6 2.3 0.1 2.9 -0.8 0.0
3 8.1 4.1 0.1 3.0 -1.5 0.0
4 9.2 1.3 0.1 4.1 -0.4 0.0
5 7.8 3.3 0.1 3.4 -1.5 0.0
6 8.0 2.2 0.1 3.6 -0.4 0.0
7 7.9 2.7 -1.3 3.5 -0.9 0.0
8 7.9 2.8 1.5 3.5 -1.0 0.0
Critical Combination:8 - (G+Q-Ny)
MinDesign
N (kN) 7.9 - 7.9
M1 (kN.m) 2.8 0.1 4.3 225
M2 (kN.m) 1.5 0.1 0.0
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-19

1C24 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 102.7 0.7 0.6 96.0 -1.2 -0.7
2 72.9 0.5 0.4 68.2 -0.9 -0.5
3 79.6 0.4 0.4 73.0 -0.5 -0.4
4 96.7 0.8 0.5 90.0 -1.5 -0.8
5 89.7 3.7 0.4 84.0 -4.0 -0.5
6 85.4 -2.5 0.5 79.7 1.9 -0.6
7 87.4 0.6 3.9 81.8 -1.0 -3.9
8 87.6 0.6 -3.0 81.9 -1.0 2.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 102.7 - 102.7
M1 (kN.m) -1.2 -1.2 -2.3 225
M2 (kN.m) -0.7 -1.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.081 Le1/b1 = 11.6 < 15.0 225
Beta = 0.90 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.05 N/mm2
Links = Y10-175

2C24 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.4 1.2 0.4 10.3 -1.2 -0.2
2 11.0 0.8 0.3 7.3 -0.8 -0.2
3 14.6 0.5 0.0 9.5 -1.1 -0.1
4 13.1 1.4 0.6 8.0 -0.9 -0.3
5 13.4 1.2 0.3 9.0 -1.4 -0.2
6 13.0 0.7 0.4 8.6 -0.6 -0.2
7 13.2 1.0 0.9 8.8 -1.0 -0.8
8 13.2 1.0 -0.2 8.8 -1.0 0.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 15.4 - 15.4
M1 (kN.m) -1.2 -0.2 -1.6 225
M2 (kN.m) 0.4 0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-20

1C25 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 220.8 -0.6 0.2 214.2 1.4 0.0
2 156.4 -0.4 0.1 151.6 1.0 0.0
3 209.9 -0.8 0.1 203.2 1.8 0.1
4 161.0 -0.2 0.1 154.4 0.5 -0.1
5 188.0 2.6 0.1 182.3 -1.9 0.0
6 187.3 -3.7 0.2 181.6 4.3 0.0
7 185.4 -0.5 3.5 179.7 1.2 -3.2
8 189.9 -0.5 -3.2 184.2 1.2 3.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 220.8 - 220.8
M1 (kN.m) 1.4 2.5 0.0 225
M2 (kN.m) 0.2 2.5 4.5
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.174 Le1/b1 = 11.6 < 15.0 225
Beta = 0.80 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y10-175

2C25 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 20.4 -2.1 1.3 15.3 0.1 -1.3
2 14.6 -1.5 0.9 10.9 0.1 -0.9
3 19.0 -2.4 1.2 13.9 0.0 -1.4
4 17.4 -0.9 0.9 12.3 0.1 -0.7
5 17.4 -1.3 1.1 13.1 -0.4 -1.1
6 17.5 -2.2 1.1 13.1 0.6 -1.1
7 17.1 -1.8 1.7 12.7 0.1 -1.8
8 17.9 -1.7 0.5 13.5 0.1 -0.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 20.4 - 20.4
M1 (kN.m) -2.1 -0.2 -3.3 225
M2 (kN.m) -1.3 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 8.6 < 15.0 225
Beta = 0.98 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-21

1C26 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 80.3 0.7 1.8 73.7 -1.2 -3.2
2 57.1 0.5 1.3 52.4 -0.9 -2.2
3 68.1 0.8 1.3 61.5 -1.4 -2.2
4 70.7 0.3 1.6 64.1 -0.6 -3.1
5 70.7 3.7 1.5 65.0 -4.0 -2.7
6 66.3 -2.5 1.5 60.6 1.9 -2.7
7 70.4 0.5 4.8 64.7 -1.0 -5.8
8 66.7 0.6 -1.8 61.0 -1.1 0.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 80.3 - 80.3
M1 (kN.m) -1.2 -0.9 0.0 225
M2 (kN.m) -3.2 -0.9 -4.3
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.063 Le1/b1 = 11.6 < 15.0 225
Beta = 0.92 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 2.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.83 / 0.83 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.07 N/mm2
Links = Y10-175

2C26 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.9 1.8 3.8 6.8 -1.2 -2.2
2 8.5 1.3 2.7 4.9 -0.9 -1.6
3 9.9 1.9 2.5 4.8 -1.1 -1.5
4 11.9 1.1 3.9 6.8 -0.9 -2.2
5 10.4 1.7 3.2 6.0 -1.3 -1.9
6 10.0 1.4 3.2 5.7 -0.8 -1.9
7 10.4 1.5 3.5 6.0 -1.0 -2.3
8 10.0 1.6 3.0 5.6 -1.1 -1.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 11.9 - 11.9
M1 (kN.m) 1.8 0.1 0.0 225
M2 (kN.m) 3.8 0.1 5.6
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 8.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 1.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.05 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-22

1C27 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 159.0 0.1 1.9 152.3 -0.1 -3.6
2 112.8 0.1 1.4 108.0 -0.1 -2.5
3 126.3 0.5 1.3 119.6 -0.8 -2.3
4 143.3 -0.3 1.9 136.7 0.6 -3.6
5 135.3 3.3 1.6 129.6 -3.2 -3.0
6 135.3 -3.1 1.7 129.6 3.0 -3.0
7 137.3 0.1 4.9 131.6 -0.1 -6.1
8 133.3 0.1 -1.6 127.7 -0.1 0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 159.0 - 159.0
M1 (kN.m) -0.1 -1.8 0.0 225
M2 (kN.m) -3.6 -1.8 -5.1
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.126 Le1/b1 = 11.6 < 15.0 225
Beta = 0.85 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 2.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.89 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.07 N/mm2
Links = Y10-175

2C27 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.3 0.3 5.7 11.2 -0.3 -3.2
2 11.6 0.2 4.0 8.0 -0.2 -2.3
3 14.5 1.1 4.1 9.4 -0.5 -2.5
4 14.9 -0.6 5.3 9.8 0.0 -2.8
5 13.9 0.6 4.8 9.6 -0.6 -2.7
6 14.0 -0.1 4.8 9.6 0.1 -2.7
7 14.3 0.3 5.3 9.9 -0.2 -3.4
8 13.7 0.2 4.3 9.3 -0.2 -2.1
Critical Combination:4 - ((G+Q)P2 *F)
Min Design
N (kN) 14.9 - 14.9
M1 (kN.m) -0.6 -0.2 0.0 225
M2 (kN.m) 5.3 0.2 5.9
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 3.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.07 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-23

1C28 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 120.7 0.4 0.1 114.1 -0.6 0.2
2 85.5 0.3 0.1 80.8 -0.4 0.1
3 98.4 0.0 0.1 91.7 0.0 0.2
4 106.3 0.6 0.0 99.7 -1.1 0.1
5 101.5 3.5 0.1 95.8 -3.7 0.1
6 103.8 -2.9 0.1 98.1 2.6 0.1
7 102.8 0.3 2.5 97.1 -0.5 -1.2
8 102.5 0.3 -2.3 96.8 -0.6 1.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 120.7 - 120.7
M1 (kN.m) -0.6 -1.4 0.0 225
M2 (kN.m) 0.2 1.4 2.6
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.095 Le1/b1 = 11.6 < 15.0 225
Beta = 0.89 Le2/b2 = 13.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y10-175

2C28 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.7 1.1 0.2 6.6 -0.9 0.0
2 8.4 0.8 0.2 4.7 -0.6 0.0
3 10.9 0.3 0.2 5.8 -0.6 0.0
4 10.7 1.5 0.2 5.6 -0.9 0.0
5 10.0 1.3 0.2 5.6 -1.1 0.0
6 10.1 0.5 0.2 5.7 -0.4 0.0
7 10.1 0.9 -1.2 5.7 -0.8 0.0
8 10.0 0.9 1.5 5.6 -0.8 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 11.7 - 11.7
M1 (kN.m) 1.1 0.1 1.3 225
M2 (kN.m) 0.2 0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-24

1C29 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 133.1 0.0 -0.8 126.5 0.2 1.7
2 94.4 0.0 -0.5 89.7 0.2 1.2
3 93.9 -0.1 -0.2 87.2 0.5 0.6
4 132.4 0.2 -1.1 125.8 -0.2 2.3
5 115.6 3.1 -0.7 110.0 -2.8 1.5
6 111.0 -3.1 -0.7 105.3 3.2 1.5
7 115.7 0.0 2.7 110.0 0.2 -1.8
8 110.9 0.0 -4.0 105.3 0.2 4.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 133.1 - 133.1
M1 (kN.m) 0.2 1.5 0.0 225
M2 (kN.m) 1.7 1.5 3.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.105 Le1/b1 = 11.6 < 15.0 225
Beta = 0.87 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.81 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.06 N/mm2
Links = Y10-175

2C29 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.7 0.5 -2.2 11.6 -1.6 1.3
2 11.9 0.4 -1.6 8.3 -1.2 0.9
3 15.3 0.1 -0.6 10.2 -1.5 0.3
4 14.6 0.8 -3.0 9.5 -1.3 1.9
5 14.5 0.6 -1.9 10.1 -1.7 1.1
6 14.1 0.3 -1.9 9.7 -1.1 1.1
7 14.3 0.4 -1.5 10.0 -1.4 0.8
8 14.2 0.4 -2.2 9.9 -1.4 1.5
Critical Combination:4 - ((G+Q)P2 *F)
Min Design
N (kN) 14.6 - 14.6
M1 (kN.m) -1.3 -0.2 0.0 225
M2 (kN.m) -3.0 -0.2 -4.3
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 8.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 1.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.04 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-25

1C30 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 95.4 -0.2 0.1 88.7 0.8 0.0
2 67.8 -0.2 0.1 63.1 0.6 0.0
3 92.0 -0.3 0.1 85.4 1.0 0.0
4 72.5 -0.1 0.0 65.8 0.3 0.0
5 82.1 2.9 0.1 76.5 -2.4 0.0
6 80.6 -3.4 0.1 74.9 3.8 0.0
7 78.1 -0.2 3.4 72.4 0.7 -3.2
8 84.7 -0.2 -3.2 79.0 0.7 3.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 95.4 - 95.4
M1 (kN.m) 0.8 1.1 0.0 225
M2 (kN.m) 0.1 1.1 2.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.075 Le1/b1 = 11.6 < 15.0 225
Beta = 0.91 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y10-175

2C30 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.2 -1.1 0.1 7.1 0.4 0.0
2 8.7 -0.8 0.1 5.1 0.3 0.0
3 11.0 -1.4 0.3 5.9 0.6 -0.3
4 11.5 -0.4 -0.1 6.4 0.1 0.4
5 10.5 -0.6 0.1 6.2 -0.1 0.0
6 10.4 -1.3 0.1 6.1 0.7 0.0
7 10.3 -1.0 0.2 5.9 0.3 -0.2
8 10.7 -0.9 0.0 6.3 0.3 0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 12.2 - 12.2
M1 (kN.m) -1.1 -0.1 -1.3 225
M2 (kN.m) 0.1 0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.7 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-26

1C31 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 234.8 -2.2 -8.1 228.2 4.7 16.7
2 166.7 -1.5 -5.7 162.0 3.3 11.8
3 224.9 -2.4 -8.0 218.3 5.1 16.6
4 172.6 -1.2 -5.4 165.9 2.6 11.1
5 200.6 1.3 -6.9 194.9 0.9 14.1
6 199.4 -5.0 -6.9 193.8 7.1 14.1
7 199.4 -1.8 -3.8 193.7 4.0 11.3
8 200.7 -1.9 -10.0 195.0 4.0 17.0
Critical Combination:8 - (G+Q-Ny)
Min Design
N (kN) 200.7 - 200.7
M1 (kN.m) 4.0 2.3 0.0 225
M2 (kN.m) 17.0 2.3 20.2
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.159 Le1/b1 = 11.6 < 15.0 225
Beta = 0.82 Le2/b2 = 11.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 6.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.93 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.17 N/mm2
Links = Y10-175

2C31 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 20.7 -6.4 -18.2 15.6 3.3 7.5
2 14.8 -4.5 -12.9 11.2 2.3 5.3
3 19.6 -7.0 -18.1 14.5 3.6 7.5
4 17.4 -3.6 -12.1 12.3 1.8 5.2
5 17.8 -5.1 -15.5 13.4 2.4 6.4
6 17.7 -5.7 -15.5 13.4 3.2 6.4
7 17.7 -5.5 -15.4 13.3 2.8 6.1
8 17.8 -5.4 -15.5 13.5 2.8 6.7
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 19.6 - 19.6
M1 (kN.m) -7.0 -0.2 0.0 225
M2 (kN.m) -18.1 -0.2 -25.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.015 Le1/b1 = 8.6 < 15.0 225
Beta = 0.98 Le2/b2 = 9.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.5 / 8.5 kN As (Required): %1.54 780.66 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.21 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-27

1C32 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 233.0 3.5 -0.1 226.4 -6.7 0.6
2 165.0 2.5 -0.1 160.2 -4.8 0.4
3 218.6 3.7 -0.1 212.0 -7.2 0.6
4 172.5 2.0 -0.1 165.8 -3.9 0.4
5 196.4 6.1 -0.1 190.7 -8.8 0.6
6 199.6 -0.2 -0.1 193.9 -2.6 0.5
7 197.9 3.0 2.3 192.2 -5.7 -0.8
8 198.1 2.9 -2.5 192.4 -5.7 1.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 233.0 - 233.0
M1 (kN.m) -6.7 -2.6 -8.8 225
M2 (kN.m) 0.6 2.6 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.184 Le1/b1 = 11.6 < 15.0 225
Beta = 0.79 Le2/b2 = 13.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

2C32 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.8 8.8 -0.1 6.7 -4.8 0.0
2 8.4 6.2 -0.1 4.8 -3.4 0.0
3 11.1 9.4 -0.1 6.0 -5.2 0.0
4 10.7 5.2 0.0 5.6 -2.9 0.0
5 10.0 7.8 0.0 5.7 -4.5 0.0
6 10.2 7.1 -0.1 5.9 -3.7 0.0
7 10.1 7.5 -1.4 5.7 -4.1 0.0
8 10.2 7.4 1.2 5.8 -4.1 0.0
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 11.1 - 11.1
M1 (kN.m) 9.4 0.1 9.5 225
M2 (kN.m) -0.1 -0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 8.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.8 / 0.5 kN As (Required): %0.51 257.96 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.12 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-28

1C33 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 113.8 0.2 0.3 107.1 -0.1 -0.3
2 80.6 0.1 0.2 75.9 -0.1 -0.2
3 96.3 0.2 0.5 89.6 -0.1 -0.8
4 96.8 0.1 -0.1 90.2 -0.1 0.2
5 96.5 2.5 0.3 90.8 -1.5 -0.3
6 96.9 -2.1 0.2 91.2 1.2 -0.3
7 97.5 0.2 3.6 91.8 -0.1 -3.6
8 95.9 0.2 -3.1 90.3 -0.1 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 113.8 - 113.8
M1 (kN.m) 0.2 1.3 0.0 225
M2 (kN.m) -0.3 -1.3 -2.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.090 Le1/b1 = 13.4 < 15.0 225
Beta = 0.89 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 1.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.05 N/mm2
Links = Y10-175

2C33 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.2 -0.1 2.1 5.1 0.0 -2.0
2 7.3 -0.1 1.5 3.7 0.0 -1.4
3 9.4 -0.1 2.7 4.3 0.0 -2.3
4 9.6 -0.1 0.9 4.5 0.0 -1.1
5 8.7 -1.4 1.8 4.4 0.0 -1.7
6 8.8 1.2 1.8 4.4 0.0 -1.7
7 8.7 -0.1 2.2 4.3 0.0 -2.2
8 8.9 -0.1 1.3 4.5 0.0 -1.2
Critical Combination:5 - (G+Q+Nx)
MinDesign
N (kN) 8.7 - 8.7
M1 (kN.m) -1.4 -0.1 0.0 225
M2 (kN.m) 1.8 0.1 3.2
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.007 Le1/b1 = 9.8 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 1.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.04 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-29

1C34 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 112.6 0.2 0.5 106.0 -0.1 -0.5
2 79.8 0.1 0.3 75.1 -0.1 -0.4
3 95.0 0.2 0.7 88.3 -0.1 -1.0
4 96.2 0.1 0.0 89.6 -0.1 0.1
5 96.0 2.4 0.4 90.3 -1.5 -0.4
6 95.5 -2.1 0.4 89.8 1.3 -0.5
7 96.6 0.2 3.8 90.9 -0.1 -3.8
8 95.0 0.2 -3.0 89.3 -0.1 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 112.6 - 112.6
M1 (kN.m) 0.2 1.3 0.0 225
M2 (kN.m) -0.5 -1.3 -2.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.089 Le1/b1 = 13.4 < 15.0 225
Beta = 0.89 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

2C34 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.2 -0.1 0.1 5.1 0.0 0.0
2 7.3 -0.1 0.1 3.6 0.0 0.0
3 9.3 -0.1 0.8 4.2 0.0 -0.4
4 9.7 -0.1 -0.6 4.6 0.0 0.4
5 8.8 -1.4 0.1 4.4 0.0 0.0
6 8.7 1.2 0.1 4.3 0.0 0.0
7 8.8 -0.1 0.7 4.4 0.0 -0.6
8 8.7 -0.1 -0.5 4.3 0.0 0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 10.2 - 10.2
M1 (kN.m) -0.1 -0.1 0.0 225
M2 (kN.m) 0.1 0.1 0.3
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 9.8 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-30

1C35 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 52.8 0.3 -0.4 46.2 -0.2 1.3
2 37.6 0.2 -0.3 32.9 -0.2 0.9
3 43.1 0.0 -0.4 36.5 0.3 1.3
4 50.0 0.4 -0.3 43.3 -0.7 0.8
5 47.4 3.3 -0.4 41.7 -3.1 1.1
6 43.0 -2.9 -0.3 37.3 2.8 1.1
7 42.8 0.3 3.0 37.1 -0.2 -2.1
8 47.5 0.2 -3.7 41.8 -0.1 4.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 52.8 - 52.8
M1 (kN.m) 0.3 0.6 0.0 225
M2 (kN.m) 1.3 0.6 1.9
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.042 Le1/b1 = 11.6 < 15.0 225
Beta = 0.95 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.4 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.80 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y10-175

2C35 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.6 1.0 -2.4 7.5 -1.9 1.5
2 8.9 0.7 -1.7 5.3 -1.4 1.1
3 11.6 0.2 -2.4 6.5 -1.5 1.4
4 11.1 1.4 -1.5 6.0 -1.7 1.1
5 10.9 1.0 -2.0 6.5 -1.9 1.3
6 10.6 0.7 -2.0 6.2 -1.4 1.3
7 10.5 0.8 -1.7 6.1 -1.7 0.9
8 11.0 0.8 -2.3 6.6 -1.6 1.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 12.6 - 12.6
M1 (kN.m) -1.9 -0.1 0.0 225
M2 (kN.m) -2.4 -0.1 -4.2
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 8.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 1.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-31

1C36 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 167.9 1.3 -2.9 161.3 -2.5 6.1
2 118.9 0.9 -2.1 114.1 -1.8 4.3
3 163.1 1.5 -2.8 156.4 -2.8 6.0
4 119.8 0.7 -2.0 113.2 -1.4 4.1
5 141.5 4.3 -2.5 135.8 -5.3 5.2
6 143.8 -2.0 -2.5 138.1 1.0 5.2
7 142.2 1.1 0.8 136.5 -2.2 2.0
8 143.1 1.1 -5.8 137.5 -2.1 8.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 167.9 - 167.9
M1 (kN.m) -2.5 -1.9 0.0 225
M2 (kN.m) 6.1 1.9 8.3
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.133 Le1/b1 = 11.6 < 15.0 225
Beta = 0.84 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.90 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.01 N/mm2
Links = Y10-175

2C36 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 15.2 3.8 -8.2 10.1 -2.4 3.7
2 10.8 2.7 -5.8 7.2 -1.7 2.6
3 14.1 4.2 -8.1 9.0 -2.5 3.6
4 13.4 2.1 -5.4 8.3 -1.4 2.5
5 12.9 3.6 -7.0 8.5 -2.4 3.1
6 13.1 2.8 -7.0 8.8 -1.6 3.1
7 12.8 3.3 -6.7 8.5 -2.0 2.7
8 13.2 3.2 -7.3 8.8 -2.0 3.5
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 14.1 - 14.1
M1 (kN.m) 4.2 0.2 0.0 225
M2 (kN.m) -8.1 -0.2 -12.3
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.5 < 15.0 225
Beta = 0.99 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.2 / 4.0 kN As (Required): %0.68 345.14 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.10 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-32

1C37 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 182.6 0.8 3.3 175.9 -1.5 -6.5
2 129.5 0.6 2.3 124.7 -1.1 -4.6
3 147.7 0.6 3.4 141.1 -1.0 -6.6
4 161.0 0.8 2.0 154.4 -1.5 -4.0
5 154.9 3.8 2.8 149.2 -4.4 -5.5
6 155.8 -2.5 2.8 150.1 1.8 -5.5
7 157.4 0.7 6.1 151.7 -1.3 -8.6
8 153.3 0.7 -0.5 147.6 -1.3 -2.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 182.6 - 182.6
M1 (kN.m) -1.5 -2.1 0.0 225
M2 (kN.m) -6.5 -2.1 -8.2
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.144 Le1/b1 = 13.4 < 15.0 225
Beta = 0.83 Le2/b2 = 11.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.83 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y10-175

2C37 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.8 2.2 7.2 11.7 -1.4 -2.8
2 12.0 1.6 5.1 8.3 -1.0 -2.0
3 15.9 1.4 7.3 10.8 -0.7 -2.8
4 14.3 2.3 4.6 9.2 -1.6 -1.8
5 14.3 2.2 6.1 10.0 -1.5 -2.4
6 14.4 1.6 6.1 10.0 -0.8 -2.3
7 14.6 1.9 6.4 10.2 -1.2 -2.8
8 14.2 1.9 5.8 9.8 -1.2 -1.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 16.8 - 16.8
M1 (kN.m) 2.2 0.2 0.0 225
M2 (kN.m) 7.2 0.2 9.4
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 8.8 < 15.0 225
Beta = 0.98 Le2/b2 = 8.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.3 / 3.4 kN As (Required): %0.47 238.19 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.08 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-33

1C39 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 154.7 0.1 1.7 148.0 0.0 -3.4
2 109.4 0.0 1.2 104.6 0.0 -2.4
3 145.5 0.1 1.8 138.9 0.0 -3.6
4 113.9 0.0 1.0 107.3 0.0 -2.0
5 131.2 2.4 1.5 125.5 -1.4 -2.9
6 131.3 -2.3 1.5 125.6 1.5 -2.9
7 128.5 0.0 4.8 122.9 0.0 -6.2
8 133.9 0.1 -1.9 128.2 0.0 0.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 154.7 - 154.7
M1 (kN.m) 0.1 1.7 0.0 225
M2 (kN.m) -3.4 -1.7 -4.9
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.122 Le1/b1 = 13.4 < 15.0 225
Beta = 0.86 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.80 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.07 N/mm2
Links = Y10-175

2C39 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 7.1 0.0 4.9 2.0 0.0 -3.3
2 5.1 0.0 3.5 1.5 0.0 -2.3
3 6.2 0.0 5.1 1.1 0.0 -3.5
4 7.9 0.0 3.0 2.8 0.0 -2.0
5 6.1 -1.4 4.2 1.7 0.0 -2.8
6 6.2 1.4 4.2 1.8 0.0 -2.8
7 6.0 0.0 4.5 1.7 0.0 -3.2
8 6.2 0.0 3.8 1.9 0.0 -2.4
Critical Combination:6 - (G+Q-Nx)
MinDesign
N (kN) 6.2 - 6.2
M1 (kN.m) 1.4 0.1 0.0 225
M2 (kN.m) 4.2 0.1 5.6
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.005 Le1/b1 = 9.8 < 15.0 225
Beta = 0.99 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 2.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.07 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-34

1C40 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 156.8 0.8 0.2 150.1 -1.5 0.0
2 110.6 0.6 0.1 105.9 -1.1 0.0
3 134.3 1.1 0.2 127.7 -2.1 0.0
4 125.3 0.2 0.1 118.7 -0.4 0.0
5 132.3 3.9 0.2 126.6 -4.5 0.0
6 133.1 -2.5 0.2 127.5 1.9 0.0
7 132.8 0.7 1.9 127.1 -1.3 0.0
8 132.7 0.7 -1.6 127.0 -1.3 0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 156.8 - 156.8
M1 (kN.m) -1.5 -1.8 0.0 225
M2 (kN.m) 0.2 1.8 3.3
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.124 Le1/b1 = 11.5 < 15.0 225
Beta = 0.85 Le2/b2 = 13.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.00 N/mm2
Links = Y10-175

1C41 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 172.5 -1.5 -0.3 165.9 3.3 0.9
2 122.2 -1.1 -0.2 117.4 2.3 0.7
3 143.2 -1.7 0.2 136.5 3.5 0.0
4 147.5 -0.8 -0.7 140.9 1.8 1.5
5 146.6 1.8 -0.3 140.9 -0.2 0.8
6 146.7 -4.4 -0.3 141.0 5.7 0.8
7 147.4 -1.3 3.2 141.7 2.8 -2.6
8 145.9 -1.3 -3.7 140.2 2.8 4.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 172.5 - 172.5
M1 (kN.m) 3.3 1.9 4.9 225
M2 (kN.m) 0.9 1.9 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.136 Le1/b1 = 11.7 < 15.0 225
Beta = 0.84 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-35

2C41 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.4 -3.0 0.3 8.3 0.1 -1.2
2 9.6 -2.1 0.2 5.9 0.0 -0.9
3 12.6 -3.3 1.5 7.5 0.1 -1.9
4 11.9 -1.7 -1.0 6.8 0.0 -0.2
5 11.6 -2.6 0.3 7.3 0.0 -1.1
6 11.4 -2.6 0.2 7.0 0.1 -1.1
7 11.6 -2.5 1.2 7.2 0.0 -2.0
8 11.4 -2.6 -0.7 7.0 0.0 -0.1
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 12.6 - 12.6
M1 (kN.m) -3.3 -0.1 -5.2 225
M2 (kN.m) -1.9 -0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.7 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.1 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.03 N/mm2
Links = Y10-175

1C42 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 124.7 0.7 -0.1 118.1 -1.3 0.6
2 88.6 0.5 -0.1 83.8 -0.9 0.4
3 95.8 0.4 0.3 89.2 -0.6 0.0
4 117.3 0.8 -0.4 110.7 -1.4 1.1
5 108.2 3.7 -0.1 102.5 -4.0 0.5
6 104.4 -2.5 -0.1 98.7 1.9 0.5
7 106.1 0.6 3.4 100.4 -1.1 -2.9
8 106.5 0.6 -3.5 100.8 -1.1 3.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 124.7 - 124.7
M1 (kN.m) -1.3 -1.4 0.0 225
M2 (kN.m) 0.6 1.4 2.6
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.099 Le1/b1 = 11.6 < 15.0 225
Beta = 0.88 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.00 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-36

2C42 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.9 0.6 -1.3 5.8 0.0 0.6
2 7.8 0.4 -0.9 4.1 0.0 0.4
3 10.1 0.0 -0.4 5.0 0.0 0.1
4 10.1 0.9 -1.7 5.0 0.0 0.9
5 9.4 0.5 -1.1 5.0 0.0 0.5
6 9.3 0.4 -1.1 5.0 0.0 0.5
7 9.4 0.4 -0.5 5.0 0.0 -0.1
8 9.3 0.5 -1.7 4.9 0.0 1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 10.9 - 10.9
M1 (kN.m) 0.6 0.1 0.0 225
M2 (kN.m) -1.3 -0.1 -1.8
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 9.6 < 15.0 225
Beta = 0.99 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y10-175

1C43 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 115.6 -0.4 0.3 109.0 1.1 -0.4
2 82.0 -0.3 0.2 77.2 0.8 -0.3
3 100.7 -0.3 0.4 94.1 0.8 -0.4
4 94.9 -0.4 0.2 88.2 1.0 -0.3
5 99.6 2.8 0.3 93.9 -2.3 -0.3
6 97.2 -3.5 0.3 91.5 4.1 -0.3
7 98.5 -0.4 2.1 92.8 0.9 -0.4
8 98.3 -0.4 -1.5 92.6 0.9 -0.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 115.6 - 115.6
M1 (kN.m) 1.1 1.3 0.0 225
M2 (kN.m) -0.4 -1.3 -2.5
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.091 Le1/b1 = 11.5 < 15.0 225
Beta = 0.89 Le2/b2 = 13.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-37

1C44 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 81.9 -0.3 0.0 75.3 1.0 0.0
2 58.3 -0.2 0.0 53.5 0.7 0.0
3 75.9 -0.4 0.1 69.2 1.1 0.0
4 65.7 -0.2 0.0 59.1 0.6 0.0
5 71.4 2.9 0.0 65.7 -2.3 0.0
6 68.4 -3.4 0.0 62.8 3.9 0.0
7 69.3 -0.3 2.5 63.7 0.8 -1.5
8 70.5 -0.3 -2.4 64.8 0.8 1.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 81.9 - 81.9
M1 (kN.m) 1.0 0.9 1.8 225
M2 (kN.m) 0.0 0.9 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.065 Le1/b1 = 11.6 < 15.0 225
Beta = 0.92 Le2/b2 = 13.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 1.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.83 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.03 N/mm2
Links = Y10-175

2C44 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.2 -1.3 -0.1 8.1 0.4 0.0
2 9.4 -0.9 0.0 5.7 0.3 0.0
3 12.7 -1.4 -0.1 7.6 0.5 0.0
4 11.2 -0.8 0.0 6.1 0.2 0.0
5 11.4 -0.8 0.0 7.0 0.0 0.0
6 11.2 -1.4 0.0 6.8 0.7 0.0
7 11.1 -1.1 -1.5 6.7 0.4 0.0
8 11.4 -1.1 1.4 7.0 0.3 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 13.2 - 13.2
M1 (kN.m) -1.3 -0.1 -1.4 225
M2 (kN.m) -0.1 -0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 8.5 < 15.0 225
Beta = 0.99 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.7 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-38

1C45 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 154.7 1.1 0.0 148.0 -2.0 0.3
2 109.4 0.8 0.0 104.7 -1.4 0.2
3 144.5 1.2 0.0 137.9 -2.2 0.3
4 115.7 0.6 0.0 109.1 -1.1 0.2
5 131.1 4.1 0.0 125.4 -4.8 0.2
6 131.6 -2.2 0.0 125.9 1.4 0.3
7 131.1 0.9 2.4 125.4 -1.7 -1.2
8 131.5 0.9 -2.4 125.9 -1.7 1.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 154.7 - 154.7
M1 (kN.m) -2.0 -1.7 -3.5 225
M2 (kN.m) 0.3 1.7 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.122 Le1/b1 = 11.6 < 15.0 225
Beta = 0.86 Le2/b2 = 13.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.3 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.00 N/mm2
Links = Y10-175

2C45 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.4 2.8 0.2 6.3 -1.5 0.0
2 8.1 2.0 0.2 4.5 -1.0 0.0
3 10.3 3.1 0.2 5.2 -1.7 0.0
4 10.6 1.6 0.2 5.5 -0.7 0.0
5 9.7 2.7 0.2 5.4 -1.6 0.0
6 9.7 2.0 0.2 5.4 -0.8 0.0
7 9.8 2.4 -1.2 5.4 -1.3 0.0
8 9.7 2.4 1.6 5.3 -1.2 0.0
Critical Combination:8 - (G+Q-Ny)
MinDesign
N (kN) 9.7 - 9.7
M1 (kN.m) 2.4 0.1 3.9 225
M2 (kN.m) 1.6 0.1 0.0
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 8.5 < 15.0 225
Beta = 0.99 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.6 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-39

1C46 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 169.3 -2.1 -1.2 162.6 4.4 2.5
2 119.8 -1.5 -0.8 115.1 3.1 1.8
3 141.3 -2.3 -0.7 134.7 4.8 1.5
4 143.6 -1.1 -1.3 136.9 2.4 2.6
5 142.6 1.3 -1.0 136.9 0.8 2.1
6 145.0 -4.8 -1.0 139.3 6.6 2.1
7 145.2 -1.8 2.4 139.5 3.7 -1.2
8 142.4 -1.7 -4.4 136.7 3.6 5.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 169.3 - 169.3
M1 (kN.m) 4.4 1.9 6.5 225
M2 (kN.m) 2.5 1.9 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.134 Le1/b1 = 11.7 < 15.0 225
Beta = 0.84 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 2.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.06 N/mm2
Links = Y10-175

2C46 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.7 -5.4 -3.2 8.6 2.6 1.5
2 9.8 -3.8 -2.2 6.2 1.8 1.0
3 12.7 -6.0 -1.9 7.6 2.9 0.9
4 12.5 -3.0 -3.3 7.4 1.5 1.6
5 11.7 -4.5 -2.7 7.4 2.0 1.2
6 11.9 -4.6 -2.7 7.5 2.4 1.3
7 11.9 -4.6 -2.3 7.5 2.2 0.8
8 11.7 -4.5 -3.1 7.4 2.2 1.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 13.7 - 13.7
M1 (kN.m) -5.4 -0.2 -8.5 225
M2 (kN.m) -3.2 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 8.9 < 15.0 225
Beta = 0.99 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.0 / 1.6 kN As (Required): %0.43 215.83 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.07 / 0.04 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-40

1C47 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 154.6 -1.0 0.5 148.0 2.2 -0.8
2 109.5 -0.7 0.4 104.8 1.6 -0.6
3 146.3 -1.1 0.6 139.7 2.4 -0.9
4 114.6 -0.6 0.3 107.9 1.3 -0.4
5 132.6 2.3 0.4 126.9 -1.2 -0.6
6 130.2 -4.0 0.5 124.6 5.0 -0.7
7 132.6 -0.9 3.8 126.9 1.9 -3.9
8 130.2 -0.9 -2.9 124.6 1.9 2.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 154.6 - 154.6
M1 (kN.m) 2.2 1.7 3.7 225
M2 (kN.m) -0.8 -1.7 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.122 Le1/b1 = 11.6 < 15.0 225
Beta = 0.86 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.3 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.01 N/mm2
Links = Y10-175

2C47 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.8 -2.5 0.6 5.7 0.8 0.0
2 7.7 -1.7 0.4 4.0 0.6 0.0
3 10.8 -2.6 0.6 5.7 0.9 0.0
4 9.1 -1.5 0.4 4.0 0.5 0.0
5 9.3 -1.7 0.4 4.9 0.3 0.0
6 9.1 -2.5 0.5 4.7 1.1 0.0
7 9.1 -2.1 0.7 4.8 0.7 0.0
8 9.3 -2.1 0.2 4.9 0.7 0.0
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 10.8 - 10.8
M1 (kN.m) -2.6 -0.1 -3.2 225
M2 (kN.m) 0.6 0.1 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 8.5 < 15.0 225
Beta = 0.99 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.2 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.01 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-41

1C48 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 199.0 -3.9 -0.6 192.3 8.0 1.2
2 141.0 -2.7 -0.4 136.3 5.6 0.9
3 181.4 -3.8 -1.0 174.8 7.9 2.0
4 154.4 -2.5 -0.1 147.8 5.2 0.1
5 167.5 -0.2 -0.5 161.8 3.8 1.0
6 171.0 -6.4 -0.6 165.3 9.7 1.1
7 168.7 -3.3 2.8 163.0 6.8 -2.2
8 169.8 -3.3 -3.9 164.1 6.7 4.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 199.0 - 199.0
M1 (kN.m) 8.0 2.2 9.8 225
M2 (kN.m) 1.2 2.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.157 Le1/b1 = 11.7 < 15.0 225
Beta = 0.82 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.1 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.01 N/mm2
Links = Y10-175

2C48 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 17.5 -9.8 -1.4 12.4 4.0 0.4
2 12.5 -6.9 -1.0 8.8 2.9 0.3
3 16.3 -9.8 -2.4 11.2 4.0 1.0
4 15.1 -6.4 0.1 10.0 2.7 -0.3
5 14.8 -8.2 -1.2 10.5 3.2 0.4
6 15.1 -8.5 -1.2 10.7 3.7 0.4
7 15.0 -8.3 -0.8 10.6 3.4 0.0
8 15.0 -8.3 -1.5 10.6 3.4 0.7
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 16.3 - 16.3
M1 (kN.m) -9.8 -0.2 -12.1 225
M2 (kN.m) -2.4 -0.2 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 8.9 < 15.0 225
Beta = 0.98 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.6 / 1.1 kN As (Required): %0.66 333.96 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.11 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING
CADVIEW M.S LTD (*1KE-QB46-HVAE-G8DF)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-42

1C49 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 258.9 4.0 -0.3 252.3 -7.8 0.6
2 183.1 2.8 -0.2 178.4 -5.5 0.4
3 228.1 4.0 0.5 221.4 -7.9 -0.9
4 204.6 2.5 -1.0 198.0 -5.0 1.9
5 221.1 6.4 -0.2 215.4 -9.6 0.5
6 218.4 0.3 -0.2 212.7 -3.7 0.5
7 219.2 3.3 3.1 213.6 -6.6 -2.8
8 220.2 3.4 -3.6 214.6 -6.6 3.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 258.9 - 258.9
M1 (kN.m) -7.8 -2.9 -10.0 225
M2 (kN.m) 0.6 2.9 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.205 Le1/b1 = 11.7 < 15.0 225
Beta = 0.76 Le2/b2 = 11.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.00 N/mm2
Links = Y10-175

2C49 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 18.0 9.4 -0.7 12.9 -3.7 0.1
2 12.9 6.7 -0.5 9.2 -2.6 0.1
3 17.2 9.5 1.3 12.1 -3.7 -0.9
4 15.2 6.1 -2.5 10.1 -2.4 1.1
5 15.5 8.1 -0.6 11.2 -3.4 0.1
6 15.3 7.8 -0.6 11.0 -2.9 0.1
7 15.4 8.0 -0.2 11.1 -3.2 -0.3
8 15.4 8.0 -1.0 11.0 -3.1 0.6
Critical Combination:3 - ((G+Q)P1 *F)
Min Design
N (kN) 17.2 - 17.2
M1 (kN.m) 9.5 0.2 10.7 225
M2 (kN.m) 1.3 0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.014 Le1/b1 = 8.9 < 15.0 225
Beta = 0.98 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.4 / 1.2 kN As (Required): %0.56 283.29 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.11 / 0.03 N/mm2
Links = Y10-175

Project: PROPOSED_SEMI_DET_BUILDING