You are on page 1of 45

CLIENT: NATIONAL GRID

OMEXOM DOCUMENT No.: BIGG_KIL_XX_XX_CA_C_0207

CUSTOMER DOCUMENT No.: 96_OMX_0028

INVESTMENT No.: 100794

BIGGLESWADE 400kV SUBSTATION

UKPN 132kV INCOMER CIRCUIT BREAKER FOUNDATION


CALCULATION PACK

B 26.03.24 NA SF SM Second Issue

A 24.10.23 NA SF SM First Issue

Rev. Date Prepared Reviewed Approved Comments

Page 1 of 45 We are VINCI Energies, working together with National Grid.


Contents
Introduction ...................................................................................................................... 3
Background ............................................................................................................ 3
Existing Ground Conditions .................................................................................... 4
Loading & Load Combinations.......................................................................................... 5
Applied Loads – Circuit Breaker ............................................................................. 5
Load Combinations................................................................................................. 7
Loads adopted for design ....................................................................................... 7
Pad Foundation Design .................................................................................................... 8
Design Inputs ......................................................................................................... 8
3.2) Circuit breaker – Load Combination 1 .................................................................... 9
3.3) Circuit breaker – Load Combination 2 .................................................................. 19
3.4) Overturning Check - Circuit Breaker ..................................................................... 28
3.5) Holding down bolt design...................................................................................... 28
3.6) Design summary .................................................................................................. 30
3.7) Concrete Specification.......................................................................................... 31

Figures

Manufacturers provided terminal loading information………………………………

Appendices
Appendix A – Manufacturers Drawing Information….………………………………………33
Appendix B – Email Correspondence on Loading Confirmation.………………………….41

Page 2 of 45 We are VINCI Energies, working together with National Grid.


Introduction

Kiloh Associates have been asked to provide engineering consultancy design services as follows:

▪ Design of new concrete foundations to support new electrical equipment


▪ Production of construction drawings.
▪ Calculation document to be read in conjunction with drawing:
30_OMX_0027 - UKPN 132kV Incomer Circuit Breaker
▪ Check on holding down bolts (Baseplate design is by others)

Background

1.1.1) Site Description & Topography


The site is located approximately 2.25km to the south-east of Biggleswade Station, located in the
field directly to the east of Park Corner Farm on Dunton Lane.

Figure 1 Site Location


The site comprises agricultural land surrounded almost entirely by agricultural fields and farmland.
The site generally slopes from north to south from between 36.5m and 40.0m.

Page 3 of 45 We are VINCI Energies, working together with National Grid.


Existing Ground Conditions

Kiloh Associates have reviewed the Geoenvironmental Appraisal undertaken by Dunelm


Geotechnical & Environmental, (Report Reference: D10439/01, dated November 2021) to
understand the existing ground conditions across the area of the proposed works.
The investigation comprised: -
• Five boreholes (BHA01 – BHA05), to maximum depth of 20.45m below ground level (bgl);
• Three hand excavated inspection pits (TPA01, TPA04 and TPA06) a maximum depth of 1m
bgl for undertaking infiltration testing;
• Four machine excavated trial pits to a maximum depth of 4m bgl (TPA02, TPA03, TPA05
and TPA07);
• Installation of four ground gas and groundwater monitoring wells;
• In-situ testing;
• Sampling for geotechnical and geo-environmental laboratory testing; and,
• Post-fieldwork groundwater and ground gas monitoring.
The ground investigation carried out by Dunelm confirmed the proposed development area to be
underlain by topsoil, typically up to 0.30m thick overlying Till. The thickness of the weathered Till
(Upper Brown Clay) ranges between 0.65m and 7.00m bgl. Bedrock was not encountered.
Sequence of strata:
• Topsoil (reworked);
• Upper Brown Clay (weather Glacial Till)
• Lower Grey Clay (Glacial Till)
On the basis of the formation level for the concrete bases being located within the brown clay an
allowable ground bearing pressure of 100kPa has been adopted.
The following has also been incorporated within the design;
▪ ACEC class AC-1s & design chemical class DC-1
▪ Density of soil = 17.0kN/m³
▪ Characteristic friction angle – 20 degrees
▪ Characteristic shear angle resistance – 25 degrees
▪ Drained foundations (i.e.no groundwater)

1.2.1) Design Standards and Codes of Practice


Foundation and geotechnical analysis in undertaken accordance with the following: -
• EN1997-1:2004 + A1:2013 incorporating corrigendum February 2009 and the UK National
Annex incorporating corrigendum No.1
• BS 8004:2015 Code of Practice for Foundations

Foundations have been designed in accordance with the following National Grid specification.
• TS_2.10.03 – Piling and Foundations
• TS_3.10.02 - Materials
• TS_3.10.04 – Concreting and Formwork
• TS_3.01.04- Busbar systems for AIS substations

Page 4 of 45 We are VINCI Energies, working together with National Grid.


Loading & Load Combinations

Applied Loads – Circuit Breaker


Table below is an extract from Grid Solutions drawing VS382926GAD01D_02

Figure 2 Manufacturers loading information - VS382926GAD01D_02 (see appendix A)

Figure 3 Manufacturers provided terminal loading information from email


KIL2054_231201_SM_PD_CE-DP06.01 UKPN 132kV Bases dated 15/01/24
– See Appendix B)
Page 5 of 45 We are VINCI Energies, working together with National Grid.
Dead load = weight of 3No. poles, base frame, mechanism, gas + 2No. supports (see appendix A)
= 835.5kg + (2 x 122kg)
= 1079.5kg x 9.81 N/kg x 10-3
= 10.6kN (Unfactored)

Figure 4 Direction of applied forces- VS382926GAD01D_02 (see appendix A)

Page 6 of 45 We are VINCI Energies, working together with National Grid.


Load Combinations

Load case 1 = 100% static terminal + weight + pressure + 30% wind + operation
Load case 2 = 50% static terminal + weight + pressure + 100% wind 100% short circuit + operation
Load case 3 = 70% static terminal + weight + pressure + 10% wind + 100% seismic + operation

(Load combinations by GE Vernova. Refer to Appendix B, email dated 13/03/24.)

Loads adopted for design


All loads below are factored

Worst case down load onto foundation = 33.9kN (load provided from email dated 13/03/24)

Worst case uplift onto foundation = 8.1kN (load provided from email dated 13/03/24)

Worst case horizontal force on foundation (X-axis) = 13.8kN (load provided from email dated
13/03/24)

Worst case horizontal force on foundation (Y-axis) = 14kN (load provided from email dated
13/03/24)

Worst case overturning moment on foundation (X-axis) = 40.5kNm (load provided from email dated
13/03/24)

Worst case overturning moment on foundation (Y-axis) = 46.3kNm (load provided from email dated
13/03/24)

Worst case horizontal shear force on anchor = 1.8kN (load provided from email dated 13/03/24)

(Worst case loads by others. Refer to Appendix B.)

Page 7 of 45 We are VINCI Energies, working together with National Grid.


Pad Foundation Design

Design Inputs

▪ Concrete class is RC32/40


▪ Steel reinforcement to be 500N/mm²
▪ Cover assumed to be 50mm top and sides and 75mm bottom.
▪ Density of concrete is 24.5kN/m²
▪ Partial Factors are in accordance with BS EN 1997 and the National Annex and TS-
_3.01.04
▪ Foundations are drained, water level is assumed to be below the foundation
▪ Presumed design resistance of the foundation is 100kN/m2, please refer to Section 1.1.2
for further details
▪ Characteristic friction angle for the clay is assumed to be 20 degrees
▪ Passive resistance of soil has been ignored for sliding checks

Page 8 of 45 We are VINCI Energies, working together with National Grid.


3.2) Circuit breaker – Load Combination 1
Worst case downwards force, horizontal force and moment applied simultaneously.

Load onto each leg is as follows. See loading information on page 7:

Fzdead = 33.9kN / 2 = 16.45kN

Fximposed = 13.8kN / 2 = 6.9kN Fyimposed = 14kN / 2 = 7kN

Mximposed = 40.5kNm / 2 = 20.25kNm Myimposed = 46.3kNm / 2 = 23.15kNm

Foundation analysis in accordance with EN1997-1:2004 + A1:2013 incorporating corrigendum


February 2009 and the UK National Annex incorporating corrigendum No.1
Tedds calculation version 3.3.05

Pad foundation details


Length of foundation; Lx = 3400 mm
Width of foundation; Ly = 1800 mm
Foundation area; A = Lx  Ly = 6.120 m2
Depth of foundation; h = 800 mm
Depth of soil over foundation; hsoil = 0 mm
Level of water; hwater = 0 mm
Density of water; water = 9.8 kN/m3
Density of concrete; conc = 24.5 kN/m3

Column no.1 details


Length of column; lx1 = 290 mm
Width of column; ly1 = 370 mm
position in x-direction; x1 = 435 mm
position in y-direction; y1 = 900 mm
Column no.2 details
Length of column; lx2 = 290 mm
Width of column; ly2 = 370 mm
position in x-direction; x2 = 2965 mm
position in y-direction; y2 = 900 mm
Soil properties
Density of soil; soil = 18.0 kN/m3

Page 9 of 45 We are VINCI Energies, working together with National Grid.


Characteristic cohesion; c'k = 0 kN/m2
Characteristic effective shear resistance angle; 'k = 30 deg
Characteristic friction angle; k = 20 deg

Foundation loads
Self weight; Fswt = h  conc = 19.6 kN/m2

Column no.1 loads


Permanent axial load; FGz1 = 16.5 kN
Variable horizontal load in x-direction; FQx1 = 6.9 kN
Variable horizontal load in y-direction; FQy1 = 7.0 kN
Variable moment in x-direction; MQx1 = 20.3 kNm
Variable moment in y-direction; MQy1 = 23.2 kNm
Column no.2 loads
Permanent axial load; FGz2 = 16.5 kN
Variable horizontal load in x-direction; FQx2 = 6.9 kN
Variable horizontal load in y-direction; FQy2 = 7.0 kN
Variable moment in x-direction; MQx2 = 20.3 kNm
Variable moment in y-direction; MQy2 = 23.2 kNm
Bearing resistance (Section 6.5.2)
Forces on foundation
Force in x-direction; Fdx = FQx1 + FQx2 = 13.8 kN
Force in y-direction; Fdy = FQy1 + FQy2 = 14.0 kN
Force in z-direction; Fdz = A  Fswt + FGz1 + FGz2 = 152.9 kN

Moments on foundation
Moment in x-direction; Mdx = A  Fswt  Lx / 2 + FGz1  x1 + FGz2  x2 + MQx1 +
FQx1  h + MQx2 + FQx2  h = 311.4 kNm
Moment in y-direction; Mdy = A  Fswt  Ly / 2 + FGz1  y1 + FGz2  y2 + MQy1 +
FQy1  h + MQy2 + FQy2  h = 195.1 kNm

Eccentricity of base reaction


Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 337 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 376 mm
The extent of the footing acting in bearing has been determined using an iterative procedure. The volume of
the resulting bearing pressure diagram is equal in magnitude to the applied axial load and its centroid
coincides with the location of the resultant applied load. More details on the procedure adopted can be found
in the paper ‘Bearing pressures for rectangular footings with biaxial uplift’ by Kenneth E Wilson.
Pad base pressures
q1 = 0 kN/m2
q2 = 40.9 kN/m2
q3 = 0 kN/m2
q4 = 76.7 kN/m2
Minimum base pressure; qmin = min(q1, q2, q3, q4) = 0 kN/m2
Maximum base pressure; qmax = max(q1, q2, q3, q4) = 76.7 kN/m2
Presumed bearing capacity
Presumed bearing capacity; Pbearing = 100.0 kN/m2
PASS - Presumed bearing capacity exceeds design base pressure
Design approach 1
Partial factors on actions - Combination1
Partial factor set; A1

Page 10 of 45 We are VINCI Energies, working together with National Grid.


Permanent unfavourable action - Table A.3; G = 1.35
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.50
Variable favourable action - Table A.3; Qf = 0.00

Partial factors for spread foundations - Combination1


Resistance factor set; R1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00

Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 20.7 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 21.0 kN
Force in z-direction; Fdz = G  (A  Fswt + FGz1 + FGz2) = 206.4 kN

Moments on foundation
Moment in x-direction; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1 + FGz2  x2) + Q 
(MQx1 + MQx2) + (Q  (FQx1 + FQx2))  h = 428.1 kNm
Moment in y-direction; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1 + FGz2  y2) + Q 
(MQy1 + MQy2) + (Q  (FQy1 + FQy2))  h = 272.0 kNm

Eccentricity of base reaction


Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 375 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 418 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 2651 mm
Effective width; L'y = Ly - 2  ey = 964 mm
Effective area; A' = L'x  L'y = 2.555 m2

Pad base pressure


Design base pressure; fdz = Fdz / A' = 80.8 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 20.7 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 21.0 kN
Force in z-direction; Fdz = Gf  (A  Fswt + FGz1 + FGz2) = 152.9 kN

Sliding resistance verification (Section 6.5.3)


Horizontal force on foundation; H = [Fdx2 + Fdy2]0.5 = 29.5 kN
Design friction angle d = atan(tan(k) / ') = 20 deg
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(d) = 55.6 kN
H / RH.d = 0.530
PASS - Foundation is not subject to failure by sliding
Design approach 1
Partial factors on actions - Combination2
Partial factor set; A2
Permanent unfavourable action - Table A.3; G = 1.00
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.30
Variable favourable action - Table A.3; Qf = 0.00

Page 11 of 45 We are VINCI Energies, working together with National Grid.


Partial factors for spread foundations - Combination2
Resistance factor set; R1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00

Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 17.9 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 18.2 kN
Force in z-direction; Fdz = G  (A  Fswt + FGz1 + FGz2) = 152.9 kN

Moments on foundation
Moment in x-direction; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1 + FGz2  x2) + Q 
(MQx1 + MQx2) + (Q  (FQx1 + FQx2))  h = 326.9 kNm
Moment in y-direction; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1 + FGz2  y2) + Q 
(MQy1 + MQy2) + (Q  (FQy1 + FQy2))  h = 212.3 kNm

Eccentricity of base reaction


Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 438 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 489 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 2523 mm
Effective width; L'y = Ly - 2  ey = 822 mm
Effective area; A' = L'x  L'y = 2.074 m2

Pad base pressure


Design base pressure; fdz = Fdz / A' = 73.7 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 17.9 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 18.2 kN
Force in z-direction; Fdz = Gf  (A  Fswt + FGz1 + FGz2) = 152.9 kN

Sliding resistance verification (Section 6.5.3)


Horizontal force on foundation; H = [Fdx2 + Fdy2]0.5 = 25.6 kN
Design friction angle d = atan(tan(k) / ') = 16.234 deg
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(d) = 44.5 kN
H / RH.d = 0.574
PASS - Foundation is not subject to failure by sliding
Foundation design in accordance with EN1992-1-1:2004 + A1:2014 incorporating corrigenda January
2008, November 2010 and January 2014 and the UK National Annex incorporating National
Amendment No.1 and No.2
Tedds calculation version 3.3.05

Concrete details (Table 3.1 - Strength and deformation characteristics for concrete)
Concrete strength class; C32/40
Characteristic compressive cylinder strength; fck = 32 N/mm2
Characteristic compressive cube strength; fck,cube = 40 N/mm2
Mean value of compressive cylinder strength; fcm = fck + 8 N/mm2 = 40 N/mm2
Mean value of axial tensile strength; fctm = 0.3 N/mm2  (fck/ 1 N/mm2)2/3 = 3.0 N/mm2
5% fractile of axial tensile strength; fctk,0.05 = 0.7  fctm = 2.1 N/mm2
Secant modulus of elasticity of concrete; Ecm = 22 kN/mm2  [fcm/10 N/mm2]0.3 = 33346 N/mm2
Partial factor for concrete (Table 2.1N); C = 1.50

Page 12 of 45 We are VINCI Energies, working together with National Grid.


Compressive strength coefficient (cl.3.1.6(1)); cc = 0.85
Design compressive concrete strength (exp.3.15); fcd = cc  fck / C = 18.1 N/mm2
Tens.strength coeff.for plain concrete (cl.12.3.1(1)); ct,pl = 0.80
Des.tens.strength for plain concrete (exp.12.1); fctd,pl = ct,pl  fctk,0.05 / C = 1.1 N/mm2
Maximum aggregate size; hagg = 20 mm
Ultimate strain - Table 3.1; cu2 = 0.0035
Shortening strain - Table 3.1; cu3 = 0.0035
Effective compression zone height factor;  = 0.80
Effective strength factor;  = 1.00
Bending coefficient k1; K1 = 0.40
Bending coefficient k2; K2 = 1.00  (0.6 + 0.0014/cu2) =1.00
Bending coefficient k3; K3 =0.40
Bending coefficient k4; K4 =1.00  (0.6 + 0.0014/cu2) = 1.00

Reinforcement details
Characteristic yield strength of reinforcement; fyk = 500 N/mm2 Cover is too low,
Modulus of elasticity of reinforcement; Es = 210000 N/mm2 should be 50mm
Partial factor for reinforcing steel (Table 2.1N); S = 1.15 top and sides and
Design yield strength of reinforcement; fyd = fyk / S = 435 N/mm2 75 bottom.
Nominal cover to top of foundation; cnom_t = 30 mm
Nominal cover to bottom of foundation; cnom_b = 30 mm
Nominal cover to side of foundation; cnom_s = 30 mm
Nominal cover to top reinforcement; cnom_t = 30 mm

Rectangular section in flexure (Section 6.1)


Design bending moment; MEd.x.max = 31.7 kNm
Depth to tension reinforcement; d = h - cnom_b - y.bot - x.bot / 2 = 746 mm
K = MEd.x.max / (Ly  d2  fck) = 0.001
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))
K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 709 mm
Depth of neutral axis; x = 2.5  (d - z) = 93 mm
Area of tension reinforcement required; Asx.bot.req = MEd.x.max / (fyd  z) = 103 mm2

Page 13 of 45 We are VINCI Energies, working together with National Grid.


Tension reinforcement provided; 16  bars @ 150 c/c bottom
Area of tension reinforcement provided; Asx.bot.prov = 2413 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Ly  d = 2111
mm2
Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Ly  d = 53712 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm
Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; Msls.x.max = 5.8 kNm
Tensile stress in reinforcement; s = Msls.x.max / (Asx.bot.prov  z) = 3.4 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 135 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Ly = 243000 mm2
Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asx.bot.prov / Ac.eff = 0.010
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  (cnom_b + y.bot) + k1  k2  k4  x.bot / p.eff =
430 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0.004 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Rectangular section in flexure (Section 6.1)


Design bending moment; abs(MEd.x.min) = 33.7 kNm
Depth to tension reinforcement; d = h - cnom_t - y.top - x.top / 2 = 746 mm
K = abs(MEd.x.min) / (Ly  d2  fck) = 0.001
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))
K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 709 mm
Depth of neutral axis; x = 2.5  (d - z) = 93 mm
Area of tension reinforcement required; Asx.top.req = abs(MEd.x.min) / (fyd  z) = 109 mm2
Tension reinforcement provided; 16  bars @ 150 c/c top
Area of tension reinforcement provided; Asx.top.prov = 2413 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Ly  d = 2111
mm2
Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Ly  d = 53712 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm

Page 14 of 45 We are VINCI Energies, working together with National Grid.


Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; abs(Msls.x.min) = 9 kNm
Tensile stress in reinforcement; s = abs(Msls.x.min) / (Asx.top.prov  z) = 5.3 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 135 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Ly = 243000 mm2
Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asx.top.prov / Ac.eff = 0.010
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  (cnom_t + y.top) + k1  k2  k4  x.top / p.eff =
430 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0.006 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Rectangular section in shear (Section 6.2)


Design shear force; abs(VEd.x.min) = 37.3 kN
CRd,c = 0.18 / C = 0.120
k = min(1 + (200 mm / d), 2) = 1.518
Longitudinal reinforcement ratio; l = min(Asx.bot.prov / (Ly  d), 0.02) = 0.002
vmin = 0.035 N1/2/mm  k3/2  fck0.5 = 0.370 N/mm2
Design shear resistance (exp.6.2a & 6.2b); VRd.c = max(CRd.c  k  (100 N2/mm4  l  fck)1/3, vmin) 
Ly  d
VRd.c = 497.1 kN
PASS - Design shear resistance exceeds design shear force

Rectangular section in flexure (Section 6.1)


Design bending moment; MEd.y.max = 37.9 kNm
Depth to tension reinforcement; d = h - cnom_b - y.bot / 2 = 762 mm
K = MEd.y.max / (Lx  d2  fck) = 0.001
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))

Page 15 of 45 We are VINCI Energies, working together with National Grid.


K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 724 mm
Depth of neutral axis; x = 2.5  (d - z) = 95 mm
Area of tension reinforcement required; Asy.bot.req = MEd.y.max / (fyd  z) = 121 mm2
Tension reinforcement provided; 16  bars @ 150 c/c bottom
Area of tension reinforcement provided; Asy.bot.prov = 4624 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Lx  d = 4074
mm2
Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Lx  d = 103632 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm
Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; Msls.y.max = 10.7 kNm
Tensile stress in reinforcement; s = Msls.y.max / (Asy.bot.prov  z) = 3.2 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 95 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Lx = 323000 mm2
Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asy.bot.prov / Ac.eff = 0.014
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  cnom_b + k1  k2  k4  y.bot / p.eff = 292 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0.003 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Rectangular section in flexure (Section 6.1)


Design bending moment; abs(MEd.y.min) = 21.4 kNm
Depth to tension reinforcement; d = h - cnom_t - y.top / 2 = 762 mm
K = abs(MEd.y.min) / (Lx  d2  fck) = 0.000
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))
K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 724 mm
Depth of neutral axis; x = 2.5  (d - z) = 95 mm
Area of tension reinforcement required; Asy.top.req = abs(MEd.y.min) / (fyd  z) = 68 mm2
Tension reinforcement provided; 16  bars @ 150 c/c top
Area of tension reinforcement provided; Asy.top.prov = 4624 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Lx  d = 4074
mm2

Page 16 of 45 We are VINCI Energies, working together with National Grid.


Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Lx  d = 103632 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm
Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; abs(Msls.y.min) = 1.3 kNm
Tensile stress in reinforcement; s = abs(Msls.y.min) / (Asy.top.prov  z) = 0.4 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 95 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Lx = 323000 mm2
Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asy.top.prov / Ac.eff = 0.014
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  cnom_t + k1  k2  k4  y.top / p.eff = 292 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Punching shear (Section 6.4)


Strength reduction factor (exp 6.6N); v = 0.6  [1 - fck / 250 N/mm2] = 0.523
Average depth to reinforcement; d = 754 mm
Maximum punching shear resistance (cl.6.4.5(3)); vRd.max = 0.5  v  fcd = 4.744 N/mm2
k = min(1 + (200 mm / d), 2) = 1.515
Longitudinal reinforcement ratio (cl.6.4.4(1)); lx = Asx.bot.prov / (Ly  d) = 0.002
ly = Asy.bot.prov / (Lx  d) = 0.002
l = min((lx  ly), 0.02) = 0.002
CRd,c = 0.18 / C =0.120
vmin = 0.035 N1/2/mm  k3/2  fck0.5 = 0.369 N/mm2
Design punching shear resistance (exp.6.47); vRd.c = max(CRd.c  k  (100 N2/mm4  l  fck)1/3, vmin) =
0.369 N/mm2
Design punching shear resistance at 1d (exp. 6.50); vRd.c1 = (2  d / d)  vRd.c = 0.738 N/mm2
Column No.1 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 1320 mm
Area within punching shear perimeter; A0 = 0.107 m2
Maximum punching shear force; VEd.max = 25 kN
Punching shear stress factor (fig 6.21N);  = 1.500
Maximum punching shear stress (exp 6.38); vEd.max =   VEd.max / (u0  d) = 0.038 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress
Column No.1 - Punching shear perimeter at 1d from column face
Punching shear perimeter; u1 = 2360 mm
Area within punching shear perimeter; A1 = 2.203 m2
Design punching shear force; VEd.1 = 50.9 kN
Punching shear stress factor (fig 6.21N);  = 1.500

Page 17 of 45 We are VINCI Energies, working together with National Grid.


Design punching shear stress (exp 6.38); vEd.1 =   VEd.1 / (u1  d) = 0.043 N/mm2
PASS - Design punching shear resistance exceeds increased design punching shear stress
Column No.1 - Punching shear perimeter at 2d from column face
Punching shear perimeter; u2 = 1860 mm
Area within punching shear perimeter; A2 = 3.675 m2
Design punching shear force; VEd.2 = 22 kN
Punching shear stress factor (fig 6.21N);  = 1.500
Design punching shear stress (exp 6.38); vEd.2 =   VEd.2 / (u2  d) = 0.024 N/mm2
PASS - Design punching shear resistance exceeds design punching shear stress
Column No.2 - Punching shear perimeter at column face
Punching shear perimeter; u0 = 1320 mm
Area within punching shear perimeter; A0 = 0.107 m2
Maximum punching shear force; VEd.max = 19.2 kN
Punching shear stress factor (fig 6.21N);  = 1.500
Maximum punching shear stress (exp 6.38); vEd.max =   VEd.max / (u0  d) = 0.029 N/mm2
PASS - Maximum punching shear resistance exceeds maximum punching shear stress

Page 18 of 45 We are VINCI Energies, working together with National Grid.


3.3) Circuit breaker – Load Combination 2
Worst case upwards force, horizontal force and moment applied simultaneously.

Load onto each leg is as follows. See loading information on page 7:

Fzdead = -8.1kN / 2 = -4.05kN

Fximposed = 13.8kN / 2 = 6.9kN Fyimposed = 14kN / 2 = 7kN

Mximposed = 40.5kNm / 2 = 20.25kNm Myimposed = 46.3kNm / 2 = 23.15kNm

Foundation analysis in accordance with EN1997-1:2004 + A1:2013 incorporating corrigendum


February 2009 and the UK National Annex incorporating corrigendum No.1
Tedds calculation version 3.3.05

Pad foundation details


Length of foundation; Lx = 3400 mm
Width of foundation; Ly = 1800 mm
Foundation area; A = Lx  Ly = 6.120 m2
Depth of foundation; h = 800 mm
Depth of soil over foundation; hsoil = 0 mm
Level of water; hwater = 0 mm
Density of water; water = 9.8 kN/m3
Density of concrete; conc = 24.5 kN/m3

Column no.1 details


Length of column; lx1 = 290 mm
Width of column; ly1 = 370 mm
position in x-direction; x1 = 435 mm
position in y-direction; y1 = 900 mm
Column no.2 details
Length of column; lx2 = 290 mm
Width of column; ly2 = 370 mm
position in x-direction; x2 = 2965 mm
position in y-direction; y2 = 900 mm

Page 19 of 45 We are VINCI Energies, working together with National Grid.


Soil properties
Density of soil; soil = 18.0 kN/m3
Characteristic cohesion; c'k = 0 kN/m2
Characteristic effective shear resistance angle; 'k = 30 deg
Characteristic friction angle; k = 20 deg

Foundation loads
Self weight; Fswt = h  conc = 19.6 kN/m2

Column no.1 loads


Permanent axial load; FGz1 = -4.0 kN
Variable horizontal load in x-direction; FQx1 = 6.9 kN
Variable horizontal load in y-direction; FQy1 = 7.0 kN
Variable moment in x-direction; MQx1 = 20.3 kNm
Variable moment in y-direction; MQy1 = 23.2 kNm
Column no.2 loads
Permanent axial load; FGz2 = -4.0 kN
Variable horizontal load in x-direction; FQx2 = 6.9 kN
Variable horizontal load in y-direction; FQy2 = 7.0 kN
Variable moment in x-direction; MQx2 = 20.3 kNm
Variable moment in y-direction; MQy2 = 23.2 kNm
Bearing resistance (Section 6.5.2)
Forces on foundation
Force in x-direction; Fdx = FQx1 + FQx2 = 13.8 kN
Force in y-direction; Fdy = FQy1 + FQy2 = 14.0 kN
Force in z-direction; Fdz = A  Fswt + FGz1 + FGz2 = 111.9 kN

Moments on foundation
Moment in x-direction; Mdx = A  Fswt  Lx / 2 + FGz1  x1 + FGz2  x2 + MQx1 +
FQx1  h + MQx2 + FQx2  h = 241.7 kNm
Moment in y-direction; Mdy = A  Fswt  Ly / 2 + FGz1  y1 + FGz2  y2 + MQy1 +
FQy1  h + MQy2 + FQy2  h = 158.2 kNm

Eccentricity of base reaction


Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 461 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 514 mm
The extent of the footing acting in bearing has been determined using an iterative procedure. The volume of
the resulting bearing pressure diagram is equal in magnitude to the applied axial load and its centroid
coincides with the location of the resultant applied load. More details on the procedure adopted can be found
in the paper ‘Bearing pressures for rectangular footings with biaxial uplift’ by Kenneth E Wilson.
Pad base pressures
q1 = 0 kN/m2
q2 = 34.2 kN/m2
q3 = 0 kN/m2
q4 = 85.3 kN/m2
Minimum base pressure; qmin = min(q1, q2, q3, q4) = 0 kN/m2
Maximum base pressure; qmax = max(q1, q2, q3, q4) = 85.3 kN/m2
Presumed bearing capacity
Presumed bearing capacity; Pbearing = 100.0 kN/m2
PASS - Presumed bearing capacity exceeds design base pressure

Page 20 of 45 We are VINCI Energies, working together with National Grid.


Design approach 1
Partial factors on actions - Combination1
Partial factor set; A1
Permanent unfavourable action - Table A.3; G = 1.35
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.50
Variable favourable action - Table A.3; Qf = 0.00

Partial factors for spread foundations - Combination1


Resistance factor set; R1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00

Forces on foundation
Force in x-direction; Fdx = Qf  (FQx1 + FQx2) = 0.0 kN
Force in y-direction; Fdy = Qf  (FQy1 + FQy2) = 0.0 kN
Force in z-direction; Fdz = G  A  Fswt + Gf  (FGz1 + FGz2) = 153.8 kN

Moments on foundation
Moment in x-direction; Mdx = G  A  Fswt  Lx / 2 + Gf  (FGz1  x1 + FGz2  x2)
+ Qf  (MQx1 + MQx2) + (Qf  (FQx1 + FQx2))  h = 261.5
kNm
Moment in y-direction; Mdy = G  A  Fswt  Ly / 2 + Gf  (FGz1  y1 + FGz2  y2)
+ Qf  (MQy1 + MQy2) + (Qf  (FQy1 + FQy2))  h = 138.5
kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 0 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 3400 mm
Effective width; L'y = Ly - 2  ey = 1800 mm
Effective area; A' = L'x  L'y = 6.120 m2
Pad base pressure
Design base pressure; fdz = Fdz / A' = 25.1 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 20.7 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 21.0 kN
Force in z-direction; Fdz = Gf  A  Fswt + G  (FGz1 + FGz2) = 109.0 kN

Sliding resistance verification (Section 6.5.3)


Horizontal force on foundation; H = [Fdx2 + Fdy2]0.5 = 29.5 kN
Design friction angle d = atan(tan(k) / ') = 20 deg
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(d) = 39.7 kN
H / RH.d = 0.743
PASS - Foundation is not subject to failure by sliding
Design approach 1
Partial factors on actions - Combination2
Partial factor set; A2
Permanent unfavourable action - Table A.3; G = 1.00

Page 21 of 45 We are VINCI Energies, working together with National Grid.


Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.30
Variable favourable action - Table A.3; Qf = 0.00

Partial factors for spread foundations - Combination2


Resistance factor set; R1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00

Forces on foundation
Force in x-direction; Fdx = Qf  (FQx1 + FQx2) = 0.0 kN
Force in y-direction; Fdy = Qf  (FQy1 + FQy2) = 0.0 kN
Force in z-direction; Fdz = G  A  Fswt + Gf  (FGz1 + FGz2) = 111.9 kN

Moments on foundation
Moment in x-direction; Mdx = G  A  Fswt  Lx / 2 + Gf  (FGz1  x1 + FGz2  x2)
+ Qf  (MQx1 + MQx2) + (Qf  (FQx1 + FQx2))  h = 190.1
kNm
Moment in y-direction; Mdy = G  A  Fswt  Ly / 2 + Gf  (FGz1  y1 + FGz2  y2)
+ Qf  (MQy1 + MQy2) + (Qf  (FQy1 + FQy2))  h = 100.7
kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-direction; ex = Mdx / Fdz - Lx / 2 = 0 mm
Eccentricity of base reaction in y-direction; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 3400 mm
Effective width; L'y = Ly - 2  ey = 1800 mm
Effective area; A' = L'x  L'y = 6.120 m2

Pad base pressure


Design base pressure; fdz = Fdz / A' = 18.3 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-direction; Fdx = Q  (FQx1 + FQx2) = 17.9 kN
Force in y-direction; Fdy = Q  (FQy1 + FQy2) = 18.2 kN
Force in z-direction; Fdz = Gf  A  Fswt + G  (FGz1 + FGz2) = 111.9 kN

Sliding resistance verification (Section 6.5.3)


Horizontal force on foundation; H = [Fdx2 + Fdy2]0.5 = 25.6 kN
Design friction angle d = atan(tan(k) / ') = 16.234 deg
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(d) = 32.6 kN
H / RH.d = 0.785
PASS - Foundation is not subject to failure by sliding
Partial factors for uplift limit state - Table A.NA.15
Permanent unfavourable action; G.dst = 1.10
Permanent favourable action; G.stb = 0.90
Variable unfavourable action; Q.dst = 1.50
Variable favourable action; Q.stb = 0.00

Uplift limit state verification


Vertical force; Fdz.u = G.stb  A  Fswt + G.dst  (FGz1 + FGz2) = 99.0 kN
PASS - Foundation is not subject to failure by uplift

Page 22 of 45 We are VINCI Energies, working together with National Grid.


Foundation design in accordance with EN1992-1-1:2004 + A1:2014 incorporating corrigenda January
2008, November 2010 and January 2014 and the UK National Annex incorporating National
Amendment No.1 and No.2
Tedds calculation version 3.3.05

Concrete details (Table 3.1 - Strength and deformation characteristics for concrete)
Concrete strength class; C32/40
Characteristic compressive cylinder strength; fck = 32 N/mm2
Characteristic compressive cube strength; fck,cube = 40 N/mm2
Mean value of compressive cylinder strength; fcm = fck + 8 N/mm2 = 40 N/mm2
Mean value of axial tensile strength; fctm = 0.3 N/mm2  (fck/ 1 N/mm2)2/3 = 3.0 N/mm2
5% fractile of axial tensile strength; fctk,0.05 = 0.7  fctm = 2.1 N/mm2
Secant modulus of elasticity of concrete; Ecm = 22 kN/mm2  [fcm/10 N/mm2]0.3 = 33346 N/mm2
Partial factor for concrete (Table 2.1N); C = 1.50
Compressive strength coefficient (cl.3.1.6(1)); cc = 0.85
Design compressive concrete strength (exp.3.15); fcd = cc  fck / C = 18.1 N/mm2
Tens.strength coeff.for plain concrete (cl.12.3.1(1)); ct,pl = 0.80
Des.tens.strength for plain concrete (exp.12.1); fctd,pl = ct,pl  fctk,0.05 / C = 1.1 N/mm2
Maximum aggregate size; hagg = 20 mm
Ultimate strain - Table 3.1; cu2 = 0.0035
Shortening strain - Table 3.1; cu3 = 0.0035
Effective compression zone height factor;  = 0.80
Effective strength factor;  = 1.00
Bending coefficient k1; K1 = 0.40
Bending coefficient k2; K2 = 1.00  (0.6 + 0.0014/cu2) =1.00
Bending coefficient k3; K3 =0.40
Bending coefficient k4; K4 =1.00  (0.6 + 0.0014/cu2) = 1.00

Reinforcement details
Characteristic yield strength of reinforcement; fyk = 500 N/mm2
Modulus of elasticity of reinforcement; Es = 210000 N/mm2
Partial factor for reinforcing steel (Table 2.1N); S = 1.15
Design yield strength of reinforcement; fyd = fyk / S = 435 N/mm2
Nominal cover to top of foundation; cnom_t = 30 mm
Cover is too low,
Nominal cover to bottom of foundation; cnom_b = 30 mm should be 50mm
Nominal cover to side of foundation; cnom_s = 30 mm top and sides and
Nominal cover to top reinforcement; cnom_t = 30 mm 75 bottom.

Page 23 of 45 We are VINCI Energies, working together with National Grid.


Rectangular section in flexure (Section 6.1)
Design bending moment; MEd.x.max = 1.7 kNm
Depth to tension reinforcement; d = h - cnom_b - x.bot / 2 = 762 mm
K = MEd.x.max / (Ly  d2  fck) = 0.000
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))
K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 724 mm
Depth of neutral axis; x = 2.5  (d - z) = 95 mm
Area of tension reinforcement required; Asx.bot.req = MEd.x.max / (fyd  z) = 5 mm2
Tension reinforcement provided; 16  bars @ 150 c/c bottom
Area of tension reinforcement provided; Asx.bot.prov = 2413 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Ly  d = 2157
mm2
Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Ly  d = 54864 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm
Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; Msls.x.max = 1.7 kNm
Tensile stress in reinforcement; s = Msls.x.max / (Asx.bot.prov  z) = 1 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 95 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Ly = 171000 mm2
Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asx.bot.prov / Ac.eff = 0.014
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  cnom_b + k1  k2  k4  x.bot / p.eff = 295 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0.001 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Page 24 of 45 We are VINCI Energies, working together with National Grid.


Rectangular section in shear (Section 6.2)
Design shear force; VEd.x.max = 0.9 kN
CRd,c = 0.18 / C = 0.120
k = min(1 + (200 mm / d), 2) = 1.518
Longitudinal reinforcement ratio; l = min(Asx.bot.prov / (Ly  d), 0.02) = 0.002
vmin = 0.035 N1/2/mm  k3/2  fck0.5 = 0.370 N/mm2
Design shear resistance (exp.6.2a & 6.2b); VRd.c = max(CRd.c  k  (100 N2/mm4  l  fck)1/3, vmin) 
Ly  d
VRd.c = 497.1 kN
PASS - Design shear resistance exceeds design shear force

Rectangular section in flexure (Section 6.1)


Design bending moment; abs(MEd.y.min) = 1.2 kNm
Depth to tension reinforcement; d = h - cnom_t - x.top - y.top / 2 = 746 mm
K = abs(MEd.y.min) / (Lx  d2  fck) = 0.000
K' = (2    cc/C)(1 -   ( - K1)/(2  K2))(  ( -
K1)/(2  K2))
K' = 0.207
K' > K - No compression reinforcement is required
Lever arm; z = min(0.5 + 0.5  (1 - 2  K / (  cc / C))0.5, 0.95)  d
= 709 mm
Depth of neutral axis; x = 2.5  (d - z) = 93 mm
Area of tension reinforcement required; Asy.top.req = abs(MEd.y.min) / (fyd  z) = 4 mm2
Tension reinforcement provided; 16  bars @ 150 c/c top
Area of tension reinforcement provided; Asy.top.prov = 4624 mm2
Minimum area of reinforcement (exp.9.1N); As.min = max(0.26  fctm / fyk, 0.0013)  Lx  d = 3988
mm2
Maximum area of reinforcement (cl.9.2.1.1(3)); As.max = 0.04  Lx  d = 101456 mm2
PASS - Area of reinforcement provided is greater than area of reinforcement required
Crack control (Section 7.3)
Limiting crack width; wmax = 0.3 mm
Variable load factor (EN1990 – Table A1.1); 2 = 0.3
Serviceability bending moment; abs(Msls.y.min) = 1.2 kNm
Tensile stress in reinforcement; s = abs(Msls.y.min) / (Asy.top.prov  z) = 0.4 N/mm2
Load duration factor; kt = 0.4
Effective depth of concrete in tension; hc.ef = min(2.5  (h - d), (h - x) / 3, h / 2) = 135 mm
Effective area of concrete in tension; Ac.eff = hc.ef  Lx = 459000 mm2

Page 25 of 45 We are VINCI Energies, working together with National Grid.


Mean value of concrete tensile strength; fct.eff = fctm = 3.0 N/mm2
Reinforcement ratio; p.eff = Asy.top.prov / Ac.eff = 0.010
Modular ratio; e = Es / Ecm = 6.298
Bond property coefficient; k1 = 0.8
Strain distribution coefficient; k2 = 0.5
k3 = 3.4 =3.4
k4 = 0.425
Maximum crack spacing (exp.7.11); sr.max = k3  (cnom_t + x.top) + k1  k2  k4  y.top / p.eff =
426 mm
Maximum crack width (exp.7.8); wk = sr.max  max([s – kt  (fct.eff / p.eff) (1 + e  p.eff)] /
Es,
0.6  s / Es) = 0 mm
PASS - Maximum crack width is less than limiting crack width
Library item: Crack width output

Punching shear (Section 6.4)


Strength reduction factor (exp 6.6N); v = 0.6  [1 - fck / 250 N/mm2] = 0.523
Average depth to reinforcement; d = 746 mm
Maximum punching shear resistance (cl.6.4.5(3)); vRd.max = 0.5  v  fcd = 4.744 N/mm2
k = min(1 + (200 mm / d), 2) = 1.518
Longitudinal reinforcement ratio (cl.6.4.4(1)); lx = Asx.bot.prov / (Ly  d) = 0.002
ly = Asy.bot.prov / (Lx  d) = 0.002
l = min((lx  ly), 0.02) = 0.002
CRd,c = 0.18 / C =0.120
vmin = 0.035 N1/2/mm  k3/2  fck0.5 = 0.370 N/mm2
Design punching shear resistance (exp.6.47); vRd.c = max(CRd.c  k  (100 N2/mm4  l  fck)1/3, vmin) =
0.370 N/mm2
Design punching shear resistance at 1d (exp. 6.50); vRd.c1 = (2  d / d)  vRd.c = 0.740 N/mm2
Column No.1 - Punching shear perimeter at 2d from column face
Punching shear perimeter; u2 = 1861 mm
Area within punching shear perimeter; A2 = 3.645 m2
Design punching shear force; VEd.2 = 0.8 kN
Punching shear stress factor (fig 6.21N);  = 1.500
Design punching shear stress (exp 6.38); vEd.2 =   VEd.2 / (u2  d) = 0.001 N/mm2
PASS - Design punching shear resistance exceeds design punching shear stress
Column No.2 - Punching shear perimeter at 2d from column face
Punching shear perimeter; u2 = 1861 mm
Area within punching shear perimeter; A2 = 3.645 m2
Design punching shear force; VEd.2 = 0.8 kN
Punching shear stress factor (fig 6.21N);  = 1.500
Design punching shear stress (exp 6.38); vEd.2 =   VEd.2 / (u2  d) = 0.001 N/mm2
PASS - Design punching shear resistance exceeds design punching shear stress

Page 26 of 45 We are VINCI Energies, working together with National Grid.


Page 27 of 45 We are VINCI Energies, working together with National Grid.
3.4) Overturning Check - Circuit Breaker
Note: Forces below are unfactored and have been ascertained from loading information
provided by GE Grid Solutions. Please refer to Appendix A for details

Applied overturning moment in X direction:


40.5kNm + 13.8kN x 0.8m = 51.54kNm
(see page 7)

Overturning resistance:
(25 x 3.4m x 1.8m x 0.8m x 1.7m x 0.9) + ((5.3kN x 0.9) x 0.435m)
+ ((5.3kN x 0.9) x 2.965m)
= 203.49KNm
FOS = 203.49kNm / 51.54kNm = 3.95, therefore accept.

Applied overturning moment in Y direction:


46.3kNm + 14kN x 0.8m = 57.5kNm
(see page 7)

Overturning resistance:
(25 x 3.4m x 1.8m x 0.8m x 0.9m x 0.9) + ((10.6kN x 0.9) x 0.9m)
= 107.73KNm
FOS = 107.73kNm / 57.5kNm = 1.87, therefore accept. moment?
is this split over two
base plates?
What bolt diameter
3.5) Holding down bolt design has been
considered?
Check on uplift: please include full
tedds calc.
Axial force; Fc = ;33.9; kN (Compression)
Characteristic strength of concrete; fcu = 30 N/mm2
Effective width of plate; Bpc = min(Bp, B + 2L1) = ;310.0; mm
Depth of compression block; x = [-1.0b - (b2 - 4ac)]/(2a) = 28.6 mm
Compression force in concrete; Cf = 0.6  fcu  Bpc  x = 159.8 kN

Tension force in bolts; Tf = Cf - Fc = 125.9 kN


Holding down bolt anchorage
Note - the following calculation to check the holding down bolt anchorage into the foundation assumes that
the distance from the edge of an anchor plate to the nearest edge of the foundation is at least equal to the
depth of embedment of the anchor plate.
Tension force to be resisted; Ft = Tf = 125.9 kN
The clear distance between anchor plates is less than the embedment (E).

Page 28 of 45 We are VINCI Energies, working together with National Grid.


Effective concrete plan area; Aplan_eff = [sbolt(Nbolt/2-
1)+bap](bap+2E)+E2+2bapE-(Nbolt/2)bap2
Aplan_eff = 859655 mm2
For tension failure pull-out, effective tensile area; At_eff = Aplan_eff = 859655 mm2
Tensile strength of concrete; pt = 1.45 N/mm2
Pull-out capacity of tension bolts; Pt = pt  At_eff = 1246.5 kN
PASS - Holding down bolt anchorage is adequate (0.101)
Shear transfer to concrete
Assumed coefficient of friction;  = 0.30
Available shear resistance; Pv = Cf   = ;48; kN
PASS - Frictional shear capacity is adequate (0.292)

Check on shear:
By inspection, M24 bolt is adequate in shear for a shear force of 1.8kN
doesn't the
(see loadings in Appendix B) calculation check
shear?

In the case of the the load being applied diagonally on the baseplate, the resultant moment
is to be found and capacity for one holding down bolt to resist this resultant moment.
Mx = 40.5 kNm
Do these need to
My = 46.3 kNm
be divided by 2?
Mresultant = √(40.52 + 46.32) = 61.5 kNm
lever arm = √(3102 + 2302) = 386mm
Tension pull-out = 615kNm x 103 / 386mm = 159 kN

Holding down bolts


Capacity of one bolt in isolation:
Tensile area per bolt; At_b = 353.0 mm2
Tensile strength; pt_b = 560 N/mm2
Tension capacity (cl.6.3.4.3); Pt_b = pt_b ´ At_b = ;197.7; kN;
Capacity of 1 bolt with concrete pull-out resistance:

Pull-out capacity of tension bolts; Pt = pt  At_eff = 1246.5 kN / 4No. bolts


= 311.6kN
Therefore, bolt in isolation governs.
FOS = 197.7kN / 159kN = 1.24, hence holding down bolt OK

It is noted from our calculations that baseplates are failing in bending and bolt edge
distances. Baseplate design is by others.

Page 29 of 45 We are VINCI Energies, working together with National Grid.


3.6) Design summary

Pad width – 1.8 m


Pad length – 3.4 m
Pad depth – 0.8 m
Concrete grade – RC 32/40
Steel reinforcement – H16 bars at 150mm centres both directions on top and bottom
Top cover – 50mm
Side cover – 50mm
Bottom cover – 75mm

Page 30 of 45 We are VINCI Energies, working together with National Grid.


3.7) Concrete Specification

CONCRETE SPECIFICATION
In accordance with BS8500-1:2015 + A2:2019 incorporating corrigenda No.1 and No.2
Tedds calculation version 1.1.01

Element definition
Element description; Biggleswade Pad Foundations
Intended working life; At least 100 years
Type of concrete; Reinforced, normal weight
Maximum aggregate size 20 mm
Allowance for deviation between minimum and nominal covers
cdev = 10 mm
Allowance for deviation (XA class); cdev_s = 10 mm

Exposure classes
Corrosion induced by carbonation (XC classes) - Table A.1
Class description; Dry or permanently wet
Class designation; XC1
Freeze/thaw attack (XF classes) - Table A.1
Class description; Moderate water saturation without de-icing agent
Class designation; XF1
Chemical attack (XA classes) - Table A.10
ACEC class; AC-1s
Section width; t = 800 mm
Hydraulic gradient (note B); Less than or equal to 5
Design chemical class; DC-1

Concrete requirements and specification


Consistence class S3
Minimum allowable nominal covers
For exposure class XC1 - Table A.5 25 mm
For design chemical class DC-1 - Table A.10 35 mm
Specified nominal cover 50 mm
PASS - The specified nominal cover is adequate
Minimum strength class with 50 mm cover
For exposure class XC1 - Table A.5 C20/25
For exposure class XF1 - Table A.9 C28/35
For design chemical class DC-1 - Table A.12 C25/30
Specified strength class C32/40
PASS - The specified strength class is adequate
Maximum water/cement ratio with 50 mm cover, 20 mm aggregate and C32/40 concrete
For exposure class XC1 - Table A.5 0.70
For exposure class XF1 - Table A.9 0.60
For design chemical class DC-1 - Table A.12 0.65
Specified maximum water/cement ratio 0.55
PASS - The specified maximum water cement ratio is acceptable
Minimum cement content with 50 mm cover and C32/40 concrete
For exposure class XC1 - Table A.5 240 kg/m3

Page 31 of 45 We are VINCI Energies, working together with National Grid.


For exposure class XF1 - Table A.9 280 kg/m3
For design chemical class DC-1 - Table A.12 260 kg/m3
For water/cement ratio of 0.55 - Table A.7 300 kg/m3
Specified minimum cement content 320 kg/m3
PASS - The specified minimum cement content is adequate
Recommended cements/combinations with 50 mm cover and C32/40 concrete
For exposure class XC1 - Table A.5 All in Table A.6
For exposure class XF1 - Table A.9 All in Table A.6
For design chemical class DC-1 - Table A.12 All in Table A.6
Recommended cement/combinations types CEM I, CEM I-SR0, CEM I-SR3, IIA, IIB-M, IIB-S, IIB-P,
IIB-Q, IIB-V, IIB-P + SR, IIB-Q + SR, IIB-V + SR, IIIA,
IIIA + SR, IIIB, IIIB + SR,IVB-P, IVB-Q, IVB-V

Designed concrete specification for Biggleswade Pad Foundations with 50 mm cover


The concrete shall be produced in accordance with BS8500-2.
Compressive strength class; C32/40
Maximum water/cement ratio; 0.55
Minimum cement/combination content; 320 kg/m3
Recommended cement/combinations types CEM I, CEM I-SR0, CEM I-SR3, IIA, IIB-M, IIB-S, IIB-P,
IIB-Q, IIB-V, IIB-P + SR, IIB-Q + SR, IIB-V + SR, IIIA,
IIIA + SR, IIIB, IIIB + SR,IVB-P, IVB-Q, IVB-V (DC-1)
Maximum aggregate size 20 mm
Chloride content class Cl 0, 40
Consistence class S3

Page 32 of 45 We are VINCI Energies, working together with National Grid.


Appendix A
Manufacturers Drawing Information

Page 33 of 45 We are VINCI Energies, working together with National Grid.


Page 34 of 45 We are VINCI Energies, working together with National Grid.
Page 35 of 45 We are VINCI Energies, working together with National Grid.
Page 36 of 45 We are VINCI Energies, working together with National Grid.
Page 37 of 45 We are VINCI Energies, working together with National Grid.
Page 38 of 45 We are VINCI Energies, working together with National Grid.
Page 39 of 45 We are VINCI Energies, working together with National Grid.
Page 40 of 45 We are VINCI Energies, working together with National Grid.
Appendix B
Email Correspondence on Loading Confirmation

Page 41 of 45 We are VINCI Energies, working together with National Grid.


Page 42 of 45 We are VINCI Energies, working together with National Grid.
Page 43 of 45 We are VINCI Energies, working together with National Grid.
Page 44 of 45 We are VINCI Energies, working together with National Grid.
Page 45 of 45 We are VINCI Energies, working together with National Grid.

You might also like