You are on page 1of 32

Customer: THIQAR OIL COMPANY (TOC)

DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA


Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 1 / 32

CAUSE & EFFECT MATRIX


ESD

Firmato digitalmente da Maikel Tosti Alessandro Firmato digitalmente da Alessandro


Leandri Firmato digitalmente da Marco Ferioli

Maikel Tosti Marco Ferioli


ND: cn=Alessandro Leandri, o, ou, ND: cn=Marco Ferioli, o, ou,
Leandri
ND: cn=Maikel Tosti, o, ou, email=leandri.a@pegitaly.it, c=IT
email=tosti.m@pegitaly.it, c=IT email=ferioli.m@pegitaly.it, c=IT
Data: 2020.09.22 10:34:32 +02'00'
Data: 2020.09.22 10:34:03 +02'00' Data: 2020.09.22 10:34:43 +02'00'

01 16/09/2020 FINAL ISSUE M. TOSTI A.LEANDRI M. FERIOLI


Mod. ST0003_0/xls

00 27/11/2019 FIRST ISSUE M. TOSTI A.LEANDRI M. FERIOLI

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED/AUTHORIZED

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 2 / 32
REV

1 LEGEND
CCR CENTRAL CONTROL ROOM LAH LEVEL ALARM HIGH PDALL PRESS. DIFF. ALARM LOW LOW XL GENERAL STATUS INDICATION
DCS DISTRIBUTED CONTROL SYSTEM LAHH LEVEL ALARM HIGH HIGH PDIC PRESS. DIFF. INDICATOR CONTROLLER XLR LOCAL / REMOTE STATUS
EAHH VOLTAGE ALARM HIGH HIGH LAL LEVEL ALARM LOW PDIT PRESS. DIFF. INDICATOR TRANSMITTER XR RUNNING STATUS
ESD EMERGENCY SHUTDOWN SYSTEM LALL LEVEL ALARM LOW LOW PIC PRESSURE INDICATOR CONTROLLER XS TRIP SWITCH
ESDV EMERGENCY SHUTDOWN VALVE LCP LOCAL CONTROL PANEL PIT PRESSURE INDICATOR TRANSMITTER XZIC POSITION INDICATOR "CLOSED STATUS"
FAH FLOW ALARM HIGH LIC LEVEL INDICATOR CONTROLLER POS PROCESS OVERRIDE SWITCH XZIO POSITION INDICATOR "OPEN STATUS"
FAHH FLOW ALARM HIGH HIGH LIT LEVEL INDICATOR TRANSMITTER SDHS COMMON ESD HAND SWITCH
FAL FLOW ALARM LOW MCC MOTOR CONTROL CENTER TAH TEMPERATURE ALARM HIGH
FALL FLOW ALARM LOW LOW MCP MAIN CONTROL PANEL TAHH TEMPERATURE ALARM HIGH HIGH
FM CLOSE FORCE MANUAL CLOSE MOS MAINTENANCE OVERRIDE SWITCH TAL TEMPERATURE ALARM LOW
FM OPEN FORCE MANUAL OPEN P PUMP TALL TEMPERATURE ALARM LOW LOW
FIC FLOW INDICATOR CONTROLLER PAH PRESSURE ALARM HIGH TIC TEMPERATURE INDICATOR CONTROLLER
FIT FLOW INDICATOR TRANSMITTER PAHH PRESSURE ALARM HIGH HIGH TIT TEMPERATURE INDICATOR TRANSMITTER
HLR HAND OPERATED "LOCAL / REMOTE" SWITCH PAL PRESSURE ALARM LOW UCP UNIT CONTROL PANEL
HS HAND OPERATED SWITCH / PUSHBUTTON PALL PRESSURE ALARM LOW LOW VAH VIBRATION ALARM HIGH
HSH PUSHBUTTON "START" PB PUSH BUTTON VAHH VIBRATION ALARM HIGH HIGH
HSL PUSHBUTTON "STOP" PDAH PRESS. DIFF. ALARM HIGH VIT VIBRATION INDICATOR TRANSMITTER
IAHH CURRENT ALARM HIGH HIGH PDAHH PRESS. DIFF. ALARM HIGH HIGH XA STATUS ALARM
KOD KNOCK OUT DRUM PDAL PRESS. DIFF. ALARM LOW XF FAULT STATUS

2 REFERENCE DOCUMENTS
A) PROCESS CONTROL PHILOSOPHY : DOC. N° PE14017AR-00-GSD-0002-01
B) PROCESS & INSTRUMENTATION DIAGRAMS : AS INDICATED IN THE RESPECTIVE SHEET

3 GENERAL NOTES
A) CAUSE AND EFFECT DIAGRAM FOR CHEMICAL INJECTION PACKAGES, AUTOMATIC SELF CLEANING FILTER, AND INDIRECT OIL HEATER PACKAGE WILL BE DEVELOPPED AND FURNISHED BY THE RESPECTIVE PACKAGE VENDORS.
B) MAINTENANCE OVERRIDE SWITCH (MOS)
- ONCE THE RESPECTIVE MOS IS ENABLED, THE INDIVIDUAL OVERRIDE FUNCTION FOR EACH INSTRUMENT SHALL BE CARRIED OUT FROM THE OPERATOR WORK STATION WITH PROCESS ACCESS PROTECTION.
- OPERATOR WORK STATION SHALL BE CONFIGURED WITH MOS GRAPHICS PAGE WITH PROPER ACCESS PROTECTION LEVEL FOR MAINTENANCE PERSONNEL
C) RESET PHILOSOPHY
- ALL RESET ESD ACTIONS SHALL HAVE DEDICATED REMOTE RESET
- ALL FIELD RESET ACTIONS HAVE A DEDICATED FIELD RESET
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Mod. ST0003_0/xls


REV

NOTES:

TAG N°

108-HS-00
108-XST-92
DESCRIPTION:

2. TO EXISTING ESD
GENERAL UNIT SHUT-DOWN

EXISTING TRAIN TRIP COMMAND


1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

GENERAL TRIP (SOFTWARE PUSH BUTTON ON ESD)


DESCRIPTION

MOS
MOS
MOS/POS
CAUSES OF INTERLOCK ACTIVATION
VOTING

01-PID-0021-08
01-PID-0021-08
P&ID N° / LOCATION
NOTES

EFFECTS OF INTERLOCK ACTION

TAG N° DESCRIPTION ACTION P&ID N° / LOCATION NOTES

102-ESDV-01 ESDV ON OIL OUTLET OF DEHYDRATOR 01-V-001 CLOSE 01-PID-0021-02


X
X

104-ESDV-01 ESDV ON OIL OUTLET OF DESALTER 01-V-004 CLOSE 01-PID-0021-04


X
X

107-ESDV-01 ESDV ON DISCHARGE OF PUMPS 01-P-002A/S CLOSE 01-PID-0021-07


X
X

107-ESDV-02 ESDV ON PRODUCED WATER OUTLET OF 01-E-002 CLOSE 01-PID-0021-07


X
X

108-ESDV-01 ESDV ON DISCHARGE OF PUMPS 01-P-001A/S CLOSE 01-PID-0021-08


X
X

108-ESDV-02 ESDV ON SUCTION OF PUMPS 01-P-001A/S CLOSE 01-PID-0021-08


X
X

108-ESDV-03 ESDV ON BY-PASS OF PUMPS 01-P-001A/S CLOSE 01-PID-0021-08


X
X

302-ESDV-01 ESDV ON WATER OUTLET OF COALESCER 03-F-003 CLOSE 03-PID-0021-02


X
X

303-ESDV-01 ESDV ON DISCHARGE OF PUMPS 03-P-001A/S CLOSE 03-PID-0021-03


X
X

102-XST-91 DEHYDRATOR TRANSFORMER "A" TRIP 01-PID-0021-02


X
X
INTERLOCK ESD-01

102-XST-92 DEHYDRATOR TRANSFORMER "B" TRIP 01-PID-0021-02


X
X

104-XST-91 DESALTER TRANSFORMER "A" TRIP 01-PID-0021-04


X
X

104-XST-92 DESALTER TRANSFORMER "B" TRIP 01-PID-0021-04


X
X

105-XST-90 INDIRECT OIL HEATER PACKAGE TRIP 01-PID-0021-05


X
X

108-XST-91 DEHYDRATION AND DESALTING UNIT TRIP STATUS INDICATION 01-PID-0021-08 NOTE 2
X
X

401-XST-90 DEMULSIFIER INJECTION PACKAGE TRIP 04-PID-0021-01


X
X

402-XST-90 CORROSION INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-02


X
X

403-XST-90 SCALE INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-03


X
X

01-PM-001A MOTOR OF CHARGE PUMP 01-P-001A TRIP 01-PID-0021-08


X
X

01-PM-001S MOTOR OF CHARGE PUMP 01-P-001S TRIP 01-PID-0021-08


X
X

01-PM-002A MOTOR OF FRESH WATER PUMP 01-P-002A TRIP 01-PID-0021-09


X
X

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
01-PM-002S MOTOR OF FRESH WATER PUMP 01-P-002S TRIP 01-PID-0021-09
X
X
Plant:

01-PM-003A MOTOR OF RECYCLE WATER PUMP 01-P-003A TRIP 01-PID-0021-10


X
X
Location:
Customer:

01-PM-003S MOTOR OF RECYCLE WATER PUMP 01-P-003S TRIP 01-PID-0021-10


X
X

02-PM-001A MOTOR OF DRAIN PUMP 02-P-001A TRIP 02-PID-0021-01


X
X
Project

02-PM-001S MOTOR OF DRAIN PUMP 02-P-001S TRIP 02-PID-0021-01


X
X
PE14017AR

03-PM-001A MOTOR OF EFFLUENT WATER PUMP 03-P-001A TRIP 03-PID-0021-03


X
X

03-PM-001S MOTOR OF EFFLUENT WATER PUMP 03-P-001S TRIP 03-PID-0021-03


X
X

03-PM-002A MOTOR OF SUMP PUMP 03-P-002A TRIP 03-PID-0021-04


X
X
00
Unit

03-PM-002S MOTOR OF SUMP PUMP 03-P-002S TRIP 03-PID-0021-04


X
X

101-LIC-01 LEVEL CONTROL OF DEHYDRATOR DEGASSER 01-V-001 FM CLOSE 01-PID-0021-01 / 03 NOTE 1


X
X
DEGASSING STATION

101-PIC-01 PRESS. CONTROL OF DEHYDRATOR DEGASSER 01-V-001 FM OPEN 01-PID-0021-02 NOTE 1


X
X
NASSIRIYA FIELD - IRAQ

102-LIC-01 INTERFACE LEVEL CONTROL OF DEHYDRATOR 01-V-002 FM CLOSE 01-PID-0021-02 / 07 NOTE 1


X
X
THIQAR OIL COMPANY (TOC)

103-LIC-01 LEVEL CONTROL OF DESALTER DEGASSER 01-V-003 FM CLOSE 01-PID-0021-03 / 06 NOTE 1


X
X
DW-1514
Document Code

103-PIC-01 PRESS. CONTROL OF DESALTER DEGASSER 01-V-003 FM OPEN 01-PID-0021-03 NOTE 1


X
X

104-LIC-01 INTERFACE LEVEL CONTROL OF DESALTER 01-V-004 FM CLOSE 01-PID-0021-04 / 10 NOTE 1


X
X
01
Serial n°

107-FIC-01 FLOW CONTROL OF FRESH WATER PUMPS 01-P-002A/S FM CLOSE 01-PID-0021-07 NOTE 1
X
X

108-FIC-01 FLOW CONTROL OF CHARGE PUMPS 01-P-001A/S FM CLOSE 01-PID-0021-08 / 01 NOTE 1


X
X

110-FIC-01 FLOW CONTROL OF RECYCLE WATER PUMPS 01-P-003A/S FM CLOSE 01-PID-0021-10 NOTE 1
X
X
01
Rev.

301-LIC-01 LEVEL CONTROL OF ACCUMULATED WATER TANK 03-V-001 FM CLOSE 03-PID-0021-01 / 03 NOTE 1
X
X
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA

302-PIC-01 PRESS. CONTROL OF PRODUCED WATER FROM TIE-IN 02 FM CLOSE 03-PID-0021-02 SH.1 NOTE 1
X
X

302-LIC-01 INTERFACE LEVEL CONTROL OF COALESCER 03-F-003 FM CLOSE 03-PID-0021-02 SH.2 NOTE 1
X
X
Sheet
3 / 32
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 4 / 32
REV


INTERLOCK ESD-02
DESCRIPTION:

ND

NOTE 1
NOTES
EXISTING 2 STAGE SEPARATOR SHUT-DOWN

NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-08 / 01

01-PID-0021-08

01-PID-0021-08

01-PID-0021-08

01-PID-0021-08
EFFECTS OF INTERLOCK ACTION

FM CLOSE
ACTION

CLOSE

CLOSE

TRIP

TRIP
FLOW CONTROL OF CHARGE PUMPS 01-P-001A/S

ESDV ON DISCHARGE OF PUMPS 01-P-001A/S

ESDV ON BY-PASS OF PUMPS 01-P-001A/S

MOTOR OF CHARGE PUMP 01-P-001A

MOTOR OF CHARGE PUMP 01-P-001S


DESCRIPTION

108-ESDV-01

108-ESDV-03

01-PM-001A

01-PM-001S
108-FIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

108-LALL-90 ND
VERY LOW LIQUID LEVEL IN EXISTING 2 STAGE SEPARATOR MOS 01-PID-0021-08 X X X X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 5 / 32
REV


INTERLOCK ESD-03
DESCRIPTION:

NOTE 1

NOTE 1
SHUT-DOWN DEHYDRATOR DEGASSER 01-V-001

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-02 / 07

01-PID-0021-01 / 03
01-PID-0021-07

01-PID-0021-02

01-PID-0021-02

01-PID-0021-02
EFFECTS OF INTERLOCK ACTION

FM CLOSE

FM CLOSE
ACTION

CLOSE

CLOSE

TRIP

TRIP
INTERFACE LEVEL CONTROL OF DEHYDRATOR 01-V-002

LEVEL CONTROL OF DEHYDRATOR DEGASSER 01-V-001


ESDV ON PRODUCED WATER OUTLET OF 01-E-002

ESDV ON OIL OUTLET OF DEHYDRATOR 01-V-001


DESCRIPTION

DEHYDRATOR TRANSFORMER "B"


DEHYDRATOR TRANSFORMER "A"
107-ESDV-02

102-ESDV-01

102-XST-91

102-XST-92
102-LIC-01

101-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

101-LALL-02 VERY LOW LIQUID LEVEL IN DEHYDRATOR DEGASSER 01-V-001 MOS 01-PID-0021-01 X X X X X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Mod. ST0003_0/xls


REV

NOTES:

TAG N°
DESCRIPTION:

101-LAHH-02
SHUT-DOWN DEHYDRATOR DEGASSER 01-V-001

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

DESCRIPTION

VERY HIGH LIQUID LEVEL IN DEHYDRATOR DEGASSER 01-V-001


MOS
MOS/POS
CAUSES OF INTERLOCK ACTIVATION
VOTING

01-PID-0021-01
P&ID N° / LOCATION
NOTES

EFFECTS OF INTERLOCK ACTION

TAG N° DESCRIPTION ACTION P&ID N° / LOCATION NOTES

401-XST-90 DEMULSIFIER INJECTION PACKAGE TRIP 04-PID-0021-01


X

110-FIC-01 FLOW CONTROL OF RECYCLE WATER PUMPS 01-P-003A/S FM CLOSE 01-PID-0021-10 NOTE 1
X

01-PM-003A MOTOR OF RECYCLE WATER PUMP 01-P-003A TRIP 01-PID-0021-10


X

01-PM-003S MOTOR OF RECYCLE WATER PUMP 01-P-003S TRIP 01-PID-0021-10


X

108-FIC-01 FLOW CONTROL OF CHARGE PUMPS 01-P-001A/S FM CLOSE 01-PID-0021-08 / 01 NOTE 1


X

108-ESDV-01 ESDV ON DISCHARGE OF PUMPS 01-P-001A/S CLOSE 01-PID-0021-08


X

108-ESDV-03 ESDV ON BY-PASS OF PUMPS 01-P-001A/S CLOSE 01-PID-0021-08


X

01-PM-001A MOTOR OF CHARGE PUMP 01-P-001A TRIP 01-PID-0021-08


X

01-PM-001S MOTOR OF CHARGE PUMP 01-P-001S TRIP 01-PID-0021-08


X

03-PM-002A MOTOR OF SUMP PUMP 03-P-002A TRIP 03-PID-0021-04


X
INTERLOCK ESD-04

03-PM-002S MOTOR OF SUMP PUMP 03-P-002S TRIP 03-PID-0021-04


X

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Plant:

Location:
Customer:

Project
PE14017AR
00
Unit
DEGASSING STATION
NASSIRIYA FIELD - IRAQ
THIQAR OIL COMPANY (TOC)

DW-1514
Document Code
01
Serial n°
01
Rev.
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA

Sheet
6 / 32
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 7 / 32
REV


INTERLOCK ESD-05
DESCRIPTION:

NOTE 1
SHUT-DOWN DEHYDRATOR 01-V-002

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-02 / 07

01-PID-0021-07
EFFECTS OF INTERLOCK ACTION

FM CLOSE
ACTION

CLOSE
INTERFACE LEVEL CONTROL OF DEHYDRATOR 01-V-002

ESDV ON PRODUCED WATER OUTLET OF 01-E-002


DESCRIPTION

107-ESDV-02
102-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

102-LALL-02 VERY LOW INTERFACE LEVEL IN DEHYDRATOR 01-V-002 MOS 01-PID-0021-02 X X


Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 8 / 32
REV


INTERLOCK ESD-06
DESCRIPTION:

NOTE 1

NOTE 1
SHUT-DOWN DEHYDRATOR 01-V-002

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-01 / 03

01-PID-0021-02

01-PID-0021-02

01-PID-0021-02

04-PID-0021-01

01-PID-0021-10

01-PID-0021-10

01-PID-0021-10
EFFECTS OF INTERLOCK ACTION

FM CLOSE

FM CLOSE
ACTION

CLOSE

TRIP

TRIP

TRIP

TRIP

TRIP
FLOW CONTROL ON RECYCLE WATER PUMPS 01-P-003A/S
LEVEL CONTROL OF DEHYDRATOR DEGASSER 01-V-001

ESDV ON OIL OUTLET OF DEHYDRATOR 01-V-002

MOTOR OF RECYCLE WATER PUMP 01-P-003A

MOTOR OF RECYCLE WATER PUMP 01-P-003S


DESCRIPTION

DEMULSIFIER INJECTION PACKAGE


DEHYDRATOR TRANSFORMER "B"
DEHYDRATOR TRANSFORMER "A"
102-ESDV-01

01-PM-003A

01-PM-003S
102-XST-91

102-XST-92

401-XST-90

110-FIC-01
101-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

102-LAHH-02 VERY HIGH INTERFACE LEVEL IN DEHYDRATOR 01-V-002 MOS 01-PID-0021-02 X X X X X X X X


Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 9 / 32
REV


INTERLOCK ESD-07
DESCRIPTION:

NOTE 1

NOTE 1
SHUT-DOWN DESALTER DEGASSER 01-V-003

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-04 / 10

01-PID-0021-03 / 06
01-PID-0021-10

01-PID-0021-10

01-PID-0021-04

01-PID-0021-04

01-PID-0021-04
EFFECTS OF INTERLOCK ACTION

FM CLOSE

FM CLOSE
ACTION

CLOSE
TRIP

TRIP

TRIP

TRIP
INTERFACE LEVEL CONTROL OF DESALTER 01-V-004

LEVEL CONTROL OF DESALTER DEGASSER 01-V-003


MOTOR OF RECYCLE WATER PUMP 01-P-003A

MOTOR OF RECYCLE WATER PUMP 01-P-003S

ESDV ON OIL OUTLET OF DESALTER 01-V-004


DESCRIPTION

DESALTER TRANSFORMER "B"


DESALTER TRANSFORMER "A"

104-ESDV-01
01-PM-003A

01-PM-003S

104-XST-91

104-XST-92
104-LIC-01

103-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

103-LALL-02 VERY LOW LIQUID LEVEL IN DESALTER DEGASSER 01-V-003 MOS 01-PID-0021-03 X X X X X X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Mod. ST0003_0/xls


REV

NOTES:

TAG N°
DESCRIPTION:

103-LAHH-02
SHUT-DOWN DESALTER DEGASSER 01-V-003

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

DESCRIPTION

VERY HIGH LIQUID LEVEL IN DESALTER DEGASSER 01-V-003


MOS
MOS/POS
CAUSES OF INTERLOCK ACTIVATION
VOTING

01-PID-0021-03
P&ID N° / LOCATION
NOTES

EFFECTS OF INTERLOCK ACTION

TAG N° DESCRIPTION ACTION P&ID N° / LOCATION NOTES

401-XST-90 DEMULSIFIER INJECTION PACKAGE TRIP 04-PID-0021-01


X

402-XST-90 CORROSION INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-02


X

403-XST-90 SCALE INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-03


X

107-FIC-01 FLOW CONTROL OF FRESH WATER PUMPS 01-P-002A/S FM CLOSE 01-PID-0021-07 NOTE 1
X

107-ESDV-01 ESDV ON DISCHARGE OF PUMPS 01-P-002A/S CLOSE 01-PID-0021-07


X

01-PM-002A MOTOR OF FRESH WATER PUMP 01-P-002A TRIP 01-PID-0021-09


X

01-PM-002S MOTOR OF FRESH WATER PUMP 01-P-002S TRIP 01-PID-0021-09


X

101-LIC-01 LEVEL CONTROL OF DEHYDRATOR DEGASSER 01-V-001 FM CLOSE 01-PID-0021-01 / 03 NOTE 1


X

102-ESDV-01 ESDV ON OIL OUTLET OF DEHYDRATOR 01-V-002 CLOSE 01-PID-0021-02


X
INTERLOCK ESD-08

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Plant:

Location:
Customer:

Project
PE14017AR
00
Unit
DEGASSING STATION
NASSIRIYA FIELD - IRAQ
THIQAR OIL COMPANY (TOC)

DW-1514
Document Code
01
Serial n°
01
Rev.
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA

Sheet
10 / 32
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 11 / 32
REV


INTERLOCK ESD-09
DESCRIPTION:

NOTE 1
SHUT-DOWN DESALTER 01-V-004

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

01-PID-0021-04 / 10

01-PID-0021-10

01-PID-0021-10
EFFECTS OF INTERLOCK ACTION

FM CLOSE
ACTION

TRIP

TRIP
INTERFACE LEVEL CONTROL OF DESALTER 01-V-004

MOTOR OF RECYCLE WATER PUMP 01-P-003A

MOTOR OF RECYCLE WATER PUMP 01-P-003S


DESCRIPTION

01-PM-003A

01-PM-003S
104-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

104-LALL-02 VERY LOW INTERFACE LEVEL IN DESALTER 01-V-004 MOS 01-PID-0021-04 X X X


Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Mod. ST0003_0/xls


REV

NOTES:

TAG N°
DESCRIPTION:

104-LAHH-02
SHUT-DOWN DESALTER 01-V-004

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

VERY HIGH INTERFACE LEVEL IN DESALTER 01-V-004


DESCRIPTION

MOS
MOS/POS
CAUSES OF INTERLOCK ACTIVATION
VOTING

01-PID-0021-04
P&ID N° / LOCATION
NOTES

EFFECTS OF INTERLOCK ACTION

TAG N° DESCRIPTION ACTION P&ID N° / LOCATION NOTES

104-XST-91 DESALTER TRANSFORMER "A" TRIP 01-PID-0021-04


X

104-XST-92 DESALTER TRANSFORMER "B" TRIP 01-PID-0021-04


X

103-LIC-01 LEVEL CONTROL OF DESALTER DEGASSER 01-V-003 FM CLOSE 01-PID-0021-03 / 06 NOTE 1


X

104-ESDV-01 ESDV ON OIL OUTLET OF DESALTER 01-V-004 CLOSE 01-PID-0021-04


X

401-XST-90 DEMULSIFIER INJECTION PACKAGE TRIP 04-PID-0021-01


X

402-XST-90 CORROSION INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-02


X

403-XST-90 SCALE INHIBITOR INJECTION PACKAGE TRIP 04-PID-0021-03


X

107-FIC-01 FLOW CONTROL OF FRESH WATER PUMPS 01-P-002A/S FM CLOSE 01-PID-0021-07 NOTE 1
X

107-ESDV-01 ESDV ON DISCHARGE OF PUMPS 01-P-002A/S CLOSE 01-PID-0021-07


X

01-PM-002A MOTOR OF FRESH WATER PUMP 01-P-002A TRIP 01-PID-0021-09


X
INTERLOCK ESD-10

01-PM-002S MOTOR OF FRESH WATER PUMP 01-P-002S TRIP 01-PID-0021-09


X

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Plant:

Location:
Customer:

Project
PE14017AR
00
Unit
DEGASSING STATION
NASSIRIYA FIELD - IRAQ
THIQAR OIL COMPANY (TOC)

DW-1514
Document Code
01
Serial n°
01
Rev.
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA

Sheet
12 / 32
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 13 / 32
REV


INTERLOCK ESD-11
DESCRIPTION:

SHUT-OFF SUMP PUMPS 03-P-002A/S

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-04

03-PID-0021-04
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP

TRIP
DESCRIPTION

MOTOR OF SUMP PUMP 03-P-002A

MOTOR OF SUMP PUMP 03-P-002S


03-PM-002A

03-PM-002S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

304-LALL-02 VERY LOW LIQUID LEVEL IN SUMP TANK 03-V-002 MOS 03-PID-0021-04 X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 14 / 32
REV


INTERLOCK ESD-12
DESCRIPTION:

NOTE 1
SHUT-DOWN ACCUMULATED WATER TANK 03-V-001

NOTES
NOTES:

1. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

P&ID N° / LOCATION

03-PID-0021-01 / 03

03-PID-0021-03

03-PID-0021-03

03-PID-0021-03
EFFECTS OF INTERLOCK ACTION

FM CLOSE
ACTION

CLOSE

TRIP

TRIP
LEVEL CONTROL OF ACCUMULATED WATER TANK 03-V-001

MOTOR OF EFFLUENT WATER PUMP 01-P-001A

MOTOR OF EFFLUENT WATER PUMP 01-P-001S


ESDV ON DISCHARGE OF PUMPS 03-P-001A/S
DESCRIPTION

303-ESDV-01

03-PM-001A

03-PM-001S
301-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

301-LALL-02 VERY LOW LIQUID LEVEL IN ACCUMULATED WATER TANK 03-V-001 MOS 03-PID-0021-01 X X X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 15 / 32
REV


INTERLOCK ESD-13
DESCRIPTION:

SHUT-DOWN ACCUMULATED WATER TANK 03-V-001

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-02
EFFECTS OF INTERLOCK ACTION

ACTION

CLOSE
ESDV ON WATER OUTLET OF COALESCER 03-F-003
DESCRIPTION

302-ESDV-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

301-LAHH-02 VERY HIGH LIQUID LEVEL IN ACCUMULATED WATER TANK 03-V-001 MOS 03-PID-0021-01 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 16 / 32
REV


INTERLOCK ESD-14
DESCRIPTION:

SHUT-OFF CHARGE PUMPS 01-P-001A

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-08
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF CHARGE PUMP 01-P-001A
DESCRIPTION

01-PM-001A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

108-PALL-02 VERY LOW SUCTION PRESSURE ON CHARGE PUMP 01-P-001A MOS 01-PID-0021-08 X
108-PALL-04 VERY LOW DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001A MOS / POS 01-PID-0021-08 X
108-PAHH-04 VERY HIGH DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001A MOS 01-PID-0021-08 X
108-TAHH-01AA VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01AB VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01AC VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01AD VERY HIGH TEMPERATURE IN MOTOR BEARING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01AE VERY HIGH TEMPERATURE IN MOTOR BEARING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01AF VERY HIGH TEMPERATURE IN PUMP BEARING OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-VAHH-01AA VERY HIGH VIBRATION OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
108-VAHH-01AB VERY HIGH VIBRATION OF CHARGE PUMP 01-P-001A MOS 00-PID-0021-01 Sh.4of4 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 17 / 32
REV


INTERLOCK ESD-15
DESCRIPTION:

SHUT-OFF CHARGE PUMPS 01-P-001S

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-08
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF CHARGE PUMP 01-P-001S
DESCRIPTION

01-PM-001S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

108-PALL-03 VERY LOW SUCTION PRESSURE ON CHARGE PUMP 01-P-001S MOS 01-PID-0021-08 X
108-PALL-05 VERY LOW DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001S MOS / POS 01-PID-0021-08 X
108-PAHH-05 VERY HIGH DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001S MOS 01-PID-0021-08 X
108-TAHH-01SA VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01SB VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01SC VERY HIGH TEMPERATURE IN MOTOR WINDING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01SD VERY HIGH TEMPERATURE IN MOTOR BEARING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01SE VERY HIGH TEMPERATURE IN MOTOR BEARING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-TAHH-01SF VERY HIGH TEMPERATURE IN PUMP BEARING OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-VAHH-01SA VERY HIGH VIBRATION OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
108-VAHH-01SB VERY HIGH VIBRATION OF CHARGE PUMP 01-P-001S MOS 00-PID-0021-01 Sh.4of4 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 18 / 32
REV


INTERLOCK ESD-16
DESCRIPTION:

SHUT-OFF CHARGE PUMPS 01-P-001A/S

NOTES
NOTES:

1. "AND" LOGIC TO BE CONSIDERED. ACTION WILL OCCUR ONLY IF NONE OF THE INVOLVED SIGNALS ARE AVAILABLE.

P&ID N° / LOCATION

01-PID-0021-08

01-PID-0021-08

01-PID-0021-08
2. EVENT SHALL LAST FOR FIVE (5) SECONDS BEFORE SIGNAL IS GNEREATED. GENERATED SIGNAL IS "IMPULSE" TYPE.

EFFECTS OF INTERLOCK ACTION


3. RESET ACKNOWLEDGE REQUIRED.

4. POS RESET SHALL BE ACTIVATED WHEN EITHER 108-PIT-04 or 108-PIT-05 RETURN TO NORMAL OPERATING CONDITION (i.e. "1oo2" VOTING).

5. BOTH 108-PIT-04 AND 108-PIT-05 SHALL BE FORESEEN WITH INDIVIDUAL POS AND MOS.

6. VOLUNTARY COMMAND BY OPERATOR TO BYPASS CHARGE PUMPS

ACTION

CLOSE

CLOSE

OPEN
ESDV ON DISCHARGE OF PUMPS 01-P-001A/S

ESDV ON SUCTION OF PUMPS 01-P-001A/S

ESDV ON BY-PASS OF PUMPS 01-P-001A/S


DESCRIPTION

108-ESDV-01

108-ESDV-02

108-ESDV-03
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

108-PALL-04 VERY LOW DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001A 01-PID-0021-08


Note 4
Note 5
2oo2 NOTE 1,2,3 X X X
108-PALL-05 VERY LOW DISCHARGE PRESSURE ON CHARGE PUMP 01-P-001S 01-PID-0021-08

108-HS-01 CHARGE PUMPS 01-P-001A/S BYPASS Note 6 01-PID-0021-08 X X X


Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 19 / 32
REV


INTERLOCK ESD-17
DESCRIPTION:

SHUT-OFF FRESH WATER PUMPS 01-P-002A

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-09
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF FRESH WATER PUMP 01-P-002A
DESCRIPTION

01-PM-002A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

109-PALL-03 VERY LOW SUCTION PRESSURE ON FRESH WATER PUMP 01-P-002A MOS 01-PID-0021-09 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 20 / 32
REV


INTERLOCK ESD-18
DESCRIPTION:

SHUT-OFF FRESH WATER PUMPS 01-P-002S

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-09
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF FRESH WATER PUMP 01-P-002S
DESCRIPTION

01-PM-002S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

109-PALL-04 VERY LOW SUCTION PRESSURE ON FRESH WATER PUMP 01-P-002S MOS 01-PID-0021-09 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 21 / 32
REV


INTERLOCK ESD-19
DESCRIPTION:

NOTE 3
SHUT-OFF FRESH WATER PUMPS 01-P-002A/S

NOTES
NOTES:

1. EVENT SHALL LAST FOR FIVE (5) SECONDS BEFORE SIGNAL IS GNEREATED. GENERATED SIGNAL IS "IMPULSE" TYPE.

P&ID N° / LOCATION

01-PID-0021-09

01-PID-0021-09

01-PID-0021-07

01-PID-0021-07
2. RESET ACKNOWLEDGE REQUIRED.

EFFECTS OF INTERLOCK ACTION


3. CONTROL LOOP SOFTWARE SHUT-DOWN (MANUAL TO ZERO)

FM CLOSE
ACTION

CLOSE
TRIP

TRIP

FLOW CONTROL OF FRESH WATER PUMPS 01-P-002A/S

ESDV ON DISCHARGE OF PUMPS 01-P-002A/S


MOTOR OF FRESH WATER PUMP 01-P-002A

MOTOR OF FRESH WATER PUMP 01-P-002S


DESCRIPTION

107-ESDV-01
01-PM-002A

01-PM-002S

107-FIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

109-PALL-05 VERY LOW DISCHARGE PRESSURE ON FRESH WATER PUMP 01-P-002A/S MOS / POS 01-PID-0021-09 NOTES 1,2 X X X X
109-PAHH-05 VERY HIGH DISCHARGE PRESSURE ON FRESH WATER PUMP 01-P-002A/S MOS 01-PID-0021-09 NOTES 1,2 X X X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 22 / 32
REV


INTERLOCK ESD-20
DESCRIPTION:

SHUT-OFF RECYCLE WATER PUMPS 01-P-003A

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-10
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF RECYCLE WATER PUMP 01-P-003A
DESCRIPTION

01-PM-003A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

110-PALL-01 VERY LOW SUCTION PRESSURE ON RECYCLE WATER PUMP 01-P-003A MOS 01-PID-0021-10 X
110-PALL-04 VERY LOW DISCHARGE PRESSURE ON RECYCLE WATER PUMP 01-P-003A MOS / POS 01-PID-0021-10 X
110-PAHH-04 VERY HIGH DISCHARGE PRESSURE ON RECYCLE PUMP 01-P-003A MOS 01-PID-0021-10 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 23 / 32
REV


INTERLOCK ESD-21
DESCRIPTION:

SHUT-OFF RECYCLE WATER PUMPS 01-P-003S

NOTES
NOTES:

P&ID N° / LOCATION

01-PID-0021-10
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF RECYCLE WATER PUMP 01-P-003S
DESCRIPTION

01-PM-003S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

110-PALL-02 VERY LOW SUCTION PRESSURE ON RECYCLE WATER PUMP 01-P-003S MOS 01-PID-0021-10 X
110-PALL-05 VERY LOW DISCHARGE PRESSURE ON RECYCLE WATER PUMP 01-P-003S MOS 01-PID-0021-10 X
110-PAHH-05 VERY HIGH DISCHARGE PRESSURE ON RECYCLE WATER PUMP 01-P-003S MOS 01-PID-0021-10 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 24 / 32
REV


INTERLOCK ESD-22
DESCRIPTION:

SHUT-OFF RECYCLE WATER PUMPS 01-P-003A/S

NOTES
NOTES:

1. "AND" LOGIC TO BE CONSIDERED. ACTION WILL OCCUR ONLY IF NONE OF THE INVOLVED SIGNALS ARE AVAILABLE.

P&ID N° / LOCATION

01-PID-0021-10
2. EVENT SHALL LAST FOR FIVE (5) SECONDS BEFORE SIGNAL IS GNEREATED. GENERATED SIGNAL IS "IMPULSE" TYPE.

EFFECTS OF INTERLOCK ACTION


3. RESET ACKNOWLEDGE REQUIRED.

4. POS RESET SHALL BE ACTIVATED WHEN EITHER 110-PIT-04 or 110-PIT-05 RETURN TO NORMAL OPERATING CONDITION (i.e. "1oo2" VOTING).

5. BOTH 110-PIT-04 AND 110-PIT-05 SHALL BE FORESEEN WITH INDIVIDUAL POS AND MOS.

FM CLOSE
ACTION

FLOW CONTROL OF RECYCLE WATER PUMPS 01-P-003A/S


DESCRIPTION

110-FIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

110-PALL-04 VERY LOW DISCHARGE PRESSURE ON RECYCLE WATER PUMP 01-P-003A


NOTE 4,5 2oo2 01-PID-0021-10 NOTE 1,2,3 X
110-PALL-05 VERY LOW DISCHARGE PRESSURE ON RECYCLE WATER PUMP 01-P-003S
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 25 / 32
REV


INTERLOCK ESD-23
DESCRIPTION:

SHUT-OFF DRAIN PUMPS 02-P-001A

NOTES
NOTES:

P&ID N° / LOCATION

02-PID-0021-01
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
DESCRIPTION

MOTOR OF DRAIN PUMP 02-P-001A


02-PM-001A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

201-PALL-03 VERY LOW SUCTION PRESSURE ON DRAIN PUMP 02-P-001A MOS 02-PID-0021-01 X
201-PALL-04 VERY LOW DISCHARGE PRESSURE ON DRAIN PUMP 02-P-001A MOS / POS 02-PID-0021-01 X
201-PAHH-04 VERY HIGH DISCHARGE PRESSURE ON DRAIN PUMP 02-P-001A MOS 02-PID-0021-01 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 26 / 32
REV


INTERLOCK ESD-24
DESCRIPTION:

SHUT-OFF DRAIN PUMPS 02-P-001S

NOTES
NOTES:

P&ID N° / LOCATION

02-PID-0021-01
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
DESCRIPTION

MOTOR OF DRAIN PUMP 02-P-001S


02-PM-001S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

201-PALL-01 VERY LOW SUCTION PRESSURE ON DRAIN PUMP 02-P-001S MOS 02-PID-0021-01 X
201-PALL-05 VERY LOW DISCHARGE PRESSURE ON DRAIN PUMP 02-P-001S MOS / POS 02-PID-0021-01 X
201-PAHH-05 VERY HIGH DISCHARGE PRESSURE ON DRAIN PUMP 02-P-001S MOS 02-PID-0021-01 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 27 / 32
REV


INTERLOCK ESD-25
DESCRIPTION:

SHUT-OFF DRAIN PUMPS 02-P-001A/S

NOTES
NOTES:

P&ID N° / LOCATION

02-PID-0021-01

02-PID-0021-01
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP

TRIP
DESCRIPTION

MOTOR OF DRAIN PUMP 02-P-001A

MOTOR OF DRAIN PUMP 02-P-001S


02-PM-001A

02-PM-001S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

201-LALL-02 VERY LOW LIQUID LEVEL IN CLOSED DRAIN DRUM 02-V-001 MOS 02-PID-0021-01 X X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 28 / 32
REV


INTERLOCK ESD-26
DESCRIPTION:

SHUT-OFF EFFLUENT WATER PUMPS 03-P-001A

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-03
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF EFFLUENT WATER PUMP 03-P-001A
DESCRIPTION

03-PM-001A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

303-PALL-02 VERY LOW SUCTION PRESSURE ON EFFLUENT WATER PUMP 03-P-001A MOS 03-PID-0021-03 X
303-PALL-04 VERY LOW DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001A MOS / POS 03-PID-0021-03 X
303-PAHH-04 VERY HIGH DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001A MOS 03-PID-0021-03 X
303-TAHH-01AA VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AB VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AC VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AD VERY HIGH TEMPERATURE IN MOTOR BEARING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AE VERY HIGH TEMPERATURE IN MOTOR BEARING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AF VERY HIGH TEMPERATURE IN PUMP BEARING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01AG VERY HIGH TEMPERATURE IN PUMP BEARING OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01AA VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01AB VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01AC VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01AD VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001A MOS 00-PID-0021-01 Sh.4of4 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 29 / 32
REV


INTERLOCK ESD-27
DESCRIPTION:

SHUT-OFF EFFLUENT WATER PUMPS 03-P-001S

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-03
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
MOTOR OF EFFLUENT WATER PUMP 03-P-001S
DESCRIPTION

03-PM-001S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

303-PALL-03 VERY LOW SUCTION PRESSURE ON EFFLUENT WATER PUMP 03-P-001S MOS 03-PID-0021-03 X
303-PALL-05 VERY LOW DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001S MOS / POS 03-PID-0021-03 X
303-PAHH-05 VERY HIGH DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001S MOS 03-PID-0021-03 X
303-TAHH-01SA VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SB VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SC VERY HIGH TEMPERATURE IN MOTOR WINDING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SD VERY HIGH TEMPERATURE IN MOTOR BEARING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SE VERY HIGH TEMPERATURE IN MOTOR BEARING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SF VERY HIGH TEMPERATURE IN PUMP BEARING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-TAHH-01SG VERY HIGH TEMPERATURE IN PUMP BEARING OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01SA VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01SB VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01SC VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
303-VAHH-01SD VERY HIGH VIBRATION OF EFFLUENT WATER PUMP 03-P-001S MOS 00-PID-0021-01 Sh.4of4 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 30 / 32
REV


INTERLOCK ESD-28
DESCRIPTION:

NOTE 4
SHUT-OFF EFFLUENT WATER PUMPS 03-P-001A/S

NOTES
NOTES:

1. "AND" LOGIC TO BE CONSIDERED. ACTION WILL OCCUR ONLY IF NONE OF THE INVOLVED SIGNALS ARE AVAILABLE.

P&ID N° / LOCATION

03-PID-0021-01

03-PID-0021-03
2. EVENT SHALL LAST FOR FIVE (5) SECONDS BEFORE SIGNAL IS GNEREATED. GENERATED SIGNAL IS "IMPULSE" TYPE.

EFFECTS OF INTERLOCK ACTION


3. RESET ACKNOWLEDGE REQUIRED.

4. POS RESET SHALL BE ACTIVATED WHEN EITHER 303-PIT-04 or 303-PIT-05 RETURN TO NORMAL OPERATING CONDITION (i.e. "1oo2" VOTING).

5. BOTH 303-PIT-04 AND 303-PIT-05 SHALL BE FORESEEN WITH INDIVIDUAL POS AND MOS.

FM CLOSE
ACTION

CLOSE
LEVEL CONTROL OF ACCUMULATED WATER TANK 03-V-001

ESDV ON DISCHARGE OF PUMPS 03-P-001A/S


DESCRIPTION

303-ESDV-01
301-LIC-01
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

303-PALL-04 VERY LOW DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001A 03-PID-0021-03
NOTE 4,5 2oo2 NOTE 1,2,3 X X
303-PALL-05 VERY LOW DISCHARGE PRESSURE ON EFFLUENT WATER PUMP 03-P-001S 03-PID-0021-03
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 31 / 32
REV


INTERLOCK ESD-29
DESCRIPTION:

SHUT-OFF SUMP PUMPS 03-P-002A

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-04
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
DESCRIPTION

MOTOR OF SUMP PUMP 03-P-002A


03-PM-002A
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

304-PALL-04 VERY LOW SUCTION PRESSURE ON SUMP PUMP 03-P-002A MOS 03-PID-0021-04 X
304-PALL-02 VERY LOW DISCHARGE PRESSURE ON SUMP PUMP 03-P-002A MOS / POS 03-PID-0021-04 X
304-PAHH-02 VERY HIGH DISCHARGE PRESSURE ON SUMP PUMP 03-P-002A MOS 03-PID-0021-04 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.
Customer: THIQAR OIL COMPANY (TOC)
DEHYDRATION AND DESALTING UNIT FOR NASSIRIYA
Plant:
DEGASSING STATION
Location: NASSIRIYA FIELD - IRAQ
Project Unit Document Code Serial n° Rev. Sheet
PE14017AR 00 DW-1514 01 01 32 / 32
REV


INTERLOCK ESD-30
DESCRIPTION:

SHUT-OFF SUMP PUMPS 03-P-002S

NOTES
NOTES:

P&ID N° / LOCATION

03-PID-0021-04
EFFECTS OF INTERLOCK ACTION

ACTION

TRIP
DESCRIPTION

MOTOR OF SUMP PUMP 03-P-002S


03-PM-002S
TAG N°
CAUSES OF INTERLOCK ACTIVATION
TAG N° DESCRIPTION MOS/POS VOTING P&ID N° / LOCATION NOTES

304-PALL-05 VERY LOW SUCTION PRESSURE ON SUMP PUMP 03-P-002S MOS 03-PID-0021-04 X
304-PALL-03 VERY LOW DISCHARGE PRESSURE ON SUMP PUMP 03-P-002S MOS / POS 03-PID-0021-04 X
304-PAHH-03 VERY HIGH DISCHARGE PRESSURE ON SUMP PUMP 03-P-002S MOS 03-PID-0021-04 X
Mod. ST0003_0/xls

This document is property of Progetti Europa & Global S.p.A. Roma, it may not be copied, reproduced and/or circulated without PEG’s authorization.